69
/
96
Parameter
Description
Value range and dependencies
Factory setting
Access level Read
Access level Write
Re-start
required
1-3-5-3
Selection of thermometer function
Ambient temperature
Ambient temperature Everybody
Service
-
Water temperature
1-3-7
Calibration
-
-
-
-
-
1-3-7-1
Sensors
-
-
-
-
-
1-3-7-1-1
Pressure sensor on suction side
-
-
-
-
-
1-3-7-1-1-1
Value at 4 mA
0 … value at 20 mA
0
Everybody
Service
-
1-3-7-1-1-2
Value at 20 mA
Value at 0/4 mA … 100 bar
10 bar
Everybody
Service
-
1-3-7-1-2
Pressure sensor on discharge side
-
-
-
-
-
1-3-7-1-2-1
Value at 4 mA
0 … value at 20 mA
0
Everybody
Service
-
1-3-7-1-2-2
Value at 20 mA
Value at 0/4 mA … 100 bar
16 bar
Everybody
Service
-
1-3-7-1-3
Pressure sensor at tank
-
-
-
-
-
1-3-7-1-3-1
Value at 4 mA
0 … value at 20 mA
0
Everybody
Service
-
1-3-7-1-3-2
Value at 20 mA
Value at 0/4 mA … 10 bar
0.306 bar
Everybody
Service
-
1-3-7-1-4
Setpoint
-
-
-
-
-
1-3-7-1-4-1
Value at 4 mA
0 … value at 20 mA
0
Everybody
Service
-
1-3-7-1-4-2
Value at 20 mA
Value at 0/4 mA … 100 bar
16 bar
Everybody
Service
-
1-3-7-2
Output signal
-
-
-
-
-
1-3-7-2-1
Suction-side pressure
-
-
-
-
-
1-3-7-2-1-1
Selection of output current range
0 … 20 mA
4 mA … 20 mA
Everybody
Service
-
4 mA … 20 mA
1-3-7-2-1-2
Value at 0/4 mA
If selection … = 0 mA … 20 mA
0 … value at 20 mA
Everybody
Service
-
1-3-7-2-1-3
Value at 20 mA
-
Value at 0/4 mA …
100 bar
Everybody
Service
-
1-3-7-2-2
Discharge-side pressure
-
-
-
-
-
1-3-7-2-2-1
Selection of output current range
0 … 20 mA
4 mA … 20 mA
Everybody
Service
-
4 mA … 20 mA
1-3-7-2-2-2
Value at 0/4 mA
If selection … = 0 mA … 20 mA
0 … value at 20 mA
Everybody
Service
-
1-3-7-2-2-3
Value at 20 mA
-
-
Everybody
Service
-
1-3-7-2-4
Tank fill level
-
-
-
-
-
1-3-7-2-4-1
Selection of output current range
0 … 20 mA
4 mA … 20 mA
Everybody
Service
-
4 mA … 20 mA
1-3-7-2-4-2
Value at 0/4 mA
If selection … = 0 mA … 20 mA
0 … value at 20 mA
Everybody
Service
-
1-3-7-2-4-3
Value at 20 mA
-
Value at 0/4 mA …
100 bar
Everybody
Service
-
Содержание Hydro-Unit Utility Line F