the PLC is the center of the HPVC control panel .  the PLC 
interprets the signal from the probe, sets the timing of the 
pumping sequence, monitors for common problems, and 
provides  diagnostic  feedback  to  an  operator  the  ensure 
maximum  reliability  and  up-time .  Very  little  physical 
interaction  with  the  PLC  is  required  as  most  common 
adjustments to the pump are made from the exterior of the 
control panel .  During normal operation; the PLC display 
will display the discharge timer value, probe value, and 
pump status .

the  discharge  timer  value  is  the  amount  of  time  (in 
seconds)  that  the  pump  will  spend  in  discharge  mode 
after receiving the signal from the probe .  the discharge 
timer value can be easily adjusted with the potentiometer 
located  on  the  right  side  of  the  control  panel .    the 
discharge timer has a maximum value of 10 seconds and 
a minimum value of 1/10th of a second .

the probe value is a measure of continuity of the product 
being  pumped,  measured  between  the  tip  of  the  probe 
and the reservoir tube .  the range has a maximum value 
of 1024 and a minimum value of 0 .  typically, a very low 
number  indicates  that  the  probe  is  not  in  contact  with 
the  product  being  pumped  (reservoir  tube  is  empty) .  
typically, a high number would indicate that product is in 
contact with the probe (reservoir tube is full) . In the above 
figure  a  value  of  2  is  being  displayed  meaning  that  the 
pump is empty of product .

the pump status alerts the operator to the current status of 
the pump .  the status will change from “off” to “suction” 
or “discharge” depending on the position of the run/purge 
switch (located on the right side of the control panel) and 
the pumps current position in the pumping sequence . the 
status will indicate “waiting” when downstream control 
of  the  pump  is  used  and  product  is  no  longer  needed 
from the pump .

the adjustable probe

During  operation,  certain  products  can  coat  the  sensor 
probe  creating  false  inputs  to  the  control  panel  and 
causing poor performance .  Periodic cleaning of the sensor 
probe may be required in certain applications to maintain 
reliability .   to  decrease  the  frequency  of  cleanings,  the 
HPVC control panel has an adjustable probe set point .  this 
set point can be changed on the fly to offset the effects of 
product build-up on the sensor probe during operation .  
to adjust the probe set point, follow these steps:

 Write  down  the  probe  value  (displayed  on  the  PLC) 

1 . 

when the reservoir tube of the pump is empty . use the 
manual discharge switch to ensure the pump is empty .  
this value should be close to zero .  A reading higher than 
0 (ex . 100) indicates that the probe has some fouling 
and that the set point can be adjusted to compensate .  
An extremely high reading while the pump is empty 
(ex . 500) indicates that the probe is heavily fouled and 
should be cleaned before proceeding .  After recording 
this value proceed to step 2 .

 Write down the probe value when the reservoir tube 

2 . 

of the pump is full and the probe is in contact with the 
product .  to accomplish this, watch the PCL display, use 
the run switch to jog the pump until the probe value 
jumps significantly (ex . 600) .  this indicates the probe 
has  made  contact  with  the  product  being  pumped . 
record this number and proceed to step 3 .

 using the two numbers you’ve written down, subtract 

3 . 

the  low  value  from  the  high  value  and  divide  the 
remainder by two . the quotient is our new probe set 
point .  record this number and proceed to step 4 .

 From the PLC display, press the info button and release .  

4 . 

A new screen will be displayed requiring a password 
to proceed .  enter the password “3433” then press the 
enter button and release .

S e c t i o n   5

s u g g E s T E d   o P E R A T i o n   &   M A i n T E n A n c E

the plc:

a

b

e

– Timer Value     

– Probe Value     

– Pump Status

– Info Button     

– Enter Button

d

c

s u g g E s T E d   i n s T A L L A T i o n

6

WILDEN PUMP & ENGINEERING CO., LLC

WIL-12120-E-01

Содержание WILDEN Saniflo VC4

Страница 1: ...R e f i n e y o u r p r o c e s s Engineering Opera ti o n Maint e n a n ce Saniflo Series METAL Pumps VC4 VC6 VC8 WIL 12120 E 01 ...

Страница 2: ...ribution System 3 Section 4 Dimensional Drawings 4 Section 5 Suggested INSTALLATION OPERATION TROUBLESHOOTING 5 Section 6 Assembly 9 Section 7 Exploded View Parts Listing sANIFLOtm VC4 12 sANIFLOtm VC6 14 sANIFLOTM VC8 16 VC Pump controller 18 Section 8 vc pump controller schematic 20 ta b le o f c o n te n t s ...

Страница 3: ... CAUTION The Saniflo VC pump is not submersible Mount control panel where it is not directly in the wash down area CAUTION Always wear safety glasses when operat ing pump If rupture of wetted components occurs material being pumped may be forced from pump and may create a hazardous situation CAUTION Before any maintenance or repair is attempted the compressed air line to the pump should be disconn...

Страница 4: ...Designation Max Solids Passage Inlet Dim Outlet Dim Est Shipping Wt 81 1000 VC4 SS SS FB 76 2 mm 3 76 mm 3 76 mm 3 41 7 kg 92 lbs 81 1002 VC4 SS SS TF 76 2 mm 3 76 mm 3 76 mm 3 41 7 kg 92 lbs 81 1004 VC6 SS SS FB 101 6 mm 4 102 mm 4 102 mm 4 48 9 kg 108 lbs 81 1006 VC6 SS SS TF 101 6 mm 4 102 mm 4 102 mm 4 48 9 kg 108 lbs 81 1008 VC8 SS SS FB 152 4 mm 6 125 mm 6 125 mm 4 69 9 kg 154 lbs 81 1010 VC...

Страница 5: ...ay from the internal vacuum generator s and directed into the vertical column of the pump Once the compressed air is supplied to the top of the process medium the hydraulic force will discharge the pro cess medium from the vertical column These same forces will close the inlet flap valve and open the discharge flap valve simultaneously causing the pro cess medium to move downstream FIGURE 3 The di...

Страница 6: ...381 15 C 157 6 18 N A N A N A N A D 304 12 304 12 304 12 E 101 4 152 6 203 8 F 1486 58 50 1505 59 25 1559 61 38 G 76 3 101 4 102 4 H 76 3 101 4 152 6 J 254 10 254 10 254 10 K 436 17 18 555 21 87 647 25 50 L 352 13 87 352 13 87 352 13 87 S e c t i o n 4 DI M E NSION A L D R A W INGS S A NI F L O T M V C REV A 4 WILDEN PUMP ENGINEERING CO LLC WIL 12120 E 01 ...

Страница 7: ... including pumping distance required flow rate product viscosity and piping size ELECTRICAL The control panel requires 120 220VAC at 1 amps ELEVATION Selecting a site that is well within the pump s dynamic lift capability will assure that loss of prime troubles will be eliminated In addition pump efficiency can be adversely effected if proper attention is not given to site location PIPING Final de...

Страница 8: ... from the pump The Adjustable Probe During operation certain products can coat the sensor probe creating false inputs to the control panel and causing poor performance Periodic cleaning of the sensor probe may be required in certain applications to maintain reliability To decrease the frequency of cleanings the HPVC control panel has an adjustable probe set point This set point can be changed on t...

Страница 9: ... be displayed until the condition is corrected and the pump control is reset This screen alerts the operator to the nature of the problem and provides instructions to solve the problem and restart the pump This screen indicates that product has been in contact with the probe for a period of time that was unexpectedly long To identify the cause the operator should make sure that Air shut off valve ...

Страница 10: ...ow or no air pressure 2 Air valves not functioning properly 3 Dirty or defective vacuum generator 4 Loose connection on piping 5 Check valves misaligned 6 Solution Manually discharge the pump for 2 seconds to clear 1 any blockage If this does not help disassemble the pump and clear the check valves Turn up suction regulator to 5 bar 75 PSI 2 Check to ensure that the air supply is adequate 3 Disass...

Страница 11: ... 2 Begin assembly by installing the flange gasket and inlet flap valve housing to pump base After joining components secure with clamp band NOTE When installing inlet flap valve housing ensure that hinged portion of flap valve is located in the up position by utilizing the UP reference mark on the inlet housing Figure 2 Step 3 Figure 3 Position flange gasket and discharge flap valve housing to pum...

Страница 12: ...ons correctly g Run purge switch functions correctly h Valves function correctly i Pump Cleaning Procedure Empty the discharge piping of product using the 1 purge switch on the control panel Disconnect inlet and outlet piping from the pump 2 keeping clamps and gaskets in a secure place Remove sensor cap and diffuser screen from 3 pump and place them on the sensor cap storage bracket keeping the cl...

Страница 13: ... to the off position and 4 attach a proper lockout device After attaching the lockout devices put the keys in 5 your pocket After locking out the electrical and air supplies try to 6 start the pump to verify that it is properly disabled If the pump starts or still has power applied stop and get your supervisors help Release any stored air in the pump by turning the 7 regulator adjusting knobs full...

Страница 14: ...S e c t i o n 7 E x pl o d e d V i ew P art s L i s t i n g 6 6 6 5 1 2 4 5 3 5 5 SANIFLOTM VC4 E X P L OD E D V I E W 12 WILDEN PUMP ENGINEERING CO LLC WIL 12120 E 01 ...

Страница 15: ...Inlet Check 3 x 3 1 80 0144 80 0144 3 Valve Outlet 4 x 3 Reducer 1 80 0145 80 0145 4 Base 4 Pump 1 80 0084 80 0084 5 Gasket 4 FB Buna 4 N A 80 0101 5 Gasket 4 Teflon 4 80 0152 N A 6 Clamp 4 H D 4 80 0089 80 0089 E x pl o d e d V i ew P art s L i s t i n g SANIFLOTM VC4 part s l i s t i n g 13 WILDEN PUMP ENGINEERING CO LLC WIL 12120 E 01 ...

Страница 16: ...7 5 1 8 8 6 8 6 2 4 3 6 S e c t i o n 8 E x pl o d e d V i ew P art s L i s t i n g SANIFLOTM VC6 E X P L OD E D V I E W 14 WILDEN PUMP ENGINEERING CO LLC WIL 12120 E 01 ...

Страница 17: ...t 6 x 4 Reducer 1 80 0147 80 0147 4 Base 6 Pump 1 80 0085 80 0085 5 Gasket 4 FB Buna 1 N A 80 0101 5 Gasket 4 Teflon 1 80 0152 N A 6 Gasket 6 FB Buna 3 N A 80 0102 6 Gasket 6 Teflon 3 80 0153 N A 7 Clamp 4 HD 1 80 0089 80 0089 8 Clamp 6 HD 3 80 0090 80 0090 E x pl o d e d V i ew P art s L i s t i n g SANIFLOTM VC6 part s l i s t i n g 15 WILDEN PUMP ENGINEERING CO LLC WIL 12120 E 01 ...

Страница 18: ...1 7 5 3 6 8 2 4 6 8 8 6 S e c t i o n 8 E x pl o d e d V i ew P art s L i s t i n g SANIFLOTM VC8 E X P L OD E D V I E W 16 WILDEN PUMP ENGINEERING CO LLC WIL 12120 E 01 ...

Страница 19: ...t 4 Teflon 1 80 0152 N A 6 Gasket 8 FB Buna 3 80 0151 80 0151 6 Gasket 8 Teflon 3 80 0154 80 0154 7 Clamp 4 H D 1 80 0089 80 0089 8 Clamp 8 H D 3 80 0150 80 0150 NOTE The VC8 pump is also available with a 152 mm 6 pump discharge connection To order this other option use item number 81 1011 To order an 8 x 6 outlet reducer for a VC8 pump use item number 81 0149 E x pl o d e d V i ew P art s L i s t...

Страница 20: ...S e c t i o n 8 E x p l o d e d V i e w Pa r t s L i s t i n g vc pump controller E XP L OD E D V I E W 18 WILDEN PUMP ENGINEERING CO LLC WIL 12120 E 01 ...

Страница 21: ...GULATOR GAUGE 28 1 81 12153 8 VACUUM GENERATOR 29 1 81 12286 VACUUM GENERATOR GAUGE 30 1 81 12287 VACUUM GENERATOR MUFFLER 31 1 81 17792 1 4 NPT X 1 4 TUBE SWIVEL 90 32 1 81 12206 SS 1 4 STREET ELL 33 1 81 10938 SS 1 4 CLOSE NIPPLE 34 2 81 11900 SS 1 2 X 1 4 BUSHING 35 3 81 18348 SS 1 2 CLOSE NIPPLE 36 1 81 12497 SS 1 2 CROSS 37 1 81 13883 SS 1 2 BALL VALVE 38 1 81 17779 1 2 NPT X 1 2 TUBE STRAIGH...

Страница 22: ...S e c t i o n 8 v c p u mp c o n tr o ller s c hemat i c 20 WILDEN PUMP ENGINEERING CO LLC WIL 12120 E 01 ...

Страница 23: ...comes first Failure due to normal wear misapplication or abuse is of course excluded from this warranty Since the use of Wilden pumps and parts is beyond our control we cannot guarantee the suitability of any pump or part for a particular application and Wilden Pump and Engineering LLC shall not be liable for any consequential damage or expense arising from the use or misuse of its products on any...

Страница 24: ...nce The result of advanced thought Refine Your Process Designed for sanitary applications Minimize product degradation Improved production yields Easy to inspect clean assemble Minimized water requirements The result of progressive thought Simplify Your Process Maximize Your Process Electronic control monitoring Level control containment Pulsation dampening Drum unloading systems Complete system s...

Отзывы: