Rack Monitor 8800E/8801E
Document: Installation Manual
Date:
24 August 2016
Version: B.1
Page 23 of 29
Document: H71342
Another typical configuration is shown below.
Instead of flameproof cable glands Explosion proof seals are used.
Read the installation manual of the explosion proof seals carefully to avoid dangerous situations.
Notes:
1.
–Control Equipment and Electrical Apparatus connected to the 8800E / 8801E Rack
monitor should NOT use or generate more than 250 Volts AC.
2.
–Installation should be in accordance with Electrical installations in hazardous areas
EN60079-14, EN50281 VDE-0165,NEC ANSI/NFPA 70 and ANSI/ISA RP12.6.
In Canada, the system must be installed in accordance with the Canadian Electrical
Code, CEC Part 1 and/or in accordance with all national and local regulations
(codes) for installation of electrical equipment.
3.
–
Explosion-proof seals must be within xx inches of the enclosure.
of the enclosure.
4.
–Only certified cable-glands (M20x1.5) for flameproof enclosure may be used.
5.
–Only 4 seals may be used to connect the 8800E/8801E Rack Monitor.
Consult API Socket and Sensor drawings for detailed information.
Figure 21