5.
If there is a configuration for the component present on the Programmer: Select whether
the configuration on the Programmer should be overwritten.
6.
If there is a traceback present on the component:
Select whether the traceback should be read.
Select whether a traceback of this component stored on the Programmer should be
overwritten.
7.
The component is initialized for LEGIC:
Confirm overwriting of the initialization of the component.
8. The component is connected to a wireless gateway:
Confirm ending the connection to the gateway. The component has to be connected
afresh after the update.
ð
The configuration is saved on the Programmer.
ð
An INI reset is performed.
ð
The selected firmware is stored in the component.
ð
The component is restarted with the new firmware.
9.
Upon request, make the master available again.
ð
The configuration is transferred back to the component.
Check for success with a valid user medium.
Components not configured
If the firmware of a component that is not configured is to be updated:
1.
Connect the Programmer to the component using the programming cable.
2.
On the Programmer, select the ‘Firmware update’ menu.
ð
All the firmware versions for the connected component are displayed.
3.
Select the firmware.
ð
The update process is started.
ð
The selected firmware is stored in the component.
ð
The component is restarted with the new firmware.
ð
The firmware update is completed.
5.6.2 Crossgrade for LEGIC advant components
An upgrade to E300 (V4) is recommended for elolegic U line (U300) or N line (N300)
standalone components.
5.6.2.1 V3 upgrade to E300 (V4)
The upgrade can only be carried out on evolo standalone actuators.
evolo standalone actuators (MRD) can be started directly in the bootloader by short-
circuiting the INI reset contacts (provided no master is programmed before).
1.
Starting actuator in the bootloader.
c-lever:
Short-circuit the INI reset contacts on the actuator (10 s).
c-lever compact or digital cylinder:
a) Log in with the authorised medium before the INI reset.
b) Use the tweezers to short-circuit the INI reset contacts on the actuator (approx. 10 s.)
Remote reader or compact reader:
Note:
No INI reset contacts available.
Note:
Always interrupt the energy supply before switching.
Move DIP switches 5 and 6 to ‘ON’.
After switching, restore the energy supply.
ð
The actuator flashes.
Programming
User Manual
36
- 06/2021
dormakaba Programmer 1460