50 Hz: G625 - G690 - G750XW/XF
OPERATION & MAINTENANCE MANUAL
87
60 Hz: G655 - G750 - G800 - G850XW/XF
Table 8 shows applicable current of the ACBs. The applicable current varies depending on the ambient temperatures.
Table 8 Dependence of applicable current on ambient temperature
*1: Contact us.
NOTE:
For AR208S, AR212S and AR216S, it is assumed that main circuit terminals are of horizontal type at both the
line and load sides. For other types, it is assumed that main circuit terminals are of vertical type at both the line
and load sides. The above values may vary depending on the switchboard configuration.
Type and conductor size
AR208S
AR212S
AR216S
AR220S
AR325S
AR332S
AR440SB
AR440S
2×50×5t
2×80×5t
2×100×5t
3×100×5t
2×100x10t 3×100×10t
4×150×10t
4×150×6t
Standard
Temperature
Current (A)
IEC60947-2
EN60947-2
AS3947-2
JIS C8201-2-1
Ann.1 Ann.2
40°C (standard
ambient
temperature)
800
1250
1600
2000
2500
3200
4000
4000
45°C
800
1250
1600
2000
2500
3200
4000
4000
50°C
800
1250
1600
2000
2500
3200
3940
4000
55°C
800
1200
1540
1820
2500
2990
3820
3940
60°C
800
1150
1460
1740
2400
2850
3690
3760
NEMA,SG-3
ANSI C37.13
40°C (standard
ambient
temperature)
800
1250
1540
2000
2500
3200
3310
3700
45°C
800
1190
1470
1960
2500
3010
3200
3580
50°C
800
1130
1390
1860
2440
2860
3100
3470
55°C
790
1070
1310
1750
2300
2690
2980
3350
60°C
740
1000
1230
1640
2150
2520
2870
3140
JEC-160
40°C (standard
ambient
temperature)
800
1100
1460
1740
2370
2610
2870
3230
45°C
800
1060
1400
1680
2280
2510
2750
3100
50°C
800
1010
1340
1600
2180
2400
2620
2970
55°C
770
960
1280
1530
2080
2290
2490
2830
60°C
730
920
1220
1450
1970
2170
2360
2690
Type and conductor size
AR212H
AR216H
AR220H
AR316H
AR320H
AR325H
AR332H
AR420H
AR440H
2×80×5t
2×100×5t 3×100×5t 2×100×5t
3×100×5t
2×100×10t
3×100×10t
2×150×6t
4×150×6t
Standard
Temperature
Current (A)
IEC60947-2
EN60947-2
AS3947-2
JIS C8201-2-1
Ann.1 Ann.2
40°C (standard
ambient
temperature)
1250
1600
2000
1600
2000
2500
3200
2000
4000
45°C
1250
1600
2000
1600
2000
2500
3200
2000
4000
50°C
1250
1600
2000
1600
2000
2500
3200
2000
4000
55°C
1250
1600
1820
1600
2000
2500
2990
2000
3940
60°C
1250
1550
1740
1600
2000
2400
2850
2000
3760
NEMA,SG-3
ANSI C37.13
40°C (standard
ambient
temperature)
1250
1600
2000
1600
2000
2500
3200
*1
3700
45°C
1250
1600
1960
1600
2000
2500
3010
*1
3580
50°C
1250
1600
1860
1600
2000
2440
2860
*1
3470
55°C
1250
1510
1750
1600
1950
2300
2690
*1
3350
60°C
1240
1420
1640
1550
1830
2150
2520
*1
3140
JEC-160
40°C (standard
ambient
temperature)
1250
1500
1740
1600
2000
2370
2610
*1
3230
45°C
1250
1440
1680
1600
2000
2280
2510
*1
3100
50°C
1250
1380
1600
1600
2000
2180
2400
*1
2970
55°C
1250
1310
1530
1600
1920
2080
2290
*1
2830
60°C
1230
1250
1450
1600
1820
1970
2170
*1
2690