50 Hz: G625 - G690 - G750XW/XF
OPERATION & MAINTENANCE MANUAL
79
60 Hz: G655 - G750 - G800 - G850XW/XF
After operational testing, replace all access panels or
covers.
Dismantling and reassembly of the filters
- Remove the grille (417) then take out the filter (418), as
shown below. Change the filter if necessary; please see
later in this manual for cleaning the filter.
To replace, follow the instructions in reverse order.
INSTALLATION AND MAINTENANCE OF THE PMG
For the LSA 49.1, the PMG reference is : PMG 3.
See the PMG manual ref : 4211.
TABLE OF CHARACTERISTICS
Table of average values
Alternator - 4 poles - 50 Hz - Standard winding No. 6.
(400V for the excitation values)
The voltage and current values are given for no-load
operation and operation at rated load with separate field
excitation.
All values are given to within ± 10% and may be changed
without prior notification (for exact values, consult the test
report).
Resistances of main windings at 20°C
Average values for 6 winding - (12 wires)
Field excitation current i exc (A) 50 - 60 Hz
Table of weights
After operational testing, it is essential to replace all
access panels or covers.
LSA 49.1
Stator
L/N
Rotor
Field
Armature
M5
0,0044
0,38
12
0,08
L9
0,0023
0,43
12
0,08
LSA 49.1
No load
At rated load
M5
0,9
3,2
L9
0,9
3,3
LSA 49.1
Total weight (kg)
Rotor (kg)
M5
1620
620
L9
1820
700