50 Hz: G625 - G690 - G750XW/XF
OPERATION & MAINTENANCE MANUAL
85
60 Hz: G655 - G750 - G800 - G850XW/XF
Table 3 Standard types (Cont’d)
*1: Ambient temperature: 40°C (45°C for marine used)
*2: With horizontal terminals for AR208S - 216S and
vertical terminals for AR220S - 440S
*3: For 2-pole applications, use two poles at both ends.
*4: 4-pole ACBs are not applicable to power distribution
IT systems unless N-phase protection is provided.
*5: Varies depending on applicable standards. AC1000V
applies to ACBs conforming to IEC60947-2 and JIS
C8201-2.
*6: Varies depending on applicable standards. AC690V
applies to ACBs conforming to IEC60947-2 and JIS
C8201-2.
*7: Applicable to 3-pole ACBs with INST or MCR.
*8: For applicability to power distribution IT systems,
consult us
*9: A special version of the ACB is necessary above
250V DC. Contact Terasaki for details.
*10: For AC500V
*11: Expected service life based on endurance test. The
service life of ACB depends on the working and
environmental conditions. Refer to “Maintenance,
Inspection and Parts Replacement”.
*12: For both vertical and horizontal terminals
*13: This manual covers draw-out type ACBs.
*14: In applying or going to apply.
Frame size (A)
800
1250
1600
2000
2500
3200
4000
4000
Type
AR208S
AR212S
AR216S
AR220S
AR325S
AR332S
AR440SB
AR440S
Connection method
Line side
Vertical, horizontal or front terminals
Vertical
terminals
Vertical
terminals
Load side
Vertical, horizontal or front terminals
Vertical
terminals
Vertical
terminals
Control circuit terminal type
Screw terminals
Spring charging method
Manual or motor charging
Overcurrent release (OCR)
No OCR, or L-characteristic for general feeder protection
Operation indication
Group indication
Tripping device
Tripping coil
(TC)
Standard equipment for OCR-equipped ACB
Shunt trip
device (SHT)
Optional
Undervoltage
trip device
(UVT)
Optional
Auxiliary switches
Number of
switches
4
°
C (standard), 7
°
C or 10
°
C; available for general feeder or microload
Terminal type
Screw terminals
Rated voltage
Operation
power
AC100 - 120V, AC200 - 240V, DC100 - 125V, DC200 - 250V, DC24V or DC48V