55
G20, 30, 40 SIIIA Operation & Maintenance Manual
LOADING
ALARMS
SYMPTOM
POSSIBLE REMEDY
Engine runs but generator will
not take load
Check Warm up timer has timed out.
Ensure generator load inhibit signal is not present on the module inputs.
Check connections to the switching device.
Note that the set will not take load in manual mode unless there is an active
load signal.
Incorrect reading on Engine
gauges
Fail to stop alarm when engine is
at rest
Check engine is operating correctly.
Check that sensor is compatible with the module and that the module
configuration is suited to the sensor.
SYMPTOM
POSSIBLE REMEDY
Low oil Pressure fault operates
after engine has fired
Check engine oil pressure.
Check oil pressure switch/sensor and wiring.
Check configured polarity (if applicable) is correct (i.e. Normally Open or
Normally Closed) or that sensor is compatible with the module and is correctly
configured.
High engine temperature fault
operates after engine has fired
Check engine temperature.
Check switch/sensor and wiring.
Check configured polarity (if applicable) is correct (i.e. Normally Open or
Normally Closed) or that sensor is compatible with the module.
Shutdown fault operates
Check relevant switch and wiring of fault indicated on LCD display.
Check configuration of input.
Electrical Trip fault operates
Check relevant switch and wiring of fault indicated on LCD display.
Check configuration of input.
Warning fault operates
Check relevant switch and wiring of fault indicated on LCD display.
Check configuration of input.
CAN ECU WARNING
CAN ECU SHUTDOWN
This indicates a fault condition detected by the engine ECU and transmitted to
the DSE controller.
CAN DATA FAIL
Indicates failure of the CAN data link to the engine ECU.
Check all wiring and termination resistors (if required).
Incorrect reading on Engine
gauges
Fail to stop alarm when engine is
at rest
Check engine is operating correctly.
Check sensor and wiring paying particular attention to the wiring to terminal 10
(refer to appendix).
Check that sensor is compatible with the module and that the module
configuration is suited to the sensor.
Содержание G20 SIIIA
Страница 2: ......
Страница 4: ...4 G20 30 40 SIIIA Operation Maintenance Manual ...
Страница 10: ...10 G20 30 40 SIIIA Operation Maintenance Manual ...
Страница 15: ...15 G20 30 40 SIIIA Operation Maintenance Manual WARNING Flammable liquid ...
Страница 20: ...20 G20 30 40 SIIIA Operation Maintenance Manual ...
Страница 121: ......
Страница 122: ...Doosan Bobcat EMEA s r o U Kodetky 1810 263 12 Dobříš Czech Republic www doosanportablepower eu ...