G20, 30, 40 SIIIA Operation & Maintenance Manual
STOP MODE
MANUAL/START MODE
AUTO MODE
•
Scheduled runs do not occur when the module is in
Stop/Reset Mode
.
•
Scheduled runs do not occur when the module is in
Manual/Start Mode
waiting for a manual start.
•
Activation of a Scheduled Run 'On load' when the module is operating OFF LOAD in
Manual/
Start Mode
will force the set to run ON LOAD.
•
Scheduled runs operate ONLY if the module is in
Auto Mode
with no Shutdown or Electrical Trip
alarm present.
•
If the module is in
Stop/Reset Mode
or
Manual/Start Mode
when a scheduled run begins, the
engine is not started. However, if the module is moved into
Auto Mode
during a scheduled run,
the engine will be called to start.
•
Depending upon configuration by the system designer, an external input can be used to inhibit a
scheduled run.
•
If the engine is running OFF LOAD in
Auto Mode
and a scheduled run configured to 'On Load'
begins, the set is placed ON LOAD for the duration of the Schedule.