25
G20, 30, 40 SIIIA Operation & Maintenance Manual
CONTROL PUSH-BUTTONS
ICON
DESCRIPTION
STOP / RESET MODE
This button places the module into its
Stop/Reset Mode
. This will clear any alarm conditions for
which the triggering criteria have been removed. If the engine is running and the module is put into
Stop mode, the module will automatically instruct the generator to unload
('
Close Generator'
and
'
Delayed Load Output 1, 2, 3 & 4'
become inactive (if used))
. The fuel supply de-energises and
the engine comes to a standstill. Should any form of
remote start signal
be present while
operating in this mode, a start will not occur.
AUTO MODE
This button places the module into its
Auto Mode
. This mode allows the module to control the
function of the generator automatically. The module will monitor the remote start input and battery
charge status and once a start request is made, the set will be automatically started and placed on
load
('
Close Generator'
and '
Delayed Load Output 1, 2, 3 & 4
' become active in order from
lowest to highest (if used))
.
Upon removal of the starting signal, the module will remove the load from the generator and shut
the set down observing the
stop delay
timer and
cooling
timer as necessary
('
Close Generator
'
and '
Delayed Load Output 1, 2, 3 & 4
' become inactive at once (if used))
. The module will then
await the next start event.
For further details, please see the more detailed description of 'Auto
operation' elsewhere in this manual.
MANUAL / START MODE
This button will start the engine and run off load. To place the generator on load, digital inputs are
required to be assigned to perform this function.
If the engine is running off-load in
Manual/Start Mode
button and a
remote start signal
becomes
present, the module will automatically instruct the changeover device to place the generator on
load
('
Close Generator
' and '
Delayed Load Output 1, 2, 3 & 4
' becomes active (if used))
. Upon
removal of the
Remote Start Signal
, the generator remains on load until either selection of the
Stop/Reset Mode
or
Auto Mode
.
MENU NAVIGATION
Used for navigating the instrumentation, event log and configuration screens.
For further details, please see the more detailed description of these items elsewhere in this
manual.
Содержание G20 SIIIA
Страница 2: ......
Страница 4: ...4 G20 30 40 SIIIA Operation Maintenance Manual ...
Страница 10: ...10 G20 30 40 SIIIA Operation Maintenance Manual ...
Страница 15: ...15 G20 30 40 SIIIA Operation Maintenance Manual WARNING Flammable liquid ...
Страница 20: ...20 G20 30 40 SIIIA Operation Maintenance Manual ...
Страница 121: ......
Страница 122: ...Doosan Bobcat EMEA s r o U Kodetky 1810 263 12 Dobříš Czech Republic www doosanportablepower eu ...