G20, 30, 40 SIIIA Operation & Maintenance Manual
MAINTENANCE ALARM
Depending upon module configuration one or more levels of engine maintenance alarm may occur based upon a
configured schedule.
Example 1
Figure 18
Screen capture from DSE Configuration Suite Software showing the configuration of the Maintenance Alarm for Oil, Air
and Fuel.
When activated, the maintenance alarm can be either a
warning
(set continues to run) or
shutdown
(running the set is
not possible).
Resetting the maintenance alarm is normally actioned by the site service engineer after performing the required
maintenance.
The method of reset is either by:
•
Activating an input that has been configured to Maintenance Reset Alarm x, where x is the type
of maintenance alarm (Air, Fuel or Oil).
•
Pressing the maintenance reset button in the DSE Configuration Suite, Maintenance section.
•
Pressing and holding the
Stop/Reset Mode
button for 10 seconds on the desired Maintenance
Alarm status page. This can be protected by a PIN number.