Load requirements in inverter mode
Before connecting appliances to the AC output of
the device, always check the maximum power con-
sumption. Do not connect appliances to the AC
output continuously requiring more than the nomi-
nal power rating of the inverter, unless these appli-
ances are switched on only when the AC transfer
switch is activated, and power is drawn from an
external source with a larger capacity than the
inverter.
Some appliances, like motors or pumps, draw
large inrush currents at startup. It is possible that
the startup current exceeds the overcurrent trip
level of the inverter. In this case, the output voltage
will shortly decrease to limit the output current of
the inverter.
If the overcurrent trip level is continuously
exceeded, the inverter will shut down and auto-
matically restart within 20 seconds. In this case, it is
advisable to disconnect this appliance from the
inverter, since it requires too much power to be
driven by this unit.
The device needs to be restarted manually when it
has shut down due to overloads for four times in a
row. At higher ambient temperature levels, the
overload capacity of the device will be reduced.
Configuring the device
The device can be configured using the DIP switch
located in the connection bay. The most important
settings are preconfigured as factory default.
Local/external programming
Charge current reduction (MT ICC 1600
SI-N)
Charge current reduction (MT ICC 3000
SI-N)
Low battery protection
Switch
Description
1=ON
Switches 5 to 7 or 9 are ignored.
1=OFF
The local DIP switch settings are used. All
other parameters are set to the factory
default.
Switch
Description
2=ON
50% (30 A)
• LiFePo4 battery < 100 Ah
• Lead acid bat. > 100 Ah
2=OFF
100% (60 A)
• LiFePo4 battery > 100 Ah
• Lead acid battery > 200 Ah
Switch
Switch
Description
2=OFF
8=OFF
100% (120 A)
• LiFePo4 battery > 400 Ah
• Lead acid battery > 420 Ah
2=OFF
8=ON
75% (90 A)
• LiFePo4 battery > 200 Ah
• Lead acid battery > 320 Ah
2=ON
8=OFF
50% (60 A)
• LiFePo4 battery > 100 Ah
• Lead acid battery > 200 Ah
2=ON
8=ON
25% (30 A)
• LiFePo4 battery < 100 Ah
• Lead acid battery > 100 Ah
Switch
Description
3=ON
Disconnects when battery < 10.8 V restart
at 12.0 V if the inverter is in the continuous
mode.
3=OFF
Inverter shuts down when the battery volt-
age is < 8.0 V, restart at 8.5 V.
Содержание BUTTNER MT ICC 1600 SI-N
Страница 3: ...4445103626 3 1 126 mm 187 mm 334 mm...
Страница 4: ...4 4445103626 2 287 mm 249 mm 37 mm 231 mm 144 mm 56 mm 5 mm...
Страница 5: ...4445103626 5 3...
Страница 6: ...6 4445103626 4...
Страница 7: ...4445103626 7 2 3 1 5...
Страница 8: ...8 4445103626 100 mm 100 mm 6...
Страница 9: ...4445103626 9 7 58 mm 58 mm...
Страница 10: ...10 4445103626 8 9...
Страница 11: ...4445103626 11 0 a...
Страница 12: ...12 4445103626 b INPUT OUTPUT AC INPUT AC OUTPUT L N L N A C D F G E B OUTPUT INPUT 1 2...
Страница 13: ...4445103626 13 c d...
Страница 14: ...14 4445103626 e 2x f 2 1...
Страница 16: ...16 4445103626 i 5 25 50 75 100 charger inverter AC in 5 25 50 75 100 charger inverter AC in 1 4 2 3...
Страница 137: ...4445103626 137...
Страница 138: ...138 4445103626...
Страница 139: ...4445103626 139...