Universal Air Conditioning Unit
Intended Use
3 Intended Use
The basic principle behind an air conditioner is the
transfer of heat from one place to another. In an air-
cooled air conditioner, heat is removed from the inside
air and transferred to the outside air. The efficiency of
the system operation depends on both outside air and
inside air temperatures.
When cooling, the air conditioner will operate most
efficiently in outside air temperatures below 95 °F
(35 °C). At higher outside air temperatures, the unit will
operate but at a reduced capacity. A high-pressure shut
down may occur at outside ambient air temperatures
near 130 °F (54 °C).
The Dometic ASCDU15HV 1161 is a direct-expansion
air-cooled air conditioning system designed for use
in air-cooled applications. It is a self-contained pre-
charged unit. A complete system requires the installation
of controls and ducting. This system is designed for
use with the Q3 control. The Q3 control is a micro-
controller-based unit designed for use with direct
expansion (DX) air conditioning systems. Filling of the
system with refrigerant is not required, as this system
comes pre-charged from the factory.
The manufacturer accepts no liability for damage in the
following cases:
• Faulty assembly or connections
• Damage to the product resulting from mechanical
influences and excess voltage
• Alterations to the product without express permission
from the manufacturer
• Use for purposes other than those described above
Dometic Corporation reserves the right to modify
appearances and specifications without notice.
This manual contains essential information to ensure
the proper installation, operation, and maintenance of
your ASCDU15HV 1161 System. If you have questions or
require assistance with your unit, call your Dometic RV
Service Department at +1 574-264-2131.
4 Specifications
This section provides the unit specification information
needed for successful installation.
4 .1 System Specifications
Refer to this table for any questions regarding the
specifications of this system.
Description
Range
Model
ASCDU15HV 1161
Nominal Cooling Capacity
15,000 BTU/HR
Nominal Heating Capacity
8550 BTU/HR
Set Point Operating Range
55 °F–99 °F (13 °C–37 °C)
Sensor Accuracy
± 2 °F @ 77 °F
(± 1 °C @ 25 °C)
Low Voltage Limit 115 Volt
Units
90 VAC
Line Voltage
95–115 VAC
Phase
1
Frequency
60 Hz
Maximum Fuse
40 A
Minimum Fuse
30 A
Fan Amps Combined
Condenser and Evaporator
5.92 A
Compressor FLA Cooling
25.7 A
Compressor LRA
69.8 A
Heat FLA
24.3 A
Refrigerant Charge
38 oz / 1078 g
Compressor Oil
POE
Minimum Operating
Temperature
0 °F (-18 °C)
Maximum Ambient
Operating Temperature
130 °F (54 °C)
Maximum RH Conditions
99% Non-Condensing
Weight
136 lbs (62 kg)
Length
30.12 in. (76 cm)
Width
20.13 in. (51 cm)
Height
20.37 in. (52 cm)
Metal Finish
Bare Aluminum