Dometic ASCDU15HV 1161 Скачать руководство пользователя страница 21

21

EN

Universal Air Conditioning Unit 

Programmable Functions, Ranges, and Factory Defaults

9: Temperature Calibration

This feature calibrates the ambient sensor within a range 
of ±1%. The temperature sensor should be within one or 
two degrees of the actual room temperature. 

 

I

Setting increments are in °F even when the Q3 
control is set to display °C. Adjust this parameter to 
display the correct room-temperature reading.

To check accuracy or to calibrate:

•  The sensed temperature is displayed. Place an 

accurate thermometer beside the sensor and 
compare the temperatures.

•  Press the Up or Down buttons to recalibrate the value 

as required.

10: Dehumidification Pre-Circulation Time

The humidity control program (HU) automatically 
operates the air conditioning system for a programmed 
time period to help control humidity. This 
dehumidification feature works in three stages:

1.  The fan comes on at high speed to circulate air for ten 

minutes.

2.  The fan then drops to low speed, and the compressor 

cycles on in the cool mode to dehumidify.

3.  After the dehumidification cycle, the system turns off. 

The process repeats according to the programmed 
time period.

The compressor time delay setting (see “1: Compressor 
Time Delay” on page 19) go
verns when the 
dehumidification cycle starts. Every one  second of 
compressor delay equals a six-minute advance into the 
dehumidification cycle.

The factory default settings are:

•  Pre-circulation cycle—10 minutes

•  Dehumidification cycle—30 minutes

•  Overall time period—12 hours

The factory settings are adequate for most moderate 
climates and boats. For very humid climates, shorten 
the overall time period and extend the dehumidification 
time. In dry climates, select a longer overall time period 
between cycles and a shorter dehumidification time. 

Programmable function 10 governs the pre-circulation 
cycle time and should not be changed.

11: Dehumidification Time

The dehumidification time determines how long the 
compressor runs in the dehumidification mode (see “10: 
Dehumidification Pre-Circulation Time” on page 21
). 
The display shows the dehumidification time period in 
minutes. You can select 0, 10, 20, 30, 40, or 50 minutes. 
Select a longer dehumidification time in climates with 
high humidity. Select a lower dehumidification time in 
climates with low humidity.

12: Dehumidification Overall Time Period

This setting determines how often the system performs 
the dehumidification process. The display shows the 
overall time period in hours. You can select intervals of 2, 
4, 6, 8, 10, 12, 14, or 16 hours. Choose a shorter overall 
time period in climates with high humidity. Choose a 
longer overall time period in climates with low humidity.

Recommended Humidity Control Settings

Outside 

Temp .

Relative 

Humidity

Time 

Period

Dehumidification

Time

Below 80 °F 

(27 °C)

75–85%

12 hours

10 minutes

Above 

85%

8 hours

20 minutes

80 °F–90 °F

(27 °C–32 °C)

75–85%

10 hours

30 minutes

Above 

85%

6 hours

40 minutes

Below 90 °F 

(32 °C)

75–85%

8 hours

50 minutes

Above 

85%

6 hours

60 minutes

13: Software Revision Level

This setting displays the software version and revision 
level of the system. It will display a two-digit number 
such as “05” for version five. Have this information 
ready prior to calling a dealer or the factory for service 
assistance.

14: Determining Your Product Type

The system default is dE for “direct expansion self-
contained.”

Содержание ASCDU15HV 1161

Страница 1: ...S AIR CONDITIONER L 5005 Form No 340813 20200305 2020 Dometic Corporation AUTO DEHUMIDIFY ASCDU15HV 1161 Q3 Control EN Universal Self Contained Air Conditioning Unit and Q3 Control Installation and Op...

Страница 2: ...9 Installing the Optional Outside Air Temperature Sensor 13 6 10 Start Up Checklist 14 7 Operation 15 7 1 Understanding Button Functions 15 7 2 Normal Heating or Cooling Cycle 16 7 3 Modes and Progra...

Страница 3: ...tand these instructions before installing or operating this product The installation must comply with all applicable local or national codes including the latest edition of the following standards U S...

Страница 4: ...luorocarbon HFC refrigerant R 410A refrigerant operates at a higher pressure than R 22 Ensure that the servicing equipment and replacement components used are designed to operate with R 410A I IRefer...

Страница 5: ...ressor Start Capacitor yHigh Pressure Switch HPS 1 Compressor Run Capacitor uLow Pressure Switch LPS 1 Evaporator Blower Capacitor i10 ft 3 m Interconnect Cable 2 Condenser Blower Capacitor oElectrica...

Страница 6: ...able Functions Ranges and Factory Defaults on page 18 12 Off Mode Indicator Lights when the system is off Note that the Data Display remains on You can continue to adjust the set point display reading...

Страница 7: ...esulting from mechanical influences and excess voltage Alterations to the product without express permission from the manufacturer Use for purposes other than those described above Dometic Corporation...

Страница 8: ...4 18 38 in 46 cm 5 20 37 in 51 cm 6 20 13 in 51 cm Evaporator Side View 7 17 75 in 45 cm 8 14 88 in 38 cm 4 3 Electrical Box Dimensions i t u y r e w q d f o s a Top Front Side 5 Electrical Box Dimen...

Страница 9: ...udes the drill and cut template P N 086812 4 5 Cable Lengths Description Size Display Cable 15 ft 5 m Typical Indoor Air Sensor 15 ft 5 m Standard on Self Contained Systems Outside Air Sensor optional...

Страница 10: ...9 7 2 10 18 19 11 3 1 6 17 16 5 4 12 13 15 14 8 19 2 7 18 10 9 17 6 1 3 11 12 4 5 16 15 13 14 2 IF PRESENT ON BOARD JUMPER CSNB MUST BE CUT WHEN USING A CONTACTOR OR SOLID STATE RELAY ON THE COMPRESS...

Страница 11: ...icing Dometic equipment to prevent any loss of refrigerant Failure to obey this caution could result in minor or moderate injury NOTICE This product contains R 410A fluorinated greenhouse gas in seale...

Страница 12: ...oper use and may cause damage to the electrical components I IConnect the wiring as per the wiring diagram located on the unit 1 Connect the vehicle s power supply to the unit 2 Install a ground fault...

Страница 13: ...lug the cable into the port labeled INSIDE on the circuit board located in the electrical box 6 8 Installing the Q3 Control 1 Plan the location of the display using the drill and cut template P N 0868...

Страница 14: ...including the main power supply tight Y N 6 10 2 Starting the Unit 1 Turn the circuit breaker for the air conditioner to the On position 2 Turn the control on 3 Use the Q3 control to set the system f...

Страница 15: ...refrigerants must by law be reclaimed If an indoor leak is suspected thoroughly ventilate the area before beginning work Never burn refrigerant as poisonous gas will be produced Always follow EPA gui...

Страница 16: ...n operation When in Auto fan mode the fan speed will return to low speed once the set point temperature has been satisfied and the cooling or heating cycle has ended 7 3 Modes and Programmable Functio...

Страница 17: ...inside temperature If inside temperature is greater than 99 F 37 C or less then 0 F 17 C the display shows either 99 F 37 C or 0 F 17 C respectively as the maximum or minimum inside temperature 7 3 7...

Страница 18: ...C 2 31 4 Fan Response Differential 8 8 8 1 F 0 6 C 2 31 5 Low Fan Speed 38 2 57 6 High Fan Speed 85 41 99 7 Fan Mode C Continuous C Continuous I Intermittent 8 AC Line Voltage Calibration Plus or min...

Страница 19: ...e delay before the display shows readings If an attempt is made to change the five minute time delay the changes will not be recognized by the system 2 Fahrenheit Celsius or Auto Selection Select F fo...

Страница 20: ...antly The high fan speed adjustment allows you to set the maximum high speed voltage to the threshold of the blower high speed response The Q3 control system divides the fan speed voltage steps into f...

Страница 21: ...boats For very humid climates shorten the overall time period and extend the dehumidification time In dry climates select a longer overall time period between cycles and a shorter dehumidification ti...

Страница 22: ...and the display will show OA closed circuit if the high pressure switch circuit is OK or FA open circuit if the high pressure switch circuit has a fault or system is overcharged or has loss of condens...

Страница 23: ...in aux heat heat mode I IWhen you enable the aux heat heat function h1 the fan will delay turning off for 30 seconds to allow the auxiliary heater to cool down The delay occurs when the auxiliary heat...

Страница 24: ...faults on page 18 3 Press the Mode button to access the programmable value of the displayed function number The function s current value flashes on the display 4 Press the Up or Down buttons to change...

Страница 25: ...reduced There is low airflow through the system The airflow through the evaporator is blocked Inspect for and remove any obstructions in the return air stream Clean the return air filter and grille C...

Страница 26: ...oad is open due to lack of air flow though the condenser Allow the compressor to cool Turn the system off for a while it may take up to three hours to reset the thermal overload 10 2 Digital Controls...

Страница 27: ...before reprogramming the Q3 control Change Programmable Function 21 to increase the duration of the Anti Icing Routine If the anti icing cycle does not melt the ice switch the air conditioning unit t...

Страница 28: ...ntrol board The low pressure switch opens when the suction pressure drops below a preset minimum limit If the low pressure switch opens the unit will first run for two minutes and then shut down for 5...

Страница 29: ...conds the Q3 control shows a constant Cool or Heat Mode may be selected for emergency operation and the display will show a constant Emergency Operation Ar FL The Q3 control flashes Ar FL for 15 secon...

Страница 30: ...aning the Return Air Filter Check the Return Air Filter once a month or more often if local conditions and usage patterns dictate and replace or clean as necessary To clean the filter Remove the filte...

Страница 31: ...coils may result in reduced performance Avoid the use of the following Coil brighteners High pressure washers Poor quality water for cleaning Use of non recommended coil cleaners is strongly discoura...

Страница 32: ...Mobile living made easy dometic com YOUR LOCAL DEALER dometic com dealer YOUR LOCAL SUPPORT dometic com contact YOUR LOCAL SALES OFFICE dometic com sales offices...

Отзывы: