Dometic ASCDU15HV 1161 Скачать руководство пользователя страница 16

16

EN

Operation 

Universal Air Conditioning Unit

•  Down button –

 Press and release to display the set 

point. Press and hold the Down button to decrease 
the set point. The set point decreases one degree 
each time the button is pressed.

•  Fan button –

 Press to select the Automatic Fan 

Mode, the Manual Fan Mode, or to advance through 
the manual fan speeds.

•  Display Outside Temperature (optional) –

 

Press the Fan and Down buttons simultaneously 
to display the outside temperature (optional). If 
the outside temperature is not available, open or 
shorted (closed), the display flashes ”- -” instead 
of a temperature reading. Press the Fan and Down 
buttons simultaneously to display the outside 
temperature (optional). If outside temperature is 
not available, open or shorted (closed), the display 
flashes “- -” instead of a temperature reading.

7 .2  Normal Heating or Cooling 
Cycle

If you select Cool Mode, only cooling is supplied. If 
you select Heat, only heat is supplied. The conditioned 
space temperature in either mode is maintained within 
the compressor differential setting.

During a Cooling or Heating cycle, the fan will operate 
at a fan speed depending on the fan’s operational 
mode. If a Manual fan speed is selected, the fan will 
operate at this speed at all times, even if the set point 
has been satisfied and the cooling or heating cycle 
has ended. If the fan is in Auto mode, the fan speed 
will be determined by programmable function 4, the 
Fan Response Differential, and programmable function 
22, Fan-Speed Divisions. Refer to these parameters 
for further details on the fan speeds during Auto fan 
operation. When in Auto fan mode, the fan speed will 
return to low speed once the set point temperature 
has been satisfied and the cooling or heating cycle has 
ended.

7 .3  Modes and Programmable 
Functions

This section provides the detailed information about 
each mode.

7 .3 .1  Power On and Basic Modes

Press the Mode button to turn the system on. In three 
seconds, the system will start operating in whichever 
mode it was running prior to the last shut down. For 
the initial startup, the control will be in Cool Mode. To 
change modes before the system starts, press the Mode 
button before the three-second startup completes (while 
the display is flashing). Or, while the system is on, press 
the Mode button at any time to change the mode. 

The modes available are: 

•  Off

•  Cool

•  Heat

•  Auto (automatically switches between Cool and Heat 

Modes, depending on set point requirements)

•  Dehumidification Mode

7 .3 .2  Dehumidification Mode

Press the Mode button until the Dehumidify LED 
indicator illuminates. The display flashes “HU” during 
this mode of operation. When Dehumidification 
Mode is activated, the Humidity Control Program 
automatically turns the air conditioning system on at 
timed intervals to remove moisture from the air. The 
system is  programmed at the factory for average 
values. To change the factory settings, see “10: 
Dehumidification Pre-Circulation Time” on page 21,  
“11: Dehumidification Time” on page 21, and “12: 
Dehumidification Overall Time Period” on page 21.

 

I

When the system is in Dehumidification Mode, 
all system safeguard controls remain active. For 
example, if the line voltage falls below preset limits, 
the system will automatically shut down. If the AC 
power is interrupted, the system will automatically 
resume operation in Dehumidification Mode when 
power is restored.

Содержание ASCDU15HV 1161

Страница 1: ...S AIR CONDITIONER L 5005 Form No 340813 20200305 2020 Dometic Corporation AUTO DEHUMIDIFY ASCDU15HV 1161 Q3 Control EN Universal Self Contained Air Conditioning Unit and Q3 Control Installation and Op...

Страница 2: ...9 Installing the Optional Outside Air Temperature Sensor 13 6 10 Start Up Checklist 14 7 Operation 15 7 1 Understanding Button Functions 15 7 2 Normal Heating or Cooling Cycle 16 7 3 Modes and Progra...

Страница 3: ...tand these instructions before installing or operating this product The installation must comply with all applicable local or national codes including the latest edition of the following standards U S...

Страница 4: ...luorocarbon HFC refrigerant R 410A refrigerant operates at a higher pressure than R 22 Ensure that the servicing equipment and replacement components used are designed to operate with R 410A I IRefer...

Страница 5: ...ressor Start Capacitor yHigh Pressure Switch HPS 1 Compressor Run Capacitor uLow Pressure Switch LPS 1 Evaporator Blower Capacitor i10 ft 3 m Interconnect Cable 2 Condenser Blower Capacitor oElectrica...

Страница 6: ...able Functions Ranges and Factory Defaults on page 18 12 Off Mode Indicator Lights when the system is off Note that the Data Display remains on You can continue to adjust the set point display reading...

Страница 7: ...esulting from mechanical influences and excess voltage Alterations to the product without express permission from the manufacturer Use for purposes other than those described above Dometic Corporation...

Страница 8: ...4 18 38 in 46 cm 5 20 37 in 51 cm 6 20 13 in 51 cm Evaporator Side View 7 17 75 in 45 cm 8 14 88 in 38 cm 4 3 Electrical Box Dimensions i t u y r e w q d f o s a Top Front Side 5 Electrical Box Dimen...

Страница 9: ...udes the drill and cut template P N 086812 4 5 Cable Lengths Description Size Display Cable 15 ft 5 m Typical Indoor Air Sensor 15 ft 5 m Standard on Self Contained Systems Outside Air Sensor optional...

Страница 10: ...9 7 2 10 18 19 11 3 1 6 17 16 5 4 12 13 15 14 8 19 2 7 18 10 9 17 6 1 3 11 12 4 5 16 15 13 14 2 IF PRESENT ON BOARD JUMPER CSNB MUST BE CUT WHEN USING A CONTACTOR OR SOLID STATE RELAY ON THE COMPRESS...

Страница 11: ...icing Dometic equipment to prevent any loss of refrigerant Failure to obey this caution could result in minor or moderate injury NOTICE This product contains R 410A fluorinated greenhouse gas in seale...

Страница 12: ...oper use and may cause damage to the electrical components I IConnect the wiring as per the wiring diagram located on the unit 1 Connect the vehicle s power supply to the unit 2 Install a ground fault...

Страница 13: ...lug the cable into the port labeled INSIDE on the circuit board located in the electrical box 6 8 Installing the Q3 Control 1 Plan the location of the display using the drill and cut template P N 0868...

Страница 14: ...including the main power supply tight Y N 6 10 2 Starting the Unit 1 Turn the circuit breaker for the air conditioner to the On position 2 Turn the control on 3 Use the Q3 control to set the system f...

Страница 15: ...refrigerants must by law be reclaimed If an indoor leak is suspected thoroughly ventilate the area before beginning work Never burn refrigerant as poisonous gas will be produced Always follow EPA gui...

Страница 16: ...n operation When in Auto fan mode the fan speed will return to low speed once the set point temperature has been satisfied and the cooling or heating cycle has ended 7 3 Modes and Programmable Functio...

Страница 17: ...inside temperature If inside temperature is greater than 99 F 37 C or less then 0 F 17 C the display shows either 99 F 37 C or 0 F 17 C respectively as the maximum or minimum inside temperature 7 3 7...

Страница 18: ...C 2 31 4 Fan Response Differential 8 8 8 1 F 0 6 C 2 31 5 Low Fan Speed 38 2 57 6 High Fan Speed 85 41 99 7 Fan Mode C Continuous C Continuous I Intermittent 8 AC Line Voltage Calibration Plus or min...

Страница 19: ...e delay before the display shows readings If an attempt is made to change the five minute time delay the changes will not be recognized by the system 2 Fahrenheit Celsius or Auto Selection Select F fo...

Страница 20: ...antly The high fan speed adjustment allows you to set the maximum high speed voltage to the threshold of the blower high speed response The Q3 control system divides the fan speed voltage steps into f...

Страница 21: ...boats For very humid climates shorten the overall time period and extend the dehumidification time In dry climates select a longer overall time period between cycles and a shorter dehumidification ti...

Страница 22: ...and the display will show OA closed circuit if the high pressure switch circuit is OK or FA open circuit if the high pressure switch circuit has a fault or system is overcharged or has loss of condens...

Страница 23: ...in aux heat heat mode I IWhen you enable the aux heat heat function h1 the fan will delay turning off for 30 seconds to allow the auxiliary heater to cool down The delay occurs when the auxiliary heat...

Страница 24: ...faults on page 18 3 Press the Mode button to access the programmable value of the displayed function number The function s current value flashes on the display 4 Press the Up or Down buttons to change...

Страница 25: ...reduced There is low airflow through the system The airflow through the evaporator is blocked Inspect for and remove any obstructions in the return air stream Clean the return air filter and grille C...

Страница 26: ...oad is open due to lack of air flow though the condenser Allow the compressor to cool Turn the system off for a while it may take up to three hours to reset the thermal overload 10 2 Digital Controls...

Страница 27: ...before reprogramming the Q3 control Change Programmable Function 21 to increase the duration of the Anti Icing Routine If the anti icing cycle does not melt the ice switch the air conditioning unit t...

Страница 28: ...ntrol board The low pressure switch opens when the suction pressure drops below a preset minimum limit If the low pressure switch opens the unit will first run for two minutes and then shut down for 5...

Страница 29: ...conds the Q3 control shows a constant Cool or Heat Mode may be selected for emergency operation and the display will show a constant Emergency Operation Ar FL The Q3 control flashes Ar FL for 15 secon...

Страница 30: ...aning the Return Air Filter Check the Return Air Filter once a month or more often if local conditions and usage patterns dictate and replace or clean as necessary To clean the filter Remove the filte...

Страница 31: ...coils may result in reduced performance Avoid the use of the following Coil brighteners High pressure washers Poor quality water for cleaning Use of non recommended coil cleaners is strongly discoura...

Страница 32: ...Mobile living made easy dometic com YOUR LOCAL DEALER dometic com dealer YOUR LOCAL SUPPORT dometic com contact YOUR LOCAL SALES OFFICE dometic com sales offices...

Отзывы: