Programmable Functions, Ranges, and Factory Defaults 

Universal Air Conditioning Unit

The fan response differential can be adjusted from 1/4°  
 to 4°, in 1/8° increments. All program functions must be 
adjusted in °F even if the temperature display is changed 
from Fahrenheit to Celsius. Refer to “2: Fahrenheit, 
Celsius, or Auto Selection” on page 19

The fan speed range is divided by the Q3 control system 
into five equal increments. If the fan response differential 
is set at 1/2°, then the fan speed will change 20% for 
each 1/2° of temperature deviation from the set point. 
Lowering the fan speed differential will cause the fan 
to change speeds more frequently as the temperature 
changes. Raising the fan speed differential will result 
in slower fan speed changes for a given temperature 
change. The factory setting of 1/2° is ideal for most 
applications.

 

I

If the compressor restart and the fan response 
differentials are both set to the factory default or a 
comparable range and the Auto fan mode is on, 
then the fan will not run at high speed unless the 
conditioned space temperature rises 3 °F  
(-16 °C) above the set point.

5: Low Fan Speed

You can adjust the lowest fan speed to suit individual 
preferences. For instance, you may wish to decrease the 
low fan speed setting to minimize fan noise.

 

I

For the most efficient operation of your system, 
you should keep the low fan speed at the highest 
possible setting, consistent with a comfortable 
noise level. Running the fan speed too low may 
have an adverse effect on the system and may cause 
the evaporator coil to freeze and shut down on low 
pressure.

6: High Fan Speed

A blower will often reach its highest speed at a voltage 
lower than full line voltage. For example, at a line voltage 
of 115 VAC, the blower might reach its fastest speed at 
110 VAC. At higher voltages, the blower speed will not 
increase significantly. 

The high fan speed adjustment allows you to set the 
maximum high-speed voltage to the threshold of the 
blower high-speed response. The Q3 control system 
divides the fan speed voltage steps into five equal 
increments (between the low-speed and high -speed 
adjustments). 

Accurately setting the high and low fan speed 
adjustments can help ensure that each fan speed 
increment step results in a noticeable change of fan 
speed.

•  While in programming mode, listen to the fan noise 

level and use the Up button to raise the displayed 
value past the point that you can hear an increase in 
the fan noise level.

•  Press the Down button to lower the voltage until 

you hear a drop in the fan speed. Raise that number 
by two or three to ensure that it is set at the highest 
speed.

7: Fan Mode

You can select continuous or intermittent fan operation. 
Select “C” and the fan will run continuously while the 
system is on. Select “I” for intermittent operation and the 
fan will cycle on and off with the compressor.

 

I

If you select intermittent fan operation, you should 
relocate the thermistor from the return-air grille to a 
conditioned space wall where it can best sense the 
average room temperature. Check with your dealer 
or call Dometic for more information.

8: AC Line Voltage Calibration

The unity control board assembly has a built-in voltmeter 
that senses AC line voltage and this feature displays 
the voltage being read. The unity control board 
automatically responds to sustained low-voltage or high-
voltage conditions by shutting down the air conditioning 
system to prevent compressor damage. At installation, 
the unity control board voltmeter should be calibrated to 
line voltage within ± 1 %. To check or re-calibrate the AC 
line voltage:

•  Line voltage will be displayed as the last two digits of 

the voltage. On 115 VAC systems, 95 VAC appears as 
“95”, 100 VAC as “00”, and 115 VAC as “15”.

•  To check accuracy or to calibrate, turn off all on-

board AC loads and measure the line voltage with an 
accurate voltmeter.

•  Press the Up or Down buttons to recalibrate the value 

as required.

Содержание ASCDU15HV 1161

Страница 1: ...S AIR CONDITIONER L 5005 Form No 340813 20200305 2020 Dometic Corporation AUTO DEHUMIDIFY ASCDU15HV 1161 Q3 Control EN Universal Self Contained Air Conditioning Unit and Q3 Control Installation and Op...

Страница 2: ...9 Installing the Optional Outside Air Temperature Sensor 13 6 10 Start Up Checklist 14 7 Operation 15 7 1 Understanding Button Functions 15 7 2 Normal Heating or Cooling Cycle 16 7 3 Modes and Progra...

Страница 3: ...tand these instructions before installing or operating this product The installation must comply with all applicable local or national codes including the latest edition of the following standards U S...

Страница 4: ...luorocarbon HFC refrigerant R 410A refrigerant operates at a higher pressure than R 22 Ensure that the servicing equipment and replacement components used are designed to operate with R 410A I IRefer...

Страница 5: ...ressor Start Capacitor yHigh Pressure Switch HPS 1 Compressor Run Capacitor uLow Pressure Switch LPS 1 Evaporator Blower Capacitor i10 ft 3 m Interconnect Cable 2 Condenser Blower Capacitor oElectrica...

Страница 6: ...able Functions Ranges and Factory Defaults on page 18 12 Off Mode Indicator Lights when the system is off Note that the Data Display remains on You can continue to adjust the set point display reading...

Страница 7: ...esulting from mechanical influences and excess voltage Alterations to the product without express permission from the manufacturer Use for purposes other than those described above Dometic Corporation...

Страница 8: ...4 18 38 in 46 cm 5 20 37 in 51 cm 6 20 13 in 51 cm Evaporator Side View 7 17 75 in 45 cm 8 14 88 in 38 cm 4 3 Electrical Box Dimensions i t u y r e w q d f o s a Top Front Side 5 Electrical Box Dimen...

Страница 9: ...udes the drill and cut template P N 086812 4 5 Cable Lengths Description Size Display Cable 15 ft 5 m Typical Indoor Air Sensor 15 ft 5 m Standard on Self Contained Systems Outside Air Sensor optional...

Страница 10: ...9 7 2 10 18 19 11 3 1 6 17 16 5 4 12 13 15 14 8 19 2 7 18 10 9 17 6 1 3 11 12 4 5 16 15 13 14 2 IF PRESENT ON BOARD JUMPER CSNB MUST BE CUT WHEN USING A CONTACTOR OR SOLID STATE RELAY ON THE COMPRESS...

Страница 11: ...icing Dometic equipment to prevent any loss of refrigerant Failure to obey this caution could result in minor or moderate injury NOTICE This product contains R 410A fluorinated greenhouse gas in seale...

Страница 12: ...oper use and may cause damage to the electrical components I IConnect the wiring as per the wiring diagram located on the unit 1 Connect the vehicle s power supply to the unit 2 Install a ground fault...

Страница 13: ...lug the cable into the port labeled INSIDE on the circuit board located in the electrical box 6 8 Installing the Q3 Control 1 Plan the location of the display using the drill and cut template P N 0868...

Страница 14: ...including the main power supply tight Y N 6 10 2 Starting the Unit 1 Turn the circuit breaker for the air conditioner to the On position 2 Turn the control on 3 Use the Q3 control to set the system f...

Страница 15: ...refrigerants must by law be reclaimed If an indoor leak is suspected thoroughly ventilate the area before beginning work Never burn refrigerant as poisonous gas will be produced Always follow EPA gui...

Страница 16: ...n operation When in Auto fan mode the fan speed will return to low speed once the set point temperature has been satisfied and the cooling or heating cycle has ended 7 3 Modes and Programmable Functio...

Страница 17: ...inside temperature If inside temperature is greater than 99 F 37 C or less then 0 F 17 C the display shows either 99 F 37 C or 0 F 17 C respectively as the maximum or minimum inside temperature 7 3 7...

Страница 18: ...C 2 31 4 Fan Response Differential 8 8 8 1 F 0 6 C 2 31 5 Low Fan Speed 38 2 57 6 High Fan Speed 85 41 99 7 Fan Mode C Continuous C Continuous I Intermittent 8 AC Line Voltage Calibration Plus or min...

Страница 19: ...e delay before the display shows readings If an attempt is made to change the five minute time delay the changes will not be recognized by the system 2 Fahrenheit Celsius or Auto Selection Select F fo...

Страница 20: ...antly The high fan speed adjustment allows you to set the maximum high speed voltage to the threshold of the blower high speed response The Q3 control system divides the fan speed voltage steps into f...

Страница 21: ...boats For very humid climates shorten the overall time period and extend the dehumidification time In dry climates select a longer overall time period between cycles and a shorter dehumidification ti...

Страница 22: ...and the display will show OA closed circuit if the high pressure switch circuit is OK or FA open circuit if the high pressure switch circuit has a fault or system is overcharged or has loss of condens...

Страница 23: ...in aux heat heat mode I IWhen you enable the aux heat heat function h1 the fan will delay turning off for 30 seconds to allow the auxiliary heater to cool down The delay occurs when the auxiliary heat...

Страница 24: ...faults on page 18 3 Press the Mode button to access the programmable value of the displayed function number The function s current value flashes on the display 4 Press the Up or Down buttons to change...

Страница 25: ...reduced There is low airflow through the system The airflow through the evaporator is blocked Inspect for and remove any obstructions in the return air stream Clean the return air filter and grille C...

Страница 26: ...oad is open due to lack of air flow though the condenser Allow the compressor to cool Turn the system off for a while it may take up to three hours to reset the thermal overload 10 2 Digital Controls...

Страница 27: ...before reprogramming the Q3 control Change Programmable Function 21 to increase the duration of the Anti Icing Routine If the anti icing cycle does not melt the ice switch the air conditioning unit t...

Страница 28: ...ntrol board The low pressure switch opens when the suction pressure drops below a preset minimum limit If the low pressure switch opens the unit will first run for two minutes and then shut down for 5...

Страница 29: ...conds the Q3 control shows a constant Cool or Heat Mode may be selected for emergency operation and the display will show a constant Emergency Operation Ar FL The Q3 control flashes Ar FL for 15 secon...

Страница 30: ...aning the Return Air Filter Check the Return Air Filter once a month or more often if local conditions and usage patterns dictate and replace or clean as necessary To clean the filter Remove the filte...

Страница 31: ...coils may result in reduced performance Avoid the use of the following Coil brighteners High pressure washers Poor quality water for cleaning Use of non recommended coil cleaners is strongly discoura...

Страница 32: ...Mobile living made easy dometic com YOUR LOCAL DEALER dometic com dealer YOUR LOCAL SUPPORT dometic com contact YOUR LOCAL SALES OFFICE dometic com sales offices...

Отзывы: