Normally closed while the keypad is secured on its box. It is open when keypad is 
separated from its box. Connect this to an alarm system if necessary.  

 

10-12: O/P 2 OR BELL (Output Relay 2) 

 

10 (Normally closed) 

 

Use 10 for equipment that requires a constant flow of electricity to function 
properly. Ex. Magnetic locks, receivers, etc. 

 

11 (Common ground) 

 

12 (Normally open) 

 

Use 12 for equipment that requires a temporary surge of electricity to activate. Ex. 
Electric door locks, automated gates, etc. 

 

13: O/P 3 (Output Relay 3 N.O.) 

 

Output 3 is a normally open terminal 

 

14: DOOR SENS N.C. (Door Position Sensing Input -- Normally Closed) 

 

DOOR SENS must be connecting to ground if not used. This feature can be connected 
to a normally closed device (ex. A magnet) to sense a door’s status (being opened or 
closed). With DOOR SENS connected, the following features are possible: 

 

Door Auto Re-lock 

 

The system will immediately lock after a door/gate has been opened and closed. 

 

Door Forced Open Warning 

 

The system will signal a warning and trigger Alarm Output once the door is 
forced open without a valid access code or egress button. The warning signal 
lasts as long as programmed. Entering an output 1 code will deactivate the 
warning signal. 

 

Open Door Warning 

 

The door will signal a warning if the door is left open for longer than the 
programmed time. 

 

Interlock Control 

 

The Interlock Control is a two-keypad, two-door feature and it will disable the 
other keypad as long as its door is open and the keypads are connected by O/P 1 
INHIBIT and INT LOCK. 

 

Open Door Alarm 

 

Open Door Alarm is designed for the emergency door. When the door is opened 
without a valid access code or egress button, the alarm will trigger. The warning 
signal lasts as long as programmed. 

 

15: (-) GND (Common Ground) 

 

16: O/P 1 INHIBIT (Output 1 Inhibit Control Input – Normally Open) 

 

This is used for the dual keypad feature. It is normally open but will disable the keypad 
when closed. This is used in conjunction with INT LOCK. 

 

NOTE: The inhibit function does not govern the Duress Codes and the Authorization 
Codes. These are always valid. 

 

17: INT LOCK (Inter-lock Control Output) 

 

This is used for the dual keypad feature. Connect this to the other keypad’s O/P 1 
INHIBIT. 

 

18: K OR A O/P (Keypad Active or Alarm Output) 

 

When any key is pressed, the K OR A O/P will switch to ground for 10 seconds. Ex. It 
may be used to turn on a light, camera, or buzzer for 10 seconds the moment a button 
is pressed. It may also be used to trigger an alarm for a security system. Be sure to 
switch the jumper to K or A located on the upper-left corner of the circuit board. 

 

LED Indicators 

 

Red 

 

This becomes a solid color when Access Lock is activated. It is also the Wiegand 
LED in reader mode 

 

Yellow 

Содержание dolksf1kb

Страница 1: ...USER MANUAL Single Gang Flush Mount Keypad DOLKSF1KB V 3 6 18...

Страница 2: ......

Страница 3: ...ed Use N C for equipment that requires a constant flow of electricity to function properly Ex Magnetic locks receivers etc COM Common ground N O Normally open Use N O for equipment that requires a tem...

Страница 4: ...warning if the door is left open for longer than the programmed time Interlock Control The Interlock Control is a two keypad two door feature and it will disable the other keypad as long as its door...

Страница 5: ...RECT ACCESS PROGRAMMING WITH CODE 8080 By pressing the egress button and entering code 8080 during the 1 minute booting time the keypad will bypass the Master Code to enter Programming Mode Take these...

Страница 6: ...4 8 digit Access Code Set 4 8 digit code for general access Each unique 4 8 digit code will require a new user number Important Note It is important to document your user numbers because users can be...

Страница 7: ...tor Code 4 Output number 1 2 or 3 User number 01 50 Delete the user s Duress Code Clear all Visitor Codes 4 Output number 1 2 or 3 0999 Clear all Access Codes Lock Settings Set door unlock timer 5 Out...

Страница 8: ...code will be required but all codes may vary in digit length Blinking Yellow LED Settings Blinking Yellow LED On 731 The amber LED will blink every 2 seconds during functionality Blinking Yellow LED O...

Страница 9: ...cess Hold press warning 905 Hold duration in seconds 0 99 Holding the egress button for the defined duration will sound a warning and grant access Hold press warning and alarm 906 Hold duration in sec...

Страница 10: ...he lock parallel with the lock power terminals to absorb the back EMF and prevent keypad damage The 1N4004 is not required for AC power To avoid electrostatic discharge from interfering with the keypa...

Страница 11: ...O dry contacts 1A 24VDC Max Output Relay 3 N C N O dry contacts 1A 24VDC Max N O contact only for Door Bell version Tamper Switch N C dry contact 50mA 24VDC Max Dimensions DOLKSF1KB 4 3 4 H X 3 1 8 W...

Страница 12: ...ITY OR WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE BUYER MAKES NO RELIANCE ON ANY REPRESENTATION OF TRANSMITTER SOLUTIONS EXPRESS OR IMPLIED WITH REGARD TO THE GOODS AND ACCEPTS THEM AS IS WHERE IS T...

Отзывы: