Configurable Safety System SAFEMASTER PRO
11
0265525 / 16.05.19 en / 101A
GENERAL DESCRIPTION
SAFEMASTER PRO is a configurable safety system. It consists of a control unit UG 6911.10, which can be
configured using the SAFEMASTER PRO DESIGNER graphic interface, and a number of expansion modules
connected to the control unit UG 6911.10 via the proprietary IN-RAIL-BUS.
The control unit UG 6911.10 e. g. UG 6911.12/080 can also be used as a stand-alone device. and they are
equipped with:
• UG 6911.10:
8 safety inputs, 2 independent programmable dual channel safety outputs (OSSD)
and 2 logic signal outputs
• UG 6911.12/080:
8 safety inputs, 4 independent programmable single channel safety outputs (OSSD
and 4 logic signal outputs
The following expansions are available: Input / Output module (UG 6916.10 and UG 6916.12/080 (for
UG 6911.12/080 only)), input modules (UG 6913.08, UG 6913.12 and UG 6913.16), output modules OSSD
(UG 6912.02, UG 6912.04 and UG 6912.04/100), with dual channel semiconductor outputs, output
modules relays with guided contact safety relays (UG 6914.04/000, UG 6914.04/008, UG 6912.14 and
UG 6912.28), output modules with programmable signal outputs (UG 6915/008, UG 6915/016) and several
speed monitoring modules (UG 6917/xx2).
The BusExtender module UG 6918 allows a decentralized system with module connection at great distance
For diagnostic over the main fieldbus, following fieldbus modules are available: UG 6951 (CanOpen),
UG 6952 (PROFIBUS), UG 6954 (PROFINET), UG 6955 (Ethernet IP), UG 6956 (EtherCAT),
UG 6957 (Universal Serial Bus), UG 6958 (MODBUS TCP/IP) and UG 6959 (MODBUS RTU).
For more detailed information, consult the fieldbus manual on the SAFEMASTER PRO Designer CD-ROM.
SAFEMASTER PRO is capable of monitoring the following safety sensors and commands:
Optoelectronic sensors (safety light curtains, scanners, safety photocells), mechanical switches, safety mats,
emergency stops, two-hand controls, all managed by a single flexible and expandable device.
The system must consist of just one control unit UG 6911.10 (or UG 6911.12/080) and a number of electronic
expansions that can range from 0 to a maximum of 14, not more than 4 of which of the same type. There is no
limit to the number of relay units that can be installed.
With 14 expansions, the system can have up to:
• UG 6911.10:
128 inputs, 16 safety outputs and 32 status outputs
• UG 6911.12/080:
128 inputs, 32 safety outputs and 48 status outputs
The control unit and its expansions modules communicate via the 5-way IN-RAIL-BUS (from DOLD), physically
arranged on the rear panel of each unit.
Furthermore 8 inputs and 16 outputs probe controllable (by Fieldbus) are available.
The SAFEMASTER PRO DESIGNER software is capable of creating complex logics, using logical operators
and safety functions such as muting, timer, counters, etc.
All this is performed through an easy and intuitive graphic interface.
The configuration performed on the PC is sent to the control unit UG 6911.10 (or UG 6911.12/080) via USB
connection; the file resides in the control unit uand can also be saved on the proprietary OA 6911 memory
chip (accessory). The configuration can therefore quickly be copied to another control unit UG 6911.10
(or UG 6911.12/080).
The modules UG 6912.04/100, UG 6915/008 and UG 6915/016 are available from UG 6911.10 firmware
version 3.0 or higher.
The SAFEMASTER PRO system is certified to the maximum safety level envisaged by the applicable
industrial safety standards (SIL 3, SILCL 3, PL e, Cat. 4).
Содержание Safemaster Pro
Страница 8: ...Configurable Safety System SAFEMASTER PRO 8 0265525 16 05 19 en 101A...
Страница 198: ...Configurable Safety System SAFEMASTER PRO 198 0265525 16 05 19 en 101A DECLARATION OF CONFORMITY...
Страница 199: ...Configurable Safety System SAFEMASTER PRO 199 0265525 16 05 19 en 101A DECLARATION OF CONFORMITY...