Configurable Safety System SAFEMASTER PRO
19
0265525 / 16.05.19 en / 101A
Connection Terminals Control unit UG 6916.10
Connection Terminals Control unit UG 6916.12/080
TERMINAL
SIGNAL
TYPE
DESCRIPTION
OPERATION
1
24VDC
-
24 V DC power supply
-
2
NODE_SEL0
Input
Node selection
Input („Type 2“ acc. to EN 61131-2)
3
NODE_SEL1
Input
Input („Type 2“ acc. to EN 61131-2)
4
0VDC
-
0 V DC power supply
-
5
OSSD1_A
Output
Static output 1
PNP active high
6
OSSD1_B
Output
PNP active high
7
RESTART_FBK1
Input
Feedback / Restart 1
Input („Type 2“ acc. to EN 61131-2)
8
OUT_STATUS1
Output
Programmable signal output
PNP active high
9
OSSD2_A
Output
Static output 2
PNP active high
10
OSSD2_B
Output
PNP active high
11
RESTART_FBK2
Input
Feedback / Restart 2
Input („Type 2“ acc. to EN 61131-2)
12
OUT_STATUS2
Output
Programmable signal output
PNP active high
13
OUT_TEST1
Output
Short circuit detection output
PNP active high
14
OUT_TEST2
Output
Short circuit detection output
PNP active high
15
OUT_TEST3
Output
Short circuit detection output
PNP active high
16
OUT_TEST4
Output
Short circuit detection output
PNP active high
17
INPUT1
Input
Digital input 1
Input („Type 2“ acc. to EN 61131-2)
18
INPUT2
Input
Digital input 2
Input („Type 2“ acc. to EN 61131-2)
19
INPUT3
Input
Digital input 3
Input („Type 2“ acc. to EN 61131-2)
20
INPUT4
Input
Digital input 4
Input („Type 2“ acc. to EN 61131-2)
21
INPUT5
Input
Digital input 5
Input („Type 2“ acc. to EN 61131-2)
22
INPUT6
Input
Digital input 6
Input („Type 2“ acc. to EN 61131-2)
23
INPUT7
Input
Digital input 7
Input („Type 2“ acc. to EN 61131-2)
24
INPUT8
Input
Digital input 8
Input („Type 2“ acc. to EN 61131-2)
TERMINAL
SIGNAL
TYPE
DESCRIPTION
OPERATION
1
24VDC
-
24 V DC power supply
-
2
NODE_SEL0
Input
Node selection
Input („Type 2“ acc. to EN 61131-2)
3
NODE_SEL1
Input
Input („Type 2“ acc. to EN 61131-2)
4
0VDC
-
0 V DC power supply
-
5
OSSD1
Output
Static output 1
PNP active high
6
OSSD2
Output
Static output 2
PNP active high
7
RESTART_FBK1/
STATUS1
Input/
Output
Feedback / Restart 1
Input („Type 2“ acc. to EN 61131-2)
Programmable signal output
PNP active high
8
RESTART_FBK2/
STATUS2
Input/
Output
Feedback / Restart 2
Input („Type 2“ acc. to EN 61131-2)
Programmable signal output
PNP active high
9
OSSD3
Output
Static output 3
PNP active high
10
OSSD4
Output
Static output 4
PNP active high
11
RESTART_FBK3/
STATUS3
Input/
Output
Feedback / Restart 3
Input („Type 2“ acc. to EN 61131-2)
Programmable signal output
PNP active high
12
RESTART_FBK4/
STATUS4
Input/
Output
Feedback / Restart 4
Input („Type 2“ acc. to EN 61131-2)
Programmable signal output
PNP active high
13
OUT_TEST1
Output
Short circuit detection output
PNP active high
14
OUT_TEST2
Output
Short circuit detection output
PNP active high
15
OUT_TEST3
Output
Short circuit detection output
PNP active high
16
OUT_TEST4
Output
Short circuit detection output
PNP active high
17
INPUT1
Input
Digital input 1
Input („Type 2“ acc. to EN 61131-2)
18
INPUT2
Input
Digital input 2
Input („Type 2“ acc. to EN 61131-2)
19
INPUT3
Input
Digital input 3
Input („Type 2“ acc. to EN 61131-2)
20
INPUT4
Input
Digital input 4
Input („Type 2“ acc. to EN 61131-2)
21
INPUT5
Input
Digital input 5
Input („Type 2“ acc. to EN 61131-2)
22
INPUT6
Input
Digital input 6
Input („Type 2“ acc. to EN 61131-2)
23
INPUT7
Input
Digital input 7
Input („Type 2“ acc. to EN 61131-2)
24
INPUT8
Input
Digital input 8
Input („Type 2“ acc. to EN 61131-2)
The STATUS signal outputs are shared with the feedback/restart inputs of the OSSDs. To use them,
the corresponding OSSD must be used with automatic reset without external feedback monitoring. For
example, to use the STATUS1 output (Terminal 7), you must program OSSD1 with automatic reset without
K feedback monitoring.