19
BG 5925 / 02.05.17 en / 851
Application Examples
2-channel safety gate monitoring.
Note: Refer to „Unit programming“!
Switches in pos.:
S1 no cross fault detection
S2 manual start
Suited up to SIL3, Performance Level e, Cat. 4
2-channel emergency stop circuit with cross fault detection
Note: Refer to „Unit programming“!
Switches in pos.:
S1 cross fault detection
S2 manual start
Suited up to SIL3, Performance Level e, Cat. 4
Contact reinforcement by external contactors, 2-channel controlled.
The output contacts can be reinforced by external contactors with forcibly
guided contacts for switching currents > 8 A.
Functioning of the external contactors is monitored by looping the NC
contacts into the closing circuit (terminals S33-S34).
Note: Refer to „Unit programming“!
Switches in pos.:
S1 no cross fault detection
S2
manual
start
Suited up to SIL3, Performance Level e, Cat. 4
K5
K4
L1
M7120_a
N
E-stop
A2(-)
A1(+) S11
S34
S33
S12 S22
S21
On
K5
K4
13
23
14
24
BG5925
..
..
Contact reinforcement by external contactors controlled by one contact
path.
Note: Refer to „Unit programming“!
Switches in pos.:
S1 no cross fault detection
S2
manual
start
Suited up to SIL3, Performance Level e, Cat. 4
13
14
K5
K4
L1
M7119_a
N
E-stop
A2(-)
A1(+) S11
S34
S33
S12 S22
S21
On
K5
K4
BG5925
..
..
..
..
2-channel emergency stop circuit without cross fault monitoring.
Note: Refer to „Unit programming“!
Switches in pos.:
S1 no cross fault detection
S2
manual
start
Suited up to SIL3, Performance Level e, Cat. 4
Single channel emergency stop circuit. This circuit does not have any red-
undancy in the emergency-stop control circuit.
Note: Refer to „Unit programming“!
Switches in pos.:
S1 no cross fault detection
S2
manual
start
Suited up to SIL2, Performance Level d, Cat. 3