Operating instructions 

ENGLISH

  SAFEMASTER

 

Delay module, on delayed 

  LG 7927

0264222

The LG 7927 is used to start or to delay a movement or to enable safety 
interlocks as e.g. SAFEMASTER STS.

When used in accordance with its intended purpose and following these 
operating instructions, this device presents no known residual risks. Non-
observance may lead to personal injuries and damages to property.

 

Designated use

  Main features

Your advantage

  Easy to realise safe timing circuits

  4 positive guided output contacts at only 22.5 mm width

Features

  According to

  - Performance Level (PL) d and category 3 to EN ISO 13849-1: 2008

  - SIL Claimed Level (SIL CL) 2 to IEC/EN 62061

  - Safety Integrity Level (SIL) 2 to IEC/EN 61508 and IEC/EN 61511

  when connected to a suitable safety module

  Adjustable time delay

  As option fixed time delay

  High long life stability due to digital time base  

  Adjustable with or without cross fault detection

  Output: 3 NO co 1 NC c 1 positive guided 

  feedback contact 

  or 4 NO co 1 1 positive guided feedback contact 

  LED indicator for channel 1, 2 and operation voltage

  Removable terminal strips 

  -  LG 7927:   

fixed screw terminals

  -  LG 7927 PS: 

plug in screw terminals

  -  LG 7927 PC: 

plug in cage clamp terminals

  Connection Terminals

Before installing, operating or maintaining this device, these instructions 
must be carefully read and understood.

  

DANGER

  

CAUTION

Dangerous voltage.
Electric shock will result in death or serious injury.

Disconnect all power supplies before servicing equipment.

Safe operation of the device is only guaranteed when using certified 
components!

 

Important Notes

The product hereby described was developed to perform safety functions 
as a part of a whole installation or machine. A complete safety system 
normally includes sensors, evaluation units, signals and logical modules 
for safe disconnections. The manufacturer of the installation or machine 
is responsible for ensuring proper functioning of the whole system. DOLD  
cannot guarantee all the specifications of an installation or machine that 
was not designed by DOLD. The total concept of the control system into 
which the device is integrated must be validated by the user. DOLD also 
takes over no liability for recommendations which are given or implied in 
the following description. The following description implies no modification 
of the general Contrinex terms of delivery, warranty or liability claims.

 

Safety Regulations

-  This device must be installed and operated by trained staff who are  

 

familiar with these instructions and with the current regulations for safety  

  at work and accident prevention.

-  Pay attention to applicable local regulations, especially regarding safety  

 measures.

-  The shock protection on the connected elements and the cable insulation 

  must be designed for the highest voltage applied to the device.

-  Opening the device or implementing unauthorized changes voids any  

 warranty

-  The unit should be panel mounted in an enclosure rated at IP 54 or  

  superior. Dust and dampness may lead to malfunction.

-  Adequate fuse protection must be provided on all output contacts with  

  capacitive and inductive loads.
-  The safety function must be triggered during commissioning

  

 

Safety notes

Attention!

To achieve the safety levels stated under features, a the 

supervising control must check the NC contact 55/56 be-

fore starting to make sure that both relays (Kt1 and Kt2) 

are switched off.

 

Indication

LED "Power": 

 

on, when supply connected

LED K1t and K2t:   on, when relay K1t and K2t energized

Terminal designation

Signal designation

A1 (+)

+ / L

A2 (-)

- / N

S11, S21

Inputs

Y1, Y2

Outputs

17, 18, 27, 28, 37, 38, 47, 48

Positive driven NO contacts for 
release circuit

45, 46

Positive guided indicator output

55, 56

Positive guided feedback circuit

 

Function diagram

M10115

tv

tv

37-38

55-56

27-28

45-46

17-18

Y2

Y1

A1/A2

U

UN

ORIGINAL

All technical data in this list relate to the state at the moment of edition. We reserve the right for 
technical improvements and changes at any time.

Содержание LG 7927

Страница 1: ...er Funktionen f hren Sorgen Sie an allen Ausgangskontakten bei kapazitiven und induktiven Lasten f r eine ausreichende Schutzbeschaltung Die Sicherheitsfunktion muss bei Inbetriebnahme ausgel st werde...

Страница 2: ...rge zwischen Versorgungsleitungen 1 kV IEC EN 61 000 4 5 zwischen Leitung und Erde 2 kV IEC EN 61 000 4 5 HF leitungsgef hrt 10 V IEC EN 61 000 4 6 Funkentst rung Grenzwert Klasse B EN 55 011 Technisc...

Страница 3: ...installation or machine is responsible for ensuring proper functioning of the whole system DOLD cannot guarantee all the specifications of an installation or machine that was not designed by DOLD The...

Страница 4: ...IEC EN 61 000 4 3 Fast transients 2 kV IEC EN 61 000 4 4 Surge voltage between wires for power supply 1 kV IEC EN 61 000 4 5 between wire and ground 2 kV IEC EN 61 000 4 5 HF wire guided 10 V IEC EN 6...

Страница 5: ...achine dont la conception lui chappe C est l utilisateur de valider la conception globale du syst me auquel ce relais est connect DOLD ne prend en charge aucune responsabilit quantauxrecommandationsqu...

Страница 6: ...6 Tensions transitoires 2 kV IEC EN 61 000 4 4 Surtensions entre c bles d alimentation 1 kV IEC EN 61 000 4 5 entre c bles et terre 2 kV IEC EN 61 000 4 5 HFinduite par conducteurs 10 V IEC EN 61 000...

Страница 7: ...et bis SIL2 Performance Level d Kat 3 EN LG 5925 with 2 LG 7927 non cross fault detection suitable up to SIL2 Performance Level d Cat 3 FR LG 5925 avec 2 LG 7927 sans reconnaissance de cc transversaux...

Страница 8: ...AWG 20 to 18 A 10 12 mm 1 x 0 5 1 5 mm2 1 x AWG 20 to 16 A 12 mm 1 x 0 5 2 5 mm2 1 x AWG 20 to 14 M10250 A A 8 mm 1 x 0 5 4 mm2 1 x AWG 20 to 12 2 x 0 5 2 5 mm2 2 x AWG 20 to 14 A 8 mm 1 x 0 5 2 5 mm...

Страница 9: ...e the adjustment of the time as the time potentiometer has to be set fully anti clock wise before removing the front plate After selecting the operating mode the front plate is remounted Please make s...

Страница 10: ...om Anwender bestimmt werden EN The values stated above are valid for the standard type Safety data for other variants are available on request The safety relevant data of the complete system has to be...

Страница 11: ...11 LG 7927 141119 486...

Страница 12: ...12 LG 7927 141119 486 E DOLD S HNE KG D 78120 Furtwangen e mail dold relays dold com internet http www dold com Bregstra e 18 Telefon 0 77 23 654 0 Telefax 0 77 23 654 356...

Отзывы: