14 AutoPing
61
14
AutoPing
AutoPing can monitor a network device and perform a task if the device stops responding. It can also monitor a
group of devices, the task will be executed if none of the group members respond. The task is either a list of outlets
to reboot or a script to execute.
14.1
Common configuration
AutoPing Properties
Enable AutoPing:
Time between pings:
30
seconds. (2-3600)
Ping timeout to reboot:
150
seconds. (2-3600)
Ping responses to enable autoping:
5
pings. (0-100)
Times to attempt reboot:
5
tries. (1-255)
Device reboot delay:
120
seconds. (1-43200)
Apply
Common AutoPing settings
Be sure to enable AutoPing operation by ticking the "Enable AutoPing" checkbox. Certain
may
turn it off automatically.
The following parameters are used for AutoPing operation:
• Time between pings: This is the time between each ping check of an address. 60 seconds should be useful
for most applications.
• Ping timeout to reboot: This sets the maximum time that sequential communication attempts may fail. Any
failure beyond this time limit will cause the task to be executed. For example, when set to 300 seconds
and a time between pings is 30 seconds, if a target system fails to any pings for 330 seconds, the task
will be executed. The ping that occurred after 300 seconds came at 330 seconds and still failed. Since
occasional network overloads and missed packets can occur during normal network operation, be sure to
choose a reasonable time. AutoPing may handle certain failures immediately instead of waiting for the timeout
if configured to (see below).
• Ping responses to enable autoping: To ensure a reliable connection, autoping will only be enabled after this
many successful pings. We do not recommend changing this (10 is default) unless you must configure your
controller before connecting it to the target devices.
• Times to attempt reboot: If you have an unreliable target device, limit the number of times it will be rebooted
by entering that value here. For example, entering 5 will execute the task up to 5 times before giving up.
• Device reboot delay: After rebooting a device with a cold-boot power-off, a waiting period should occur before
the IP address is re-checked by AutoPing. This delay allows the device to reboot. Windows and Linux servers
can force automatic file system checks which may take several minutes to complete. Enter a safe value here,
for example entering 600 would cause the power controller to start checking the server for normal operation
10 minutes after reboot. If a script is to be triggered, any delays contained in the code being executed should
be considered in determining the delay setting here so that the thread completes before the delay elapses.
This timer starts at the execution of the thread started.
DLI LPC9 User’s Guide: 1.7.24.0
Содержание LPC9
Страница 1: ...DLI LPC9 User s Guide 1 7 24 0 ...
Страница 81: ......