Instructions regarding intended installation:

Vehicular gates should be constructed and installed in accordance with ASTM F2200; Standard Specification for Automated 
Vehicular Gate Construction. For a copy of this standard, contact ASTM directly at 610-832-9585; [email protected]; or 

www.astm.org

Important Safety Instructions

WARNING - To reduce the risk of injury or death: 

1. READ AND FOLLOW ALL INSTRUCTIONS. 
2. Never let children operate or play with gate controls. Keep the remote control away from children. 
3. Always keep people and objects away from gate. 

NO ONE SHOULD CROSS THE PATH OF THE MOVING GATE. 

4. Test the operator monthly. The gate MUST reverse on contact with a rigid object or stop or reverse when an object    
  activates the non-contact sensors. After adjusting the force or the limit of travel, retest the gate operator. Failure to adjust  
  and retest the gate operator properly can increase the risk of injury or death. 
5. Use the emergency release only when the gate is not moving. 
6. KEEP GATES PROPERLY MAINTAINED. Read the owner's manual. Have a qualified service person make repairs to gate  
 hardware. 
7. The entrance is for vehicles only. Pedestrians must use separate entrance. 
8. 

SAVE THESE INSTRUCTIONS! 

 Install the gate operator only if:

    1. The operator is appropriate for the construction of the gate and the usage class of the gate.
    2. All openings of a horizontal slide gate are guarded or screened from the bottom of the gate to a minimum of 6 feet  
      (1.83 m) above the ground to prevent a 2 ¼ inch (57.2 mm) diameter sphere from passing through the openings  
      anywhere in the gate, and in that portion of the adjacent fence that the gate covers in the open position.
    3. All exposed pinch points are eliminated or guarded.
    4. Guarding is supplied for exposed rollers. 

 The operator is intended for installation only on gates used for vehicles. Pedestrians must be supplied with a separate  

  access opening. The pedestrian access opening shall be designed to promote pedestrian usage. Locate the gate such that  
  persons will not come in contact with the vehicular gate during the entire path of travel of the vehicular gate. 

 The gate must be installed in a location so that enough clearance is supplied between the gate and adjacent structures  

  when opening and closing to reduce the risk of entrapment. Swinging gates should not open into public access areas.

 The gate must be properly installed and work freely in both directions prior to the installation of the gate operator. Do not  

  over-tighten the operator clutch, pressure relief valve or reduce reversing sensitivity to compensate for a damaged gate.

 For gate operators utilizing Type D protection:

    1. The gate operator controls must be placed so that the user has full view of the gate area when the gate is moving.
    2. A warning placard shall be placed adjacent to the controls.
    3. An automatic closing device (such as a timer, loop sensor, or similar device) shall not be employed.
    4. No other activation device shall be connected.

 Controls intended for user activation must be located at least ten feet (10’) away from any moving part of the gate and  

  where the user is prevented from reaching over, under, around or through the gate to operate the controls. Outdoor or  
  easily accessible controls should have a security feature to prevent unauthorized use.

 The Stop and/or Reset button must be located in the line-of-sight of the gate. Activation of the reset control shall not   

  cause the operator to start.

 A minimum of two (2) WARNING SIGNS shall be installed, one on each side of the gate where easily visible.

 For gate operators utilizing a non-contact sensor: 

    1. See the instructions on the placement of non-contact sensors for each type of application.
    2. Care shall be exercised to reduce the risk of nuisance tripping, such as when a vehicle trips the sensor while the gate  
      is still moving in the opening direction.
    3. One or more non-contact sensors shall be located where the risk of entrapment or obstruction exist, such as the  
      perimeter reachable by a moving gate or barrier.

Содержание 9024

Страница 1: ...tic clos ing de vice suc h as a tim er loop se ns or or simila r de vice sh all no t be em ploy ed SERIO US IN JURY OR DEATH CL AS S CE RTIFIED TO CA N C SA C2 2 2 NO 24 7 CO NFO RMS TO AN SI U L 32 5...

Страница 2: ......

Страница 3: ...imary Inherent entrapment sensing system Type A Secondary Provision for connection of photo sensors Type B1 and or reversing edges Type B2 Use this manual for the Model 9024 operator with circuit boar...

Страница 4: ...ete Pad Setup or Optional Post Mount Kit 1 6 Positioning Operator and Chain 1 7 Attaching Operator and Chain 1 8 Endless Idler Assembly On Select Installations 1 9 DoorKing s Chain Tray Kit 1 10 Insta...

Страница 5: ...stics 8 3 Troubleshooting 8 4 Accessory Items Model 9024 080 AC Input Power ONLY Wiring Diagram Model 9024 081 Solar Input Power ONLY Wiring Diagram 39 39 40 41 42 43 44 SECTION 7 OPERATING INSTRUCTIO...

Страница 6: ...uld be installed in this area for safety See on next page and page 30 A gap measured in the horizontal plane parallel to the roadway between a fixed stationary object nearest the roadway such as a gat...

Страница 7: ...horizontally or vertically project no more than is required to perform their intended function Physical Stops Permanently mounted and easily visible from either side of the gate Warning Signs Non Cont...

Страница 8: ...separate access opening The pedestrian access opening shall be designed to promote pedestrian usage Locate the gate such that persons will not come in contact with the vehicular gate during the entire...

Страница 9: ...d and maintained serious injuries or death can result Be sure that the installer has instructed you on the proper operation of the gate and gate operator system Be sure that the installer has trained...

Страница 10: ...in which unauthorized access is prevented via supervision by security personnel This table illustrates the entrapment protection requirements for each of the four UL 325 classes A Inherent entrapment...

Страница 11: ...for vehicular traffic flow at entrances or exits to areas such as parking garages lots or toll areas VEHICULAR HORIZONTAL SLIDE GATE OPERATOR OR SYSTEM A vehicular gate operator or system that control...

Страница 12: ...minimize a pinch point for a 180 chain return Guide Rollers with Protective Covers Helps to minimize a pinch point on the gate Roller Bearing V Wheels with Protective Cover Helps to minimize a pinch p...

Страница 13: ...positions Cantilever Steel or Aluminum 1 000 lb max weight per gate Chain tray recommended for gates over 20 ft Post mount installation when using a chain tray Single operator 40 ft max gate length D...

Страница 14: ...ps Once the mounting position has been selected refer to pages 15 thru 18 for specific installation instructions Top View Idler Wheels and Chain Setup Top View Idler Wheels and Chain Setup Set operato...

Страница 15: ...eights Idler Wheels and Chain Setup Set one chain Idler wheel at the center and one in the bottom position Set one chain Idler wheel at the top and one in the center position Idler Wheels and Chain Se...

Страница 16: ...to attach to gate This is useful with long gates It supports the chain s weight and helps prevent chain stretching Gate in Close Position Endless Idler Endless Idler Gate in Open Position Gate shown i...

Страница 17: ...t specifically for the Model 9024 P N 9000 015 The kit includes a base plate 2 posts and hardware to attach the operator to the base plate This kit will raise the operator and allow different chain he...

Страница 18: ...ghten the chain Operator and chain are NOT parallel to gate Chain bracket does NOT align with idler wheels Chain bracket MUST line up with chain idler wheels Chain brackets MUST be mounted so the chai...

Страница 19: ...Make sure the endless idler assembly is securely fastened to the wall or post Depending on which type of installation will be used Extreme force will be exerted on this assembly during gate cycling L...

Страница 20: ...ppropriate hardware such as wood or sheet metal screws not supplied to install the warning signs 1 9 DoorKing s Chain Tray Kit The Chain tray supporting brackets can be mounted facing up as shown or f...

Страница 21: ...during the summer months will cast longer shadows in the winter which could block the panel then Wind can exert extreme pressure on the solar panel and support post Make sure they are securely fasten...

Страница 22: ...panel is oriented to TRUE SOUTH The directions of magnetic South and TRUE South differ from one another depending on geographic location The map below shows the difference between magnetic south and...

Страница 23: ...ed from the operator DO NOT install a heater kit when using solar power Cover solar panel BEFORE connecting wire to power terminal Route incoming solar power wire through the solar panel conduit and r...

Страница 24: ...il the DIP Switches and the Limit Switches have been adjusted Damage could occur to the gate and gate operator See pages 26 27 and 28 DC Power Switch KEY SWITCH Battery Charging LED Monitor OFF ON To...

Страница 25: ...or electronic box Be sure wiring is installed in accordance with local codes Be sure to color code all wiring It is recommended that a surge suppressor be installed on the high voltage power lines to...

Страница 26: ...using Type D entrapment protection an automatic closing device such as a timer loop sensor or similar device shall not be employed SERIOUS INJURY OR DEATH CLASS CERTIFIED TO CAN CSA C22 2 NO 247 CONF...

Страница 27: ...oop LEDs Input LEDs See page 34 Tracker Data See page 33 Input LEDs should be OFF and will only illuminate when the input that is next to the LED is activated See page 34 Limit LEDs will only illumina...

Страница 28: ...de Gate Operator Swing Gate Operator Barrier Gate Operator Overhead Gate Operator Switch Function Setting Description SW 2 Bottom 8 Switches Switches 7 and 8 MUST be turned OFF for Model 9024 operator...

Страница 29: ...auto close timer potentiometer This will also cause an opening gate to stop and reverse when the reverse loops and or photo sensors are cleared after vehicle passes by them Switches 6 7 These work in...

Страница 30: ...aged in the slots on the limit nuts to prevent them from rotating Loosen adjustment nut to position the partial open assembly to stop the opening gate at a desired Partial Open position Partial Open F...

Страница 31: ...ULL open limit switch setting and NOT the partial open setting For the reverse system to function correctly the gate must be properly installed and work freely in both directions and the limit switche...

Страница 32: ...otection device inputs CLOSE Contact Sensor Reversing Edge Obstructed closing direction reversing edge will stop then reverse the gate to the open position during the closing direction only After the...

Страница 33: ...hould be installed on the post or barrier for safety See page 4 for more information Photo Sensor Power Note Photo sensors can be powered by the built in convenience outlets model 9024 080 ONLY locate...

Страница 34: ...Direction Reversing Edge Opening Direction Reversing Edge Opening Direction Reversing Edge If filler post is used 9 V battery operated transmitter mounted on gate Filler Post If necessary Edge Transmi...

Страница 35: ...thout having to use a transmitter or keypad The exit loop can be placed a minimum of 4 feet away from the reverse loop or far enough away from the gate so the gate has started opening or even complete...

Страница 36: ...ugged into the EXIT loop port Used for specialized functions ON 1 2 3 4 5 6 7 8 SW 1 This input ONLY functions when gate is fully opened or in the closing cycle When gate is closing SW 1 switch 4 is O...

Страница 37: ...rd will activate the gate operator Refer to the manual 2358 065 for detailed information ON 1 2 3 4 5 6 7 8 SW 1 OFF ON P N 9024 005 A 8 13 Depend ant on SW1 switch 4 Depend ant on SW1 switch 3 Fire D...

Страница 38: ...a r The gate is capa ble of bein g mov ed with out prio r warn ing Do not let child ren oper ate the gate or play in the gate area This entr ance is for vehi cles only Pede stria ns mus t use a sepa r...

Страница 39: ...the open position If the inherent entrapment protection gets activated during this opening cycle the gate reverses and runs back to the closed position After the inherent entrapment protection is cle...

Страница 40: ...gate until you have verified that ALL power to operator has been shut off Pull Manual Release Handle Pull straight OUT as far as possible and then UP Manually Push Gate to Desired Position 1 Release...

Страница 41: ...ion The alarm will continue to sound for five minutes and then will chirp once every five seconds The operator reset button must be pressed or power must be removed and then reapplied to return the op...

Страница 42: ...to the motor or a bad control board If the motor runs in both steps above contunue troubleshooting control board and accessories Operator will not run Power LED is ON 1 Check the input indicator LEDs...

Страница 43: ...ol board lights when the keying device connected to the respective terminal is activated If LED does not light momentarily place a jumper wire from terminal 1 to the input terminal being checked If LE...

Страница 44: ...old and hot environments For 115 VAC input power ONLY P N 1601 154 208 230 VAC Heater with Fan Assembly Kit Thermostatically controlled heater and fan for cold and hot environments For 208 230 VAC inp...

Страница 45: ...Selector Switch 115 VAC Outlet 115 VAC Outlet Capacitor 4700uF Resistor 1K Bridge Rectifier Transformer Toroidal Blue Blue Blue Blue Blue NO NO NO Com Com Com Purple Purple Purple Red Red Red Red Red...

Страница 46: ...P N XXXX XXX DC Power Switch Solar Power Input Terminal Solar Panel NO NO NO Com Com Com Red Support Post Not Included Red Red to Pos Red to Pos Black Black Black to Neg Black to Neg To Neg To Pos Ora...

Страница 47: ...9024 065 G 11 14 45...

Страница 48: ...this manual for circuit board 4405 010 Revision D or higher www doorking com Vehicular Slide Gate Operator DoorKing Inc 120 S Glasgow Avenue Inglewood California 90301 U S A Phone 310 645 0023 Fax 310...

Отзывы: