1592015620 Quick reference guide iCHILL 200D EVO FW 4.5 rel. 1.0.doc
42/42
Type of analogue output:
(configurable via software parameter)
3 configurable outputs:
- OUT1: 0-10Vdc
- OUT2 and OUT 3:
0-10Vdc
4-20mA
PWM (to use with Dixell XV serie)
Maximum load:
40mA (Out1..Out4) when connected to an external
relay
Accuracy:
Out1..Out3: ±2% full scale
Note:
The electrical devices controlled by these analogue
outputs must be powered separately with another
transformer (do not use the same secondary of the
controller's power) in order to prevent the outputs
from malfunctioning or being damaged.
18.5 DIGITAL OUTPUTS
Type:
Relays with NO contacts
Number of outputs:
5: IC205D model
7: IC207D model
Maximum load:
5A(250Vac) SPST 5(2)A
Note:
Verify maximum current of the loads and maximum
current of the common line of the relay (10A max).
There is double insulation between the digital outputs
and the low voltage of the rest of the circuit.
Do not use different voltages for the various groups
of relays nor within each group.
18.6
OPERATING AND STORAGE TEMPERATURE
Operating temperature:
-10°C ÷ 55°C
Storege temperature:
-30°C ÷ 85°C
Operating humidity: