1592015620 Quick reference guide iCHILL 200D EVO FW 4.5 rel. 1.0.doc
11/42
lower display shows SetH (set heat pump);
press SET key again, lower display shows SEtr (set real of operation, in the case
where the Energy Saving and / or function dynamic set point are active);
press SET key again, lower display shows SEtS (set domestic water circuit, in
case it is enabled)
6.2 MODIFY THE SET POINT
push
SET
key for at least
3
seconds
use the
UP
or
DOWN
key to modify the setpoint. In chiller mode it is possible to modify the
chiller set point, in heat pump it is possible to modify the heat pump set point, in std-by it is
possible to modify both the set point.
push
SET
to confirm or wait the timeout (15seconds).
7. KEY FUNCTION
KEY
ACTION
FUNCTION
Push and release
Show chiller set point
SetC,
heat pump set point
SetH,
sanitay water set point
SetS
Push once again
In chiller or heat pump if the Energy saving or the
Dynamic setpoint are enabled it shows the real
setpoint
Setr.
Push for 3 seconds
Set point modification
During the programming: push
once
To enter parameter modification or confirm a
value
Push when an alarm is showed
in menù ALrM
To reset the alarm
Push once with probe label
showed on the bottom display
(press up or down starting from
default visualization)
To read probes values of circuit 1 or circuit 2
Push once
To read probes value
Pushing once during the
programming
To change the group of parameters, to change
the parameter, to change the value of the
parameter
Push for 1 second during the
programming when the display
visualize Pr1 or Pr2 or Pr3
1 time shows the Pr2 programming level
2 times shows the Pr3 programming level
Push once
To read probes value
Pushing once during the
programming
To change the group of parameters, to change
the parameter, to change the value of the
parameter
Push once
To turn ON or turn OFF the controller (in chiller or
heat pump depending from CF58 parameter)