1592015620 Quick reference guide iCHILL 200D EVO FW 4.5 rel. 1.0.doc
15/42
5.
Push
UP
or
DOWN
to select Pr3 password
6.
Push
SET
and, if the value is correct, the top display shows the first family of parameters
“ALL”
7.
Push
UP
or
DOWN
to select the parameter family
8.
Push
SET
to enter; the bottom display shows the first available parameter label while the top
display shows its value
9.
Push
UP
or
DOWN
to modify its value
10. Push
SET
to confirm the new value
11. If necessary, modify others parameter
12. Push
SET
+
UP
keys together to exit parameters programming
11. MENU ( MENU KEY)
Enter the menu:
• press the menu button;
• press the UP or DOWN button to select the submenu;
• press the SET to enter the submenu.
Exit menu functions:
• Press the menu button or wait the time-out.
Entering the menu, it is possbile to:
1. Read and reset the alarms (
ALrM)
2. Read and reset the alarm log (
ALOG)
3. Upload the parameter into the Hot Key (
UPL)
4. Enable – disable a gas circuit (
CrEn)
5. Enable – disable a compressors (
COEn)
6. Read and reset the number of compressor running hour (
Hour)
7. Read and reset the number of compressor starts-up (
COSn)
8. Read dynamic set point probe value
(
PbdS
)
9. Read compressor discharge temperature (
COdt)
10. Read condensing fan speed percentage of the proportional output (
Cond)
11. Read the percentage of the proportional output 0 ÷ 10 Vdc
Pout
12. Enable – disable one of the pumps
POEn
13. Read the delay time between two defrost cycles (
dF)
14.
Read auxiliary output probe value (
uS)
15.
Read the temperature measured by internal sensor of the remote keyboards
(
trEM)
16.
Read the temperature, the set point and the output status of the Free cooling
(FC)
17.
Read the temperature, the set point and the output status of the Solar panel
(SoL)
18.
Read temperature, pressure and status of the electronic expansion valve 1
(Et1)
19.
Read temperature, pressure and status of the electronic expansion valve 2
(Et2)
11.1 ALARM LIST: READ AND RESET
ALrM FUNCTION