- 33 -
0DT872 01-12-2021
5.1 52E CONTROL PANEL (INVERTER) - Connections
INPUTS
Command
Function
Description
1
2
NC STOP
If on the programming menu (page 15 point 16)
Contact 1-2 enabled, opening of the contact STOPS the door
1
3
NO Opening
The closure of the contact activates the opening operation.
1
4
NO Closure
The closure of the contact activates the closing operation.
41
40
NC Reversal safety
contact
Opening the safety contact triggers a reversal of the movement (reopening)
during the closing operation.
1
8
NC Reversal safety
contact
Opening the safety contact triggers a reversal of the movement (reopening)
during the closing operation.
1
20
NO Partial opening
Closing of the contact activates a partial opening operation of the duration set
with the advanced menu.
1
11
NC Closing position
Opening of the contact indicates the closing position. (max. 50 mA)
1
13
NC Opening position
Opening of the contact indicates the opening position. (max. 50 mA)
1
9
NC Dead man
By external selector
OUTPUTS
Output
Value
Description
1
0
+
-
24V = / 0.5A
Power supply to accessories.
Power supply output for external accessories, including automation status
lamps.
LAMP
230 V~
Flashing light (FLM).
Non-flashing signal (jumper ON on FML).
Activated during opening and closing operations.
-F
+F
200 V = / 0.2 A
Motor electric brake.
The output is active for the duration of both the opening and closing operation.
U W V
M
3 ~
230 V~ / 6 A
Three-phase motor.
M2
Safety device / Commands
M3
Position signal
M4
Interlock
M4A
Back
M5
Motor / brake motor
M6
Thermal motor
M7
Absolute encoder
J4
Brake resistance
OPEN
Auxiliary panel card
SAFETY
Auxiliary safety card
CONTROL PANEL CONNECTORS
52E
EN