26
A
Set to the same Amp value that was set for Max A
Charge.
3
Float V
Value is communicated by BMS in a closed-loop
configuration. Ignore the displayed value.
Absorption V
Value is communicated by BMS in a closed-loop
configuration. Ignore the displayed value.
Equalization V
The function is disabled in a closed-loop configuration.
Ignore the displayed value.
Gen Exercise Cycle Day &
Cycle
Refer to Solar-Ark documentation.
Gen Force
Refer to Solar-Ark documentation.
1
Left column options are for Gen Charge AutoStart values (Reference Sol-Ark
documentation for more details on the generator AutoStart function.
2
Right Column options are for Grid Charge values.
3
If need be, this value is used to curtail the maximum current output of the charger.
The values and parameters used are for an operating temperature of 25 deg C.
6.3.3 Closed-Loop - Batt Setup > Discharge
Touch the DISCHARGE tab onscreen to start the programming sequence
(Figure
14).
• Touch the OK button to save all onscreen values - Ignore data displayed
in GREY boxes.
Batt Setup
Batt Charge Discharge Smart Load
Shutdown
Batt
Resistance
Batt Charge
Efficiency
Low Batt
Restart
Batt Empty V
BMS_Err_Stop
CANCEL
OK
48.0V
49.5V
52.8V
10%
8mOhms
98.0%
20%
80%
48.0V
Figure 14. Closed-Loop Battery Setup > Disharge (Two 130Ah AES Batteries with 12K-P