19
Max A Discharge
For a single inverter: set to the lesser of the inverter’s max
discharge capacity, or the quantity of attached batteries,
multiplied by the battery model’s specific max discharge rating.
For example, a 12k-P inverter would be set to the lessor of the
inverter’s max discharge rate of 185 A, or 260 A for two AES 42-
48-6650 batteries rated at 130 A max charge each.
1
For a three-phase system: set to the lessor of the max discharge
value for the master inverter, or the quantity of attached
batteries, multiplied by the battery model’s max charge rating,
divided by the number of inverters. For example, the master
12k-P would be set to the lessor of the inverter’s max charge
rate of 185 A, or 173 A for a battery bank of four AES 42-48-6650
batteries rated at 130A Max Charge each (520 A divided by
three inverters).
TEMPCO
Set to 0 mv/C/Cell.
2
Use Batt V Charged
Enable
Use Batt % Charged Disable
No Battery
Disable
BMS Lithium Batt
Disable (Displays 00 value)
3
Activate Battery
Enable
1
The recommended value for Max A Charge is 75% of the rated maximum charge current for the
battery.
2
Discover Lithium batteries do not require temperature compensation. Setting TEMPCP to
O mv/C/Cell will disable inverter-charger controlled temperature compensation.
3
Setting the BMS Lithium Batt parameter to Disable confirms open-loop operation. Setting the
parameter to Enable confirms closed-loop operation.
The values and parameters used are for an assumed operating temperature of 25 deg C.
6.1.2 Open-Loop - Batt Setup > Charge
Touch the CHARGE tab onscreen to start the programming sequence (Figure 10).
• Touch the OK button to save all onscreen values - Ignore data displayed
in GREY boxes.