6.1.3 Open-Loop - Batt Setup > Discharge
Touch the DISCHARGE tab onscreen to start the programming sequence (Figure
11).
• Touch the OK button to save all onscreen values - Ignore data displayed
in GREY boxes.
Batt Setup
Batt Charge Discharge Smart Load
Shutdown
Batt
Resistance
Batt Charge
Efficiency
Low Batt
Restart
Batt Empty V
BMS_Err_Stop
CANCEL
OK
48.0V
49.5V
52.8V
10%
8mOhms
98.0%
20%
80%
48.0V
Figure 11. Open-Loop Battery Setup > Discharge (Two 130Ah AES Batteries with 12K-P)
Batt Setup > Discharge
BMS_Err_Stop
Disable
Shutdown
48.0 V
1
Low Batt
49.5 V
1
Restart
52.8 V
1
Batt Empty V
48.0 V
Batt Resistance
Set to: Ten mOhm divided by the number of batteries,
plus the mOhm value of resistance for interconnection
and homerun cabling.
2
Batt Charge Efficiency
98.0 %
1
Discharge state-of-charge percentage values are unavailable in an open-loop
(voltage-based) configuration.
2
This value should include cable and connection resistance. The formula is provided
to assist with the calculation of a general value.
The values and parameters used are for an operating temperature of 25 deg C.
6.2 Setting the LYNK II Communication Protocol for Sol-Ark
After establishing the open-loop configuration, the LYNK II Communication
Protocol is set, followed by the Sol-Ark closed-loop configuration.
The Protocol Configuration Procedure
1. Download the current version of LYNK ACCESS software from the Discover
Battery website to obtain the most up-to-date suite of available protocol