18
NOTE
If necessary, configure Sol-Ark inverters to operate in parallel before setting the
parameters for battery operation.
6.1.1 Open-Loop - Batt Setup > Batt
Touch the BATT tab onscreen to start the programming sequence (Figure 9.).
• Touch the OK button to save all onscreen values - Ignore data displayed
in GREY boxes.
Batt Setup
Batt
Batt Capacity
Use Batt V Charged
Charge Discharge Smart Load
Use Batt % Charged
No Battery
BMS Lithium Batt
Activate Battery
Max A Charge
Max A Discharge
TEMPCO
CANCEL
OK
260 Ah
185 A
185A
-0mV/C/Cell
00
Figure 9. Open-Loop Battery Setup > Batt Menu (Two 130Ah AES Batteries with 12K-P)
Batt Setup > Batt
Batt Capacity
Set to the number of Discover Lithium batteries x Ah capacity
of each. For example, set to 260 Ah (2 x 130 Ah) for two AES
42-48-6650 batteries.
Max A Charge
For a single inverter: set to the lesser of the inverter’s max
charge capacity, or the quantity of attached batteries, multiplied
by the battery model’s specific max charge rating. For example,
a 12K-P inverter would be set to the lessor of the inverter’s max
charge rate of 185 A, or 260 A for two AES 42-48-6650 batteries
rated at 130 A max charge each.
1
For a three-phase system: set to the lessor of the max charge
value for the master inverter, or the quantity of attached
batteries, multiplied by the battery model’s max charge rating,
divided by the number of inverters. For example, the 12k-P
master would be set to the lessor of the inverter’s max charge
rate of 185A, or 173 A for four AES 42-48-6650 batteries rated at
130 A max charge each (520 A divided by three inverters).