11
©
Dinel, s.r.o. CLM–70
Heat insulation
50
high-temperature
extension
• The level meter must not be in
-
stalled in places exposed to direct
sunlight
and must be protected
from the weather influences. Even
so installation is in exposed places
to direct sunlight a
shielding cov-
er
is necessary to be fitted over
the level meter (see Fig. 7).
• The level meters for high operat
-
ing temperatures are equipped
with an extension. This is used to
thermally insulate the electronics
part of the meter from the high
operating temperature. The ex
-
tension must not be embedded in
the insulation more than 50 mm.
Fig. 7: A shielding cover protecting against direct sunlight
Fig. 6: Installation of the level meter in an insulated tank
COVERING THE LEVEL METER
APPLIES TO: All types
TANK WITH INSULATION
APPLIES TO: CLM-70NT-_
• The level meter is not recommended to be installed at or above the
filling
point. Measure
-
ment may be influenced by the inflow medium.
Fig. 8: Installation of the level meter out of the reach of filling flow
OUT OF REACH OF FILLING
APPLIES TO: All types