6 Assembly

6.1 General

The following connections need to be established on the heat
pump:

„

Flow and return flow of the heating system

„

Condensate outflow

„

Control line to the heat pump manager

„

Power supply

6.2 Connection on heating side

The heating system connections on the heat pump have a
1 1/4" external thread.
Route the connection hoses out of the device in a downwards di-
rection. Use a spanner to firmly grip the transitions when con-
necting the heat pump. After the heat pump has been installed,
the ductwork must be sealed so that the connection is gastight.
Before connecting the heating water system to the heat pump,
the heating system must be flushed to remove any impurities,
residue from sealants, etc., and to prevent any accumulation of
deposits in the liquifier. A contaminated liquifier may cause the
heat pump to completely break down. For systems in which the
heating water flow can be shut off via the radiator or thermostat
valves, an overflow valve must be installed in a heating bypass
downstream from the heat pump by the customer. This ensures
a minimum heating water flow rate through the heat pump and
helps to avoid faults.
Once the heating system has been installed, it must be filled, de-
aerated and pressure-tested (in the heat pump the air-relief cock
is located at or in the water pipes at the condenser).

Consideration must be given to the following when filling the sys-
tem:

„

Untreated filling water and make-up water must be of drink-
ing water quality
(colourless, clear, free from sediments)

„

Filling water and make-up water must be pre-filtered (pore
size max. 5µm).

Scale formation in hot water heating systems cannot be com-
pletely avoided, but in systems with flow temperatures below
60°C the problem can be disregarded.
With medium and high-temperature heat pumps, temperatures
above 60°C can be reached.
The following standard values should therefore be adhered to
concerning the filling water and make-up water (according to VDI
2035 Sheet 1):

Minimum heating water flow rate

The minimum heating water flow rate through the heat pump
must be assured in all operating states of the heating system.
This can be accomplished, for example, by installing either a dual
differential pressureless manifold or an overflow valve. The pro-
cedure for adjusting an overflow valve is described in the Chap-
ter Start-up. When the minimum flow rate is undershot drasti-
cally, the plate steel exchanger in the refrigerating cycle can
freeze, which can lead to total loss of the heat pump.

NOTE

The use of an overflow valve is only recommended for panel heating and
a max. heating water flow of 1.3 m³/h. System faults may result if this is
not observed.

Antifreeze

Manual drainage should be provided for heat pumps which are
exposed to frost. The antifreeze function of the heat pump man-
ager is active whenever the heat pump manager and the heat cir-
culating pump are ready for operation. If the heat pump is taken
out of service or in the event of a power failure, the system has to
be drained, and if required, blown out, at three locations (see il-
lustration). The heating circuit should be operated with a suitable
antifreeze if heat pump systems are implemented in buildings
where a power failure can not be detected (holiday home).

Total heat

output in [kW]

Total alkaline earths

in mol/m³ and/or

mmol/l

Total

hardness in °dH

up to 200

≤ 

2.0

≤ 

11.2

200 to 600

≤ 

1.5

≤ 

8.4

> 600

< 0.02

< 0.11

$LUUHOLHIFRFN

&RQGHQVHU

Содержание LA 14PMS

Страница 1: ...p for Outdoor Installation Pompe chaleur air eau pour installation ext rieure Montage und Gebrauchsanweisung Deutsch English Fran ais Instructions d installation et d utilisation Installation and Oper...

Страница 2: ......

Страница 3: ...2 Schaltkasten DE 3 3 3 W rmepumpenmanager DE 4 4 Transport DE 4 5 Aufstellung DE 4 5 1 Allgemein DE 4 5 2 Kondensatleitung DE 4 6 Montage DE 5 6 1 Allgemein DE 5 6 2 Heizungsseitiger Anschluss DE 5...

Страница 4: ...rschriften eingehalten siehe CE Konformit tserkl rung Beim elektrischen Anschluss und bei der Durchf hrung von Ser vicearbeiten an der W rmepumpe sind die entsprechenden VDE EN und IEC Normen einzuhal...

Страница 5: ...au gepumpt und ber den Verfl ssiger W rmeaus tauscher an das Heizwasser abgegeben Dabei wird die elektrische Energie eingesetzt um die W rme der Umwelt auf ein h heres Temperaturniveau anzuheben Da di...

Страница 6: ...Zur ckziehen oben ausgeh ngt Beim Einh ngen der Blechteile sollten diese mit leichtem Druck nach oben geschoben werden Beim Durchstecken der Tragrohre durch den Rahmen ist darauf zu achten dass keine...

Страница 7: ...und Erg nzungswasser muss vorfiltriert sein Po renweite max 5 m Eine Steinbildung in Warmwasserheizungsanlagen kann nicht vollst ndig vermieden werden ist aber bei Anlagen mit Vorlauf temperaturen kl...

Страница 8: ...ine ordnungsgem e Inbetriebnahme zu gew hrleisten sollte diese von einem vom Werk autorisierten Kundendienst durchgef hrt werden Unter bestimmten Bedingungen ist damit eine Verl ngerung der Gew hrleis...

Страница 9: ...die Anlage wie unten angegeben zu reinigen Die Reinigung darf nur wie im Folgenden vom Herstel ler beschrieben durchgef hrt werden 8 2 Reinigung Heizungsseite Sauerstoff kann im Heizwasserkreis insbes...

Страница 10: ...len ist in diesem Fall der Ansaug und Ausblasbereich von Eis und Schnee zu befreien 9 St rungen Fehlersuche Diese W rmepumpe ist ein Qualit tsprodukt und sollte st rungs frei arbeiten Tritt dennoch e...

Страница 11: ...3200 4 2 W rmeleistung Leistungszahl4 4 Bei minimalen Heizwasserdurchfluss EN 14511 bei A 7 W35 kW 8 0 2 5 kW 4 0 2 0 bei A2 W35 kW 10 2 3 1 kW 5 8 2 9 bei A7 W35 kW 13 3 3 6 kW 7 4 3 7 bei A7 W55 kW...

Страница 12: ...ne Teile und Ger te Anlagenm ngel die auf nicht vom Liefe rer bezogene Teile zur ckzuf hren sind fallen nicht unter den Garantieanspruch Sofern der Mangel nicht beseitigt werden kann oder die Nach bes...

Страница 13: ...3 3 2 Switch Box EN 3 3 3 Heat Pump Manager EN 4 4 Transport EN 4 5 Installation EN 4 5 1 General EN 4 5 2 Condensed Water Pipe EN 4 6 Assembly EN 5 6 1 General EN 5 6 2 Connection on heating side EN...

Страница 14: ...directives DIN VDE regulations see CE declaration of conformity The relevant VDE EN and IEC standards must be adhered to when connecting the heat pump to the power supply or carrying out maintenance w...

Страница 15: ...rically driven compressors It is then transferred to the heating water using the liquifier heat exchanger Electrical energy is used to raise the temperature of the heat in the environment to a higher...

Страница 16: ...f the two screws at the base and then withdrawing the panels by unhooking them from above Rehang the panels by gently pushing them in an upwards direction Be careful not to damage any components when...

Страница 17: ...5 m Scale formation in hot water heating systems cannot be com pletely avoided but in systems with flow temperatures below 60 C the problem can be disregarded With medium and high temperature heat pum...

Страница 18: ...ar The ventilator must turn in the direction indicated by the ar row The settings of the heat pump manager must be adapted to the heating system in accordance with the controller s oper ating instruct...

Страница 19: ...using appropriate neutralising agents to prevent any damage from being caused by cleaning agent residue remaining in the system Acids must be used with care and the regulations of the employ ers liabi...

Страница 20: ...00 4 2 Heat output COP4 4 With minimum heating water flow EN 14511 at A7 W35 kW 8 0 2 5 kW 4 0 2 0 at A2 W35 kW 10 2 3 1 kW 5 8 2 9 at A7 W35 kW 13 3 3 6 kW 7 4 3 7 at A7 W55 kW 11 7 2 8 kW 6 3 2 6 at...

Страница 21: ...tier lectrique FR 3 3 3 Gestionnaire de pompe chaleur FR 4 4 Transport FR 4 5 Installation FR 4 5 1 G n ralit s FR 4 5 2 Ecoulement des condensats FR 4 6 Montage FR 5 6 1 G n ralit s FR 5 6 2 Raccorde...

Страница 22: ...n de conformit CE Les normes VDE EN et CEI correspondantes sont respecter lors du branchement lectrique et de travaux de maintenance sur la pompe chaleur D autre part les prescriptions de branche ment...

Страница 23: ...n puis d livr e via le condenseur changeur de chaleur l eau de chauffage Il est fait appel l nergie lectrique pour faire passer la chaleur de l environnement un niveau de temp rature plus lev Comme l...

Страница 24: ...s Pour cela des serrer deux vis du socle pour d crocher les plaques par le haut en les tirant Pousser l g rement les plaques m talliques vers le haut pour les accrocher Lorsque vous enfoncez les tubes...

Страница 25: ...ible d emp cher totalement la formation de cal caire dans les installations de chauffage eau chaude Sa quan tit est cependant n gligeable pour les installations ayant des temp ratures aller inf rieure...

Страница 26: ...par le construc teur Le respect de cette clause permet une prorogation de la ga rantie sous certaines conditions voir Garantie 7 2 Pr paratifs Avant la mise en service il est imp ratif de proc der aux...

Страница 27: ...ille par ex dans le condenseur de la pompe chaleur Nous recommandons donc d quiper chaque installation de chauffage ouverte la diffusion d un dispositif lectrophysique contre la corrosion par ex insta...

Страница 28: ...Toute personne travaillant sur le circuit r frig rant doit tre en mesure de pr senter une autorisation certifiant sa capacit ef fectuer des travaux comprenant des manipulations de fluides fri gorig ne...

Страница 29: ...0 4 2 Capacit thermique COP 4 4 En cas de d bit minimum d eau de chauffage EN 14511 pour A 7 W35 kW 8 0 2 5 kW 4 0 2 0 pour A2 W35 kW 10 2 3 1 kW 5 8 2 9 pour A7 W35 kW 13 3 3 6 kW 7 4 3 7 pour A7 W55...

Страница 30: ...FR 10 Fran ais 11...

Страница 31: ...mas hydrauliques A VIII 4 1 Monoenergetische Anlage mit einem Heizkreis und Warmwasserbereitung Mono energy system with one heating circuits and domestic hot water preparation Installation mono nerg...

Страница 32: ...EODXI QQHQ PP HDWLQJ ZDWHU UHWXUQ IORZ HDW SXPS LQOHW H WHUQDO WKUHDG HDWLQJ ZDWHU IORZ HDW SXPS RXWOHW H WHUQDO WKUHDG RQGHQVDWH RXWIORZ LQVLGH PP 5HWRXU HDX GH FKDXIIDJH QWUpH GDQV OD 3 LOHWDJH H Wp...

Страница 33: ...LQ 3D 3HUWH GH SUHVVLRQ HQ 3D XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G DLU HQ XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G DLU HQ HLVWXQJV...

Страница 34: ...A IV Anhang Appendix Annexes 3 3 Stromlaufpl ne Circuit Diagrams Sch mas lectriques 3 1 Steuerung Control Commande...

Страница 35: ...www dimplex de A V Anhang Appendix Annexes 3 2 3 2 Last Load Charge...

Страница 36: ...A VI Anhang Appendix Annexes 3 3 3 3 Anschlussplan Circuit Diagram Sch ma lectrique...

Страница 37: ...or Ventilateur M3 Verdichter 2 Compressor 2 Compresseur 2 N1 W rmepumpenmanager Heat pump manager Gestionnaire de pompe chaleur N7 Sanftanlasser M1 Soft starter M1 D marrage progressif M1 N8 Sanftanla...

Страница 38: ...ng Diagram Sch mas hydrauliques 4 1 Monoenergetische Anlage mit einem Heizkreis und Warmwasserbereitung Mono energy system with one heating circuits and domestic hot water preparation Installation mon...

Страница 39: ...es 4 2 4 2 Bivalente Anlage mit zwei Heizkreisen und Warmwasserbereitung Bivalent system with two heating circuits and domestic hot water preparation Installation bivalente avec deux circuits de chauf...

Страница 40: ...water cylinder R servoir d eau chaude sanitaire E9 Flanschheizung Warmwasser Flange heater hot water Cartouche chauffante ECS E10 1 Tauchheizk rper Immersion heater R sistance immerg e E10 2 l Gaskess...

Страница 41: ...ie 2004 108 EG Druckger terichtlinie 97 23 EG EC Directives Low voltage directive 2006 95 EC EMC directive 2004 108 EC Pressure equipment directive 97 23 EC Directives CEE Directive Basse Tension 2006...

Страница 42: ...A XII Anhang Appendix Annexes 5...

Страница 43: ...www dimplex de A XIII Anhang Appendix Annexes 5...

Страница 44: ...schland GmbH Gesch ftsbereich Dimplex Am Goldenen Feld 18 D 95326 Kulmbach Irrt mer und nderungen vorbehalten Subject to alterations and errors Sous r serve d erreurs et modifications 49 0 9221 709 56...

Отзывы: