11
11 Device Information
Device information for air-to-water heat pumps (heating only)
1
Type and order code
LA 11MSR
2
Design
2.1
Model
Reversible
2.2
Degree of protection according to EN 60 529
IP24
2.3
Installation location
Outdoors
3
Performance data
3.1
Operating temperature limits:
Heating water flow/return flow
1
°C / °C
1. See operating limits diagram
Up to 55 / above 18
Cooling, flow
°C
+7 to +20
Air (heating)
°C
-25 to +35
Air (cooling)
°C
+15 to +40
3.2
Temperature spread
of heating water (flow/return flow) at A7 / W35
9.6
5.0
3.3
Heat output / COP
at A-7 / W35
2
kW
/
---
2. This data indicates the size and capacity of the system according to EN 255 and EN 14511. For an analysis of the economic and energy efficiency of the system, other parame-
ters,such as, in particular, the defrosting capacity, the bivalence point and regulation, should also be taken into consideration. The specified values, e.g. A2 / W35, have the fol-
lowingmeaning: 2 °C external air temperature and 35 °C heating water flow temperature.
7.5 / 2.8
7.0 / 2.7
at A-7 / W45
kW / ---
6.8 / 2.3
at A2 / W35
kW / ---
8.9 / 3.4
8.8 / 3.3
at A2 / W50
kW / ---
8.8 / 2.5
at A7 / W35
kW / ---
11.1 / 4.2
11.1 / 4.0
kW / ---
9.4 / 3.5
at A10 / W35
kW / ---
12.1 / 4.6
12.0 / 4.4
3.4
Temperature spread of cooling water at A35 / W7
6.5
5.0
3.5
Cooling capacity / COP
at A27 / W7
kW / ---
8.8 / 2.8
8.8 / 2.8
at A27 / W18
kW / ---
10.9 / 3.3
10.8 / 3.2
at A35 / W7
kW / ---
7.6 / 2.1
7.5 / 2.1
at A35 / W18
kW / ---
9.5 / 2.5
9.5 / 2.5
3.6
Sound power level
dB(A)
63
3.7
Sound pressure level at a distance of 10m
(discharge end)
dB(A)
33
3.8
Heating water flow with an internal pressure differential of m³/h / Pa
1.0 / 3000
1.9 / 10900
3.9
Cooling water flow with an internal pressure differential of m³/h / Pa
1.3 / 5900
3.10 Air flow rate with an external static pressure differential of m³/h / Pa
2500
3.11 Refrigerant; total filling weight
type / kg
R404A / 3.6
3.12 Lubricant; total filling weight
type / litres
Polyolester (POE) / 1.5
4
Dimensions, connections and weight
4.1
Device dimensions
H x W x L cm
136 x 136 x 85
4.2
Device connections to heating system
Inch
1'' external thread
4.3
Weight of the transportable unit(s) incl. packing
kg
224
5
Electrical Connection
5.1
Nominal voltage; fuse protection
V / A
230 / 25
5.2
Nominal power consumption
A2 W35
kW
2.61
2.67
5.3
Starting current with soft starter
A
38
5.4
Nominal current
A2 W35 / cos
ϕ
A / ---
14.2 / 0.8
14.5 / 0.8
5.5
max. power consumption of compressor protection
(per compressor)
W
70
6
Complies with the European safety regulations
3
3. See CE declaration of conformity
7
Additional model features
7.1
Defrosting
Automatic
Type of defrosting
Reverse cycle
Defrosting tray included
Yes (heated)
7.2
Heating water in device protected against freezing
Yes
4
4. The heat circulating pump and the heat pump manager must always be ready for operation.
7.3
Performance levels
1
7.4
Controller internal/external
External
Содержание LA 11MSR