HPL 9S-TU(R)W - HPL 18S-TU(R)W 

9 Cleaning / maintenance

9.1 Maintenance

To protect the paintwork, avoid leaning anything against the de-
vice or putting objects on the device. External heat pump parts
can be wiped with a damp cloth and commercially available do-
mestic cleaner.

NOTE

Never use cleaning agents containing sand, soda, acid or chloride, as
these can damage the surfaces.

To prevent faults due to sediment in the heat exchanger of the
heat pump, ensure that the heat exchanger in the heating system
cannot be contaminated. Should operating malfunctions due to
contamination still occur, however, the system should be cleaned
as described below.

9.2 Cleaning the heating system

The ingress of oxygen into the heating water circuit may result in
the formation of oxidation products (rust), particularly if steel
components are used. These enter the heating system via the
valves, the circulating pumps and/or plastic pipes. A diffusion-re-
sistant installation is therefore essential, especially with regard to
the complete piping.

NOTE

We recommend the installation of a suitable corrosion protection system
to prevent the formation of deposits (e.g. rust) in the condenser of the
heat pump. We recommend equipping diffusion-open heating systems
with an electrophysical anti-corrosion system (e.g. ELYSATOR system).

Residue from lubricants and sealants may also contaminate the
heating water.
In the event of severe contamination leading to a reduction in the
performance of the liquefier in the heat pump, the system must
be cleaned by a heating technician.
Based on current information, we recommend using a 5% phos-
phoric acid solution for cleaning purposes. However, if cleaning
needs to be performed more frequently, a 5% formic acid solu-
tion should be used.
In both cases, the cleaning fluid should be at room temperature.
We recommend flushing the heat exchanger in the direction op-
posite to the normal flow direction.
To prevent acidic cleaning agents from entering the heating sys-
tem circuit, we recommend connecting the flushing device di-
rectly to the flow and return of the liquefier of the heat pump.
It is then important that the system be thoroughly flushed using
appropriate neutralising agents to prevent any damage from
being caused by cleaning agent residue remaining in the system.
Acids must be used with care and the regulations of the employ-
ers liability insurance associations must be adhered to.
The instructions of the cleaning agent manufacturer must always
be observed.

9.3 Cleaning the air system

The evaporator, fan and condensate drain should be cleaned of
contamination (leaves, twigs, etc.) before each new heating pe-
riod. Do this by opening the heat pump as described in
Chapter 7.1.

ATTENTION!

Before opening the device, ensure that all circuits are disconnected from
the power supply!

To prevent the evaporator and the condensate tray from being
damaged, do not use hard or sharp objects when cleaning.
Under extreme weather conditions (e.g. snow drifts), ice may
form on the air intake and air outlet grids. If this happens, the ice
must be removed from the vicinity of the air intake and air outlet
grids to ensure that the minimum air flow is maintained.
To ensure proper drainage from the condensate tray, it must be
regularly inspected and cleaned, if necessary.

10 Faults / troubleshooting

This heat pump is a quality product and is designed for trouble-
free operation. Should a fault occur, however, it will be indicated
on the heat pump manager display. In this case, consult the
"Faults and troubleshooting" page in the operating instructions of
the heat pump manager. If you cannot correct the fault yourself,
please contact your after-sales service technician.

ATTENTION!

Work on the heat pump must only be performed by authorised and
qualified after-sales service technicians! 

11 Decommissioning / 

disposal

Before removing the heat pump, disconnect it from the power
source and close all valves. The heat pump must be dismantled
by trained personnel. Observe all environmental requirements
regarding the recovery, recycling and disposal of materials and
components in accordance with all applicable standards. Partic-
ular attention should be paid to the proper disposal of refrigerants
and refrigerant oils.

Содержание HPL 12S-TURW

Страница 1: ...o Water Heat Pump for Outdoor Installation with hydro tower Pompe chaleur air eau pour installation ext rieure avec tour hydraulique combin e Montage und Gebrauchsanweisung Deutsch English Fran ais In...

Страница 2: ......

Страница 3: ...Aufstellung DE 6 6 1 Allgemein DE 6 6 2 Kondensatleitung DE 6 7 Montage DE 6 7 1 Allgemein DE 6 7 2 Heizungsseitiger Anschluss DE 7 7 3 Elektrischer Anschluss DE 8 8 Inbetriebnahme DE 8 8 1 Allgemein...

Страница 4: ...rbeiten an der W rmepumpe d rfen nur vom autorisierten und sachkundigen Kundendienst durchgef hrt werden 1 2 Bestimmungsgem er Gebrauch Dieses Ger t ist nur f r den vom Hersteller vorgesehenen Ver wen...

Страница 5: ...es Verdampfers zu gew hrleisten Die W rmepumpe ist nicht f r den erh hten W rmebedarf w h rend der Bauaustrocknung ausgelegt deshalb muss der zus tz liche W rmebedarf mit speziellen bauseitigen Ger te...

Страница 6: ...nem un gemischten Heizkreis ben tigt werden Ein doppelt differenzdruckloser Verteiler in Kombination mit einem Pufferspeicher er gibt eine energetisch optimale hydraulische Einbindung des W rmeerzeuge...

Страница 7: ...tlichen Fassadierungsteile abzunehmen Jedes Verkleidungsblech ist mit zwei Schrauben gesichert Nach dem L sen der Schrauben m ssen die Verkleidungsbleche gekippt und aus dem Sockelblech gezogen werden...

Страница 8: ...orschriften sind zu beachten ACHTUNG Bei wandnaher Aufstellung sind bauphysikalische Beeinflussungen zu beachten Im Ausblasfeld des Ventilators sollten keine Fenster bzw T ren vorhanden sein ACHTUNG B...

Страница 9: ...folgende Richtwerte eingehalten werden HINWEIS Die Hinweise Einstellungen in der Anweisung des W rmepumpenmanagers sind unbedingt zu beachten und dementsprechend vorzunehmen eine Nichtber cksichtigun...

Страница 10: ...ikationsunterbrechung mit dem W rmepumpenmana ger auch keine Regelung des 2 W rmeerzeuger m glich HINWEIS Der in der W rmepumpe eingebaute R cklauff hler R2 ist bei laufendem Verdichter aktiv und darf...

Страница 11: ...klauf des Verfl ssigers der W rme pumpe anzuschlie en Danach muss mit geeigneten neutralisierenden Mitteln gr ndlich nachgesp lt werden um Besch digungen durch eventuell im System verbliebene Reinigun...

Страница 12: ...L mm 1650 x 910 x 750 1650 x 910 x 750 1650 x 910 x 750 5 2 Ger teanschl sse f r Heizung Zoll G 1 1 4 AG G 1 1 4 AG G 1 1 4 AG 5 3 Gewicht der Transporteinheit en incl Verpackung kg 225 265 295 5 4 K...

Страница 13: ...rkaufsbezeichnung HPL 9S TURW HPL 12S TURW HPL 18S TURW 2 Bauform W rmequelle Luft Luft Luft 2 1 Ausf hrung Reversibel mit Hydro Tower Reversibel mit Hydro Tower Reversibel mit Hydro Tower 2 2 Regler...

Страница 14: ...8 1 3 9 bei A7 W55 kW 8 0 3 0 10 0 3 1 7 7 3 2 bei A10 W35 kW 8 9 5 3 12 0 5 1 8 8 5 4 10 K hlleistung Leistungszahl 4 12 10 1 K hlleistung Leistungszahl EN 14511 EN 14511 EN 14511 Leistungsstufe 1 2...

Страница 15: ...ht vom Lieferer bezogene Teile und Ger te Anlagen m ngel die auf nicht vom Lieferer bezogene Teile zur ckzuf h ren sind fallen nicht unter den Garantieanspruch Bei endg ltig fehlgeschlagener Nachbesse...

Страница 16: ...DE 14 452168 66 05 FD 9512 www dimplex de Deutsch HPL 9S TU R W HPL 18S TU R W...

Страница 17: ...5 6 Installation EN 6 6 1 General EN 6 6 2 Condensate pipe EN 6 7 Assembly EN 6 7 1 General EN 6 7 2 Connection on heating side EN 7 7 3 Electrical connection EN 8 8 Commissioning EN 8 8 1 General EN...

Страница 18: ...e device ensure that all circuits are disconnected from the power supply ATTENTION Work on the heat pump must only be performed by authorised and qualified after sales service technicians 1 2 Intended...

Страница 19: ...consump tion required when a building is being dried out For this reason the additional heat consumption should be met using special de vices provided by the customer For drying out a building in au t...

Страница 20: ...h an unmixed heating circuit A dual differen tial pressureless manifold with a buffer tank allows an energy op timised hydraulic integration of the heat generator and the heat distribution The integra...

Страница 21: ...rame it is necessary to remove the two side panel assemblies Each covering panel is secured with two screws After the screws are loosened the pan els must be tilted and pulled out of the kickplate The...

Страница 22: ...ION Observe country specific building regulations ATTENTION The physical impacts must be observed for installation close to walls No windows or doors should be present in the area surrounding the air...

Страница 23: ...TE The notes settings in the instructions of the heat pump manager must always be observed and carried out accordingly not doing so will lead to malfunctions Minimum heating water flow rate The minimu...

Страница 24: ...If a demand sensor is not connected the second heat generator can not be controlled with the heat pump manager in the event of an interruption in communication either NOTE The return sensor R2 instal...

Страница 25: ...cuit we recommend connecting the flushing device di rectly to the flow and return of the liquefier of the heat pump It is then important that the system be thoroughly flushed using appropriate neutral...

Страница 26: ...al thread G 1 1 4 external thread G 1 1 4 external thread 5 3 Weight of the transportable unit s incl packaging kg 225 265 295 5 4 Refrigerant total filling weight type kg R410A 3 9 R410A 4 78 R410A 5...

Страница 27: ...source Air Air Air 2 1 Model Reversible with hydro tower Reversible with hydro tower Reversible with hydro tower 2 2 Controller Integrated hydro tower Integrated hydro tower Integrated hydro tower 2...

Страница 28: ...9 5 3 12 0 5 1 8 8 5 4 10 Cooling capacity COP 4 12 10 1 Cooling capacity COP EN 14511 EN 14511 EN 14511 Performance level 1 2 1 2 1 2 at A27 W18 kW 7 9 4 4 8 6 3 7 8 2 4 5 15 4 3 7 at A27 W9 kW 12 7...

Страница 29: ...port FR 5 6 Installation FR 6 6 1 G n ralit s FR 6 6 2 Conduite d coulement des condensats FR 6 7 Montage FR 6 7 1 G n ralit s FR 6 7 2 Raccordement c t chauffage FR 7 7 3 Branchements lectriques FR 8...

Страница 30: ...ectriques sont bien hors tension ATTENTION Les travaux sur la pompe chaleur doivent tre effectu s uniquement par un SAV qualifi et agr 1 2 Utilisation conforme Cet appareil ne doit tre employ que pour...

Страница 31: ...fonctionnement continu pour garantir un d givrage optimal de l vaporateur La pompe chaleur n tant pas con ue pour le besoin en cha leur lev requis pour le s chage d une construction celui ci devra tre...

Страница 32: ...chaleur jusqu sa distribution Un distributeur double sans pression diff rentielle combin un ballon tampon permet une int gration hydraulique optimale en terme d nergie du g n rateur de chaleur et de...

Страница 33: ...trous de transport dans le ch ssis il est n ces saire de retirer les deux panneaux d habillage lat raux Chaque panneau d habillage est fix l aide de deux vis Apr s avoir des serr les vis incliner les...

Страница 34: ...s d un mur tenir compte des influences physiques sur la construction Aucune porte ou fen tre ne doit se trouver dans le champ d vacuation du ventilateur ATTENTION En cas d installation pr s d un mur l...

Страница 35: ...nelle doivent tre respect es selon VDI2035 feuillet1 1 dH 1 7857 f REMARQUE Il est imp ratif de suivre les remarques et consignes et d effectuer en cons quence les r glages mentionn s dans les instruc...

Страница 36: ...Sans raccordement de la sonde de demande la r gulation du deuxi me g n rateur de chaleur devient impossible en cas de coupure de la communication avec le gestionnaire de pompe chaleur REMARQUE La sond...

Страница 37: ...ndons de raccorder l appareil de nettoyage directement sur le d part et le retour du condenseur de la pompe chaleur Il faut ensuite soigneusement rincer la tuyauterie l aide de pro duits neutralisants...

Страница 38: ...en mm 1650x910x750 1650x910x750 1650x910x750 5 2 Raccordements de l appareil pour le chauffage pouces Filet ext 1 1 4 Filet ext 1 1 4 Filet ext 1 1 4 5 3 Poids de des unit s de transport emballage com...

Страница 39: ...n du coefficient de performance en charge r duite avec la s lection de l option Mode chauffage consommation nerg tique optimis e d givrage naturel 1 D signation technique et r f rence de commande HPL...

Страница 40: ...0 11 pour A7 W35 kW 8 4 4 9 11 3 4 8 8 4 5 0 pour A7 W45 kW 8 2 3 8 10 8 3 9 8 1 3 9 pour A7 W55 kW 8 0 3 0 10 0 3 1 7 7 3 2 pour A10 W35 kW 8 9 5 3 12 0 5 1 8 8 5 4 10 Puissance de rafra chissement c...

Страница 41: ...agrams Sch mas d integration hydraulique A X 3 1 Monoenergetische W rmepumpenheizungsanlage mit einem Heizkreis Puffer und Warmwasserspeicher Mono energy heat pump heating system with one heating circ...

Страница 42: ...PLQDQWV HQ FDV G LQVWDOODWLRQ VXU HPSODFHPHQW GpJDJp HL ZDVVHUYRUODXI XVJDQJ DXV lUPHSXPSH X HQJHZLQGH HL ZDVVHUU FNODXI LQJDQJ LQ lUPHSXPSH X HQJHZLQGH XUFKI KUXQJVEHUHLFK OHNWUROHLWXQJHQ XUFKI KUXQJ...

Страница 43: ...SRZHU LQSXW WR SXPS RQVRPPDWLRQ GH SXLVVDQFH LQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH...

Страница 44: ...RQVXPSWLRQ LQ N LQFO SRZHU LQSXW WR SXPS RQVRPPDWLRQ GH SXLVVDQFH HQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D XIWHLQWULWWVWHPSHUDWXU LQ...

Страница 45: ...RQ GH SXLVVDQFH LQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G DLU...

Страница 46: ...FRQVXPSWLRQ LQ N LQFO SRZHU LQSXW WR SXPS RQVRPPDWLRQ GH SXLVVDQFH HQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D XIWHLQWULWWVWHPSHUDWXU LQ...

Страница 47: ...XPSHQOHLVWXQJVDQWHLO 3RZHU FRQVXPSWLRQ LQ N LQFO SRZHU LQSXW WR SXPS RQVRPPDWLRQ GH SXLVVDQFH LQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3...

Страница 48: ...SXLVVDQFH HQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G DLU HQ L...

Страница 49: ...H LQOHW WHPSHUDWXUH 7HPSpUDWXUH G HQWUpH GH OD VRXUFH GH FKDOHXU t t t t s D d 9HUGLFKWHUEHWULHE FRPSUHVVRU PRGH RQFWLRQHPHQW j FRPSUHVVHXU 9HUGLFKWHUEHWULHE FRPSUHVVRU PRGH RQFWLRQHPHQW j FRPSUHVVHXU...

Страница 50: ...WXUH 7HPSpUDWXUH G HDX GH UDIUDvFKLVVHPHQW lUPHVHQNHQHLQWULWWVWHPSHUDWXU HDW VLQN LQOHW WHPSHUDWXUH 7HPSpUDWXUH G HQWUpH GH GLVVLSDWLRQ WKHUPLTXH 9HUGLFKWHUEHWULHE FRPSUHVVRU PRGH RQFWLRQHPHQW j FRPSU...

Страница 51: ...ue 3 1 Monoenergetische W rmepumpenheizungsanlage mit einem Heizkreis Puffer und Warmwasserspeicher Mono energy heat pump heating system with one heating circuit buffer tank and hot water cylinder Ins...

Страница 52: ...rgetische W rmepumpenheizungsanlage mit einem Heizkreis Puffer und Warmwasserspeicher Electical circuit diagram for a mono energy system with one heating circuits buffer tank and hot water cylinder Sc...

Страница 53: ...ise Puffer und Warmwasserspeicher Mono energy heat pump heating system with three heating circuits buffer tank and hot water cylinder Installation de chauffage par pompe chaleur mono nerg tique avec t...

Страница 54: ...etische W rmepumpenheizungsanlage mit drei Heizkreise Puffer und Warmwasserspeicher Electical circuit diagram for a mono energy system with three heating circuits buffer tank and hot water cylinder Sc...

Страница 55: ...ager Gestionnaire de pompe chaleur E10 1 Tauchheizk rper Immersion heater R sistance immerg e M13 Heizungsumw lzpumpe Hauptkreis Heat circulating pump for main circuit Circulateur de chauffage circuit...

Страница 56: ...pumps D signation Pompes chaleur Typ en HPL 9S TUW Type s HPL 12S TUW Type s HPL 18S TUW HPL 9S TURW HPL 12S TURW HPL 18S TURW EG Richtlinien Niederspannungsrichtlinie 2006 95 EG EMV Richtlinie 2004...

Страница 57: ...www dimplex de 452168 66 05 FD 9512 A XVII Anhang Appendix Annexes HPL 9S TU R W HPL 18S TU R W...

Страница 58: ...A XVIII 452168 66 05 FD 9512 www dimplex de Anhang Appendix Annexes HPL 9S TU R W HPL 18S TU R W...

Страница 59: ...www dimplex de 452168 66 05 FD 9512 A XIX Anhang Appendix Annexes HPL 9S TU R W HPL 18S TU R W...

Страница 60: ...schland GmbH Gesch ftsbereich Dimplex Am Goldenen Feld 18 D 95326 Kulmbach Irrt mer und nderungen vorbehalten Subject to alterations and errors Sous r serve d erreurs et modifications 49 0 9221 709 56...

Отзывы: