9.4. Problem: "Pos - Err:3".
Possible causes:
The resolution of the connected measuring system is not in accord with the input resolution. The
measuring system is faulty. The actual value is outside the range which was entered in the menu path
setting for linear systems. See Chapter "7.4.2.2. Measuring offset with a linear moved system" on page
55. If an incremental measuring system is set, then this report is an alternative for the message
"Clear..."
.
Solution:
Check the input of the measuring system setting and the cable length setting.
Consult the instruction manual of your measuring system.
Consult Chapter
"Problem: Clear..."
.
If the error is eliminated, the error-message can be deleted by pressing
9.5. Problem: "Pos - Err:5".
Possible causes:
The measuring system control is activated. The CamCon has registered a large unacceptable actual
value jump. The measuring system is possibly faulty.
Solution:
Check the input of the measuring system setting and of the setting of the cable length or increase the
permitted actual value jump. Consult Chapter "7.4.1.3. Controlling the measuring system" on page 46.
Consult the instruction manual of your measuring system.
If the error is eliminated, the error-message can be deleted by pressing
9.6. Problem: An "Pos-Error:" occurs during operation.
The monitor displays "Pos-Err:1", "Pos-Err:2", "Pos-Err:3" or "Pos-Err:5".
Possible causes:
The connection cable of the measuring system or the measuring system itself is defective. A cable
without screening or without dual strand was used. The laying of a connection cable in the vicinity of a
strong electromagnetic source of interference (e.g. high voltage cable, motor cable) can lead to an pos
error.
Solution:
Check the wiring to the measuring system. Replace the measuring system.
Take measures for screening.
Lay the connection lead in another location.
Consult the instruction manual of your measuring system.
If the error is eliminated, the error-message can be deleted by pressing
9.7. Problem: "RAM-Full" = RAM memoryis full.
Possible causes:
The resolution of the measuring system is too large.
The number of outputs is too high.
The number of Speed Compensated outputs is too high.
Solution:
Check the input of the measuring system setting.
Reduce the measuring system resolution.
Reduce the number of Speed Compensated outputs.
Please contact your customer service representative if you require a RAM memory extension.