background image

Digital Monitoring Products 

 

 

 

 

 

XR150FC/XR550FC Series Installation Guide

10

Standby Battery Selection

After performing the calculations in Power Requirements, complete the following steps to select standby batteries:

Note: 

If the Power Requirements calculation is greater than any Max. Ah Available shown on a table, add power 

supplies to reduce the required amp hours. See the 710 Bus Splitter/Repeater Installation Guide (LT‑0310) for more 

information.

1.  Select the desired standby hours required from the following table: 24, 60, or 72 hours. 

2.  Select the desired battery size, then select a Max. Ah Available that slightly exceeds the number of total required 

Ah calculated in Power Requirements.

3.  Install the number of batteries shown in the corresponding No. of Batteries column.

Example: If total required amp hours equals 22 Ah for 24 hours of standby time and you want to use 5.0 Ah batteries, 

install six Model 368 (12 VDC, 5.0 Ah) batteries.

For listed installations, batteries can be installed in a DMP Model 341, 349, 350 or 352S enclosure and all wiring shall run 

through conduit. The enclosure shall be installed to the left of the XR150FC/XR550FC Series panel enclosure to ensure 

Battery and AC wire separation. For a list of compatible batteries, refer to "Batteries and Battery Accessories".

24 hours standby power, 48 hours recharge time

5.0 Ah Batteries

7 Ah Batteries

7.7 Ah Batteries

9 Ah Batteries

18 Ah Batteries

Max. Ah 

Available

No. of 

Batteries

Max. Ah 

Available

No. of 

Batteries

Max. Ah 

Available

No. of 

Batteries

Max. Ah 

Available

No. of 

Batteries

Max. Ah 

Available

No. of 

Batteries

8

2

6

1

6

1

8

1

16

1

12

3

12

2

13

2

16

2

32

2

16

4

18

3

20

3

24

3

48

3

20

5

24

4

27

4

32

4

24

6

31

5

34

5

40

5

28

7

37

6

41

6

32

8

43

7

36

9

40

10

60 hours standby power, 48 hours recharge time

7 Ah Batteries

7.7 Ah Batteries

9 Ah Batteries

18 Ah Batteries

Max. Ah 

Available

No. of 

Batteries

Max. Ah 

Available

No. of 

Batteries

Max. Ah 

Available

No. of 

Batteries

Max. Ah 

Available

No. of 

Batteries

13

2

14

2

17

2

17

1

20

3

22

3

26

3

34

2

27

4

29

4

34

4

52

3

33

5

37

5

43

5

69

4

40

6

44

6

52

6

47

7

52

7

61

7

54

8

59

8

69

8

60

9

67

9

67

10

72 hours standby power, 72 hours recharge time

9 Ah Batteries

18 Ah Batteries

Max. Ah 

Available

No. of 

Batteries

Max. Ah 

Available

No. of 

Batteries

16

2

16

1

25

3

33

2

33

4

50

3

42

5

67

4

50

6

59

7

67

8

Table 1: Standby Battery Specifications

Содержание XR150DFC-R

Страница 1: ...XR150FC XR550FC Series DIGITAL MONITORING PRODUCTS INC 2020 INSTALLATION GUIDE...

Страница 2: ......

Страница 3: ...e installer is encouraged to try to correct the interference by one or more of the following measures Reorient the receiving antenna Relocate the computer with respect to the receiver Move the compute...

Страница 4: ...d Center LCD Keypad 5 Mounting Additional Keypads Zone Expanders and Modules 5 Wire the panel 6 Wiring Specifications 6 Wire the Transformer 6 Wire the Batteries 7 Power Requirements 8 Standby Battery...

Страница 5: ...Ordering Information 17 Accessories 17 FCC Information 21 Part 15 21 Part 68 21...

Страница 6: ...ta bus supports up to fifteen supervised device addresses with each address supporting up to four programmable expansion zones Up to 500 zones are available using the on board LX Bus connections along...

Страница 7: ...y zones 1 8 and two 3 3k Ohm EOL powered zones with reset 9 10 To select either 1k or 2 2k for zones 1 to 8 program the EOL value in REMOTE OPTIONS Keypad Bus You can connect the following supervised...

Страница 8: ...TERMINALS BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS Earth Ground Zone Expander Model 715 7 mA 12 VDC Models 715 8 715 16 20 mA 12 VDC Zone Expander up to 8 zones Model 712 8 19 mA 12 VDC Zo...

Страница 9: ...e the panel PCB when installing the enclosure The enclosure dimensions are 13 44 H X 17 1 W X 4 8 D Note When using the XR150FC XR550FC Series panel for listed applications use the Model 350 349 341 o...

Страница 10: ...e mounting the base connect the keypad wire harness leads to the panel and to any applicable devices Then attach the harness to the pin connector to the PCB mount the base and install the keypad cover...

Страница 11: ...s a maximum of 40 LX Bus devices To increase the wire length or to add devices install an additional power supply that is listed for Fire Protective Signaling power limited and regulated 12 VDC nomina...

Страница 12: ...ring up the XR150FC XR550FC Series panel without AC power briefly short the battery start pads to pull in the battery cutoff relay Once the relay has been pulled in the battery voltage holds it in tha...

Страница 13: ...715 Zone Expansion Module Active Zones EOL Installed 2 Wire Smokes Qty Qty Qty x x x 7 mA 4 mA 0 1 mA mA mA mA Qty Qty Qty x x x 7 mA 30 mA1 0 1 mA mA mA mA 715 8 715 16 Zone Expansion Modules Active...

Страница 14: ...l Panel Relay Outputs 1 2 ON Switch Grounds 3 6 ON Active Zones 1 8 Active Zones 9 10 2 Wire Smoke Detectors Panel Bell Output max 1500 mA Aux power devices on Terminals 7 and 11 except keypads and LX...

Страница 15: ...he enclosure shall be installed to the left of the XR150FC XR550FC Series panel enclosure to ensure Battery and AC wire separation For a list of compatible batteries refer to Batteries and Battery Acc...

Страница 16: ...Ethernet LEDs The two LEDs located on the top edge of the connector indicate network connection The right Link LED green lights to indicate a valid receive connection from the host network The Activi...

Страница 17: ...trouble with the phone line after rewiring the phone block you may need to replace the RJ cord If the dial tone is still not present after replacing the phone cord replace the RJ31X phone block RESET...

Страница 18: ...rating See Power Supply in the Compliance Listing Guide LT 1330 for maximum current in a fire listed application Terminal 8 YELLOW Receives data from keypads and zone expansion modules It cannot be u...

Страница 19: ...n the protec tion zones are rated for use with this delay Zones 1 10 can also be programmed for a fast response delay of 160 milliseconds Keyswitch Arming Zone Using a keyswitch on an arming zone type...

Страница 20: ...l 431 Output Harness on the OUT1 OUT2 6 pin header Each relay provides one SPDT set of contacts that can be operated by any of the functions listed below Activation by zone condition Steady Pulsing Mo...

Страница 21: ...o the OUTPUTS header on the panel to provide relays for outputs 3 6 Use these relays for electrical isolation between the alarm panel and other systems or for switching voltage to control various func...

Страница 22: ...LX G 505 12LX R Batteries and Battery Accessories Batteries 365 9 0 Ah 12 VDC ORDER 365 366 18 0 Ah 12 VDC ORDER 366 368 5 0 Ah 12 VDC ORDER 368 369 7 0 Ah 12 VDC ORDER 369 341 Small Enclosure Steel k...

Страница 23: ...d zones 12 VDC supporting two wire smoke detectors or other fire alarm initiating devices Includes red 340 enclosure and EOL resistors ORDER 715 16 716 Output Expander Provides 4 programmable Form C S...

Страница 24: ...l 893A Module for XR150 XR550 Series control panels ORDER 277 277CAN 335 Intrusion Siren Offers dual tones steady and warble is load tested to four hours is indoor surface mounted and is made out of U...

Страница 25: ...trobe horns The cadence is dictated by the panel synchronizing the alarm tones of all wired and wireless devices ORDER 1164 W 1164NS W Wireless Smoke Detector with No Sounder Has the same functionalit...

Страница 26: ...by the ACTA See installation instructions for details The Ringer Equivalence Number REN is used to determine the number of devices that may be connected to a telephone line Excessive RENs on a teleph...

Страница 27: ...ANSI UL 294 Access Control System Units ANSI UL 1610 Central Station Burglar ANSI UL 2017 General Purpose Signaling Devices and Systems ANSI UL 864 Fire Protective Signaling Compatible with Devices li...

Отзывы: