General Configuration Screen
DLE28-MA User’s Guide
5-43
In STAND ALONE mode, the module is isolated from the chassis
configuration screens, and the module may not be accessed from a module
that is in DISTRIBUTED mode. This provides additional security for any
module to which the user may wish to restrict access.
Section 5.15.10
describes how to set the Management Mode.
Com (Toggle)
This field allows the user to enable or disable the COM port. The
selection toggles between ENABLED and DISABLED. The default is
ENABLED. For details about setting up the COM port, refer to
Section 5.15.11.
Application (Modifiable)
This field allows the user to set the application that the COM port will
support, which includes:
•
Local Management (LM) via a terminal or modem connection
(default)
•
Uninterruptible Power Supply (UPS)
The UPS setting allows the COM port to be used to monitor an American
Power Conversion Uninterruptible Power Supply (UPS). For UPS, the
baud rate is automatically set to 2400.
The baud rate setting for LM is automatically sensed.
For details about how to configure the COM port for various applications,
refer to Section 5.15.11.
Clear NVRAM (Toggle)
This allows the user to reset NVRAM to the factory default settings. All
user-entered parameters, such as IP address and Community Names are
then replaced with DLE28-MA default configuration settings. For details,
refer to Section 5.15.13.
Содержание DLE28-MA
Страница 1: ...DIGITAL MultiSwitch 700EL DLE28 MA Interface Module User s Guide...
Страница 2: ......
Страница 14: ......
Страница 28: ......
Страница 36: ......
Страница 50: ......
Страница 58: ......
Страница 182: ......
Страница 186: ......
Страница 194: ......
Страница 199: ......
Страница 200: ...9032616 Printed in U S A...