PS-2000B Series User Manual
Chapter 2 – Hardware Installation
2–7
Installation Area
• Avoid overheating of the PS-B by not installing the unit near other heat-produc-
ing devices.
• Keep the PS-B away from arc-generating devices such as magnetic switches
and non-fuse breakers.
• Avoid operating the PS-B in environments where corrosive gases are generated.
• To ensure maintainability, operability, and ventilation of the PS-B, be sure to
allow a minimum of 50mm clearance between the PS-B and adjacent structure
or equipment (70mm clearance is required to the side of a fan). Also, be sure to
include sufficient clearance by considering the size and shape of connectors
and space required for removing and inserting an expansion board while the
PS-B is in the installed position.
Installed Vertically
50
[1.97]
50
[1.97]
50
[1.97]
50[1.97]
50[1.97]
70[2.76]
Front View
Side View
Installed Horizontally
50[1.97]
50[1.97]
50[1.97]
50[1.97]
50[1.97]
70[2.76]
Front View
Side View
Attached to Wall/Side of Panel
50
[1.97]
50
[1.97]
50[1.97]
50[1.97]
70[2.76]
50[1.97]
50[1.97]
Front View
Side View
Unit: mm[in.]