Seite 23 von
71
Modbus RTU
Polarity independent: Connections 60 and 61
External power supply: 12-24 V AC/DC
Energy consumption: max. 150 mW
Connection 90 (not inverted, +)
Connection 91 (inverted, +)
Communications protocol: Modbus RTU
Channel EIA-485 (electrically isolated)
Flexible data format: Standard 9600 bits/s, 8N1, Modbus Slave ID-1
Fig. K
Modbus RTU Modul
LonWorks
Polarity independent: Connections 60 and 61
External power supply: 12-24 V AC/DC
Energy consumption: max. 150 mW
Polarity independent: Connections 96 (A) and 97 (B)
Channel TP/FT-10
Baud rate: 78: kbit/s
Data format: Differential Manchester encoding
electrically isolated
Fig. L
LonWorks module