Seite 15 von
71
Analogue module
The analogue module has the size of 2 standard modules and has two passive outputs with 4 to 20
mA. If one analogue module is mounted in the meter, no other module can be installed. The internal
radio is still working. The connection cable between the main pcb board and the module has to be
installed on port 1 (left slot). By default, the two analog outputs are not programmed, the values can
be programmed with the help of the software IZAR@Mobile2 (standard). The analogue module is
electrically isolated.
3.7 Tariff function
The meter has five flexible tariff function.
A tariff is a cumulating register, which starts accumulation after its defined function is valid.
The following tariff unit are selectable:
Energy
Volume
time
Different thresholds are definable for each tariff independently:
Tariff counter 1
Type gate
LCD text
T
T < Threshold
tz000y
T
T >= Threshold
tz010y
T
R
T
R
< Threshold
tz001y
T
R
T
R
>= Threshold
tz011y
T
F
T
F
< Threshold
tz002y
T
F
T
F
>= Threshold
tz012y
fix enable
tz003y
P
Power < Threshold
tz004y
P
Power >= Threshold
tz014y
F
Flow rate < Threshold
tz005y
F
Flow rate >= Threshold
tz015y
C
Based on time
tz006y
E
External controlled
tz007y
Example:
t
30K (tz010y) – accumulate power
Содержание SCYLAR INT 8
Страница 16: ...Seite 16 von 71 The meter accumulate the power to the defined tariff register when the function is active ...
Страница 19: ...Seite 19 von 71 4 Technical data 4 1 Dimensions Fig F Dimensions ...
Страница 67: ...Seite 67 von 71 13 Declaration of conformity ...
Страница 68: ...Seite 68 von 71 ...
Страница 69: ...Seite 69 von 71 ...
Страница 70: ...Seite 70 von 71 ...
Страница 71: ...Seite 71 von 71 ...