Seite 50 von
71
7.
Taking into operation
The calculator can be taken into operation together with the connected flow sensor once it has been
installed.
Proceed as follows:
Open the stop valves.
Check the system for leaks.
Carefully bleed the system.
Check the flow rate and temperature displays for plausibility.
Bleed the system until the flow rate display is steady. Regulate the system using the flow rate
display.
Seal the sensors.
Attach the seals to the calculator and temperature sensors.
Read the meter counts for energy, volume and operating hours.
Error messages for wrong installation:
Error
display
Meaning
E – 3
Temperature sensors reversed during installation or connection.
NOTE
If the system is idle, these error messages can appear even though the installation
has been carried out correctly.