25 

 

 

 

PARAMETER 

SYMBOL  SHORT DESCRIPTION 

UNIT  default  min  Max  step 

2.14 

RESPONSE 
FACTOR 

 RF 

Inverter reactivity factor  

The reactivity factor indicates the DGBOX response velocity, to return to set pressure, compared to 
pressure variations in the plant due to linked-unit withdrawal. 
The  values  that  can  be  selected  go  from  1  (slow  reaction,  suitable  for  large-inertia  plants  or  with 
possible  resonance  phenomena)  to  5  (very  fast  reaction,  suitable  in  case  of  fast  changes  in  system 
pressure). 

 

PARAMETER 

SYMBOL  SHORT DESCRIPTION 

UNIT  default  min  Max  step 

2.15  SWITCH FREQ 

 SF 

Inverter switching frequency  

kHz 

12 

The parameter defines the switch-over frequency of the inverter used to produce the waveform which 
will supply the motor. The switching frequency can be selected between 4 kHz and 12 kHz. 
This frequency, in the absence of a sinusoid electronic filter on the cable coming out of the motor, must 
be reduced together with any increase in the length of the cable itself. 

   

NOTE The length of the cable must not in any case exceed 10 m without the use of a sinusoid filter. 

 

PARAMETER 

SYMBOL  SHORT DESCRIPTION 

UNIT  default 

step 

2.16  PRESSURE UNIT   PU 

Pressure unit of measure   

bar 

PSI  bar 

The  parameter  permits  selecting  the  unit  of  measurement  of  the  pressure  displayed  on  the  display 
screen (bar or psi). 

 

PARAMETER 

SYMBOL  SHORT DESCRIPTION 

UNIT  default  min  Max  step 

2.17  ACCELERATION 

 ACC 

Speed of variation of frequency   

Hz/s 

20 

10 

40 

The parameter regulates the speed of variation of the inverter frequency and consequently the speed at 
which the pump switches to the required speed. 
Acceleration is represented in Hz/s (Hz per second) and indicates by how many Hz the speed of rotation 
of the pump varies within the unit of time.  

example: ACCELERATION = 25  
the parameter indicates a pump acceleration of 25 Hz per second. It follows that, starting with a state of 
pump stopped, it will take 2s to reach the speed of 50 Hz.  

This  parameter,  if  regulated  at  minimum  (10Hz/s)  permits  starting  pumps  with  large  inertia  (PD

2

without excessive current absorption at breakaway. 

NOTE. The parameter ACC is automatically changed when regulating the RF parameter (see parameter 
2.7  RESPONSE  FACTOR);  such  operation  is  performed  to  adapt  acceleration  to  device  response 
requirements.  

 

PARAMETER 

SYMBOL  SHORT DESCRIPTION 

UNIT  default 

min 

Max  step 

2.18  OFF FREQ. SP1 

 OF1 

Switch-off frequency with working 
pressure 1   

Hz 

40 

Fmin

**

  45 

0.1 

2.19  OFF FREQ. SP2 

 OF2 

Switch-off frequency with working 
pressure 2  

Hz 

40 

Fmin

**

  45 

0.1 

This parameter must be set only with operation without flow sensor

 (see -  FLOW SENSOR parameter 

3.13).  

The parameter defines the 

frequency below which it is considered there is no more flow request

 and 

therefore, after a time defined by the FLOW TIMEOUT parameter (see parameter 2.6 FLOW TIMEOUT) 
the pump must be stopped. 

the  frequency  below  which  it  is  considered  there  is  no  more  flow  request  (switch-off  frequency) 
depends on the selected work pressure. 

Содержание DGB MV 30

Страница 1: ...400V 8 3 4 DGB MV 55 3 400V 3 400V 14 5 5 7 5 DGB MV 75 3 400V 3 400V 18 7 5 10 DGB MVF 30 3 400V 3 400V 8 8 3 3 4 4 DGB MVF 55 3 400V 3 400V 14 14 5 5 5 5 7 5 7 5 DGB MVF 75 3 400V 3 400V 18 18 7 5...

Страница 2: ...default 50 Hz 11 Determination of the shutdown frequency 11 setting the full scale of the pressure sensor 11 Configuration of the flow sensor 11 CONTROL OF DRY RUNNING IN APPLICATIONS WITHOUT FLOW SE...

Страница 3: ...pumps if DGBOX is in operation before you disconnect the pumps stop the control and disconnect the power supply Emergency stop An emergency stop can be performed while the inverter is running by pres...

Страница 4: ...fuse carrier module 3 Inverter 1 output terminal board 4 contactor with thermal motor protection fixed speed pump ATTENTION set the protection of the thermal relay to the rated current of the pump 2 f...

Страница 5: ...CONFIG The max load which can be connected is 2 A at 250 Vac the cable must have 2 leads and a minimum cross section of 0 5 square mm MASTER SLAVE CONNECTIONS permits connection and communication wit...

Страница 6: ...e 5 sec waiting WORK mode if DGBOX was in ON condition at last switch off OUT OF SERVICE mode if DGBOX was in OFF condition at last switch off pressing START STOP OUT OF SERVICE mode suitable for manu...

Страница 7: ...rning 1 0 s OFF Freq 3 0 0 4 0 0 Hz OFF Frequency Bar 6 8 W IZA RD P 3 0 ENTER OFF Frequency 3 0 0 Hz COM PLETED 7 8 W IZA RD ENTER Push TEST f or start Self Learning M in P Fact or Learning 1 0 s ENT...

Страница 8: ...1 minimum cosphi 0 10 0 1 00 0 01 2 8 MIN POWERF2 x Pump 2 minimum cosphi 0 10 0 1 00 0 01 2 9 MIN POWERF3 x Pump 3 minimum cosphi 0 10 0 1 00 0 01 2 10 MIN POWERF4 x Pump 4 minimum cosphi 0 10 0 1 00...

Страница 9: ...SET 1 AND THE RATED CURRENT PUMP 1 CURRENT PRESSURE SET 2 PUMP 1 CURRENT PUMP 1 ROTATION BASE SETUP BASE SETUP PUMP 1 ROTATION PUMP 1 CURRENT PRESSURE SET 2 PRESSURE SET 1 1 1 4 0 Bar 1 0 9 0 SERIAL F...

Страница 10: ...SET 1 PRESSURE SET 2 PUMP 1 CURRENT PUMP 1 ROTATION BASE SETUP BASE SETUP PUMP 1 ROTATION PUMP 1 CURRENT PRESSURE SET 2 PRESSURE SET 1 1 4 SERIAL FIIRMW DIRECT 1 MAINTENANCE HARDWARE SETUP ADV SETUP...

Страница 11: ...frequency of minimum flow flow off IMPORTANT If the OFF FREQUENCY setting is too high this will cause the pump to stop while the request is still active and involve frequent restarts if the setting is...

Страница 12: ...ad geodetic Hg is the hydrostatic pressure resulting from the maximum water level in the system The parameter PD of the set pressure should NEVER be less than the positive delivery head otherwise the...

Страница 13: ...4 0 04 11 2011 15 02 410 V 2 7 A 30 0 HZ STOP START 31 0 HZ 2 8 A 410 V 15 02 04 11 2011 P 4 1 TEST 1 STOP 1 TEST P 4 1 04 11 2011 15 02 START STOP 15 02 04 11 2011 set 4 0 Bar P 4 1 1 2 OFF SYSTEM E...

Страница 14: ...SC ERROR P SENSE P SENSE ERROR there is no pressure sensor signal or this is outside the sensor range and therefore wrong DGBOX stops the system and indicates the P SENSE ERROR message PHASE ERROR INP...

Страница 15: ...all common failures over currents dry running etc It works in stand alone configuration or in parallel with other units through serial connection in parallel configuration with other units DGBOX make...

Страница 16: ...f DGBOX and work with only the second pump controlled by means of a mechanical pressure switch connected on the delivery pipe The EMERGENCY BOARD is activated by pushing the switch shown in Fig 2 3 be...

Страница 17: ...54 Working position vertical Fire explosion hazard DGBOX units are not suitable for use in environments with risk of explosion Environment temp max min 45 C 10 C Storage temp max min 50 C 10 C Voltage...

Страница 18: ...LE speed pump 1 FIXED speed pump MVF 30 MVF 55 MVF 75 2 VARIABLE speed pumps MW 30 2 VARIABLE speed pumps MV 55 SV 55 MV 75 SV 75 3 VARIABLE speed pumps MW 30 SV 30 3 VARIABLE speed pumps MV 55 2x SV...

Страница 19: ...rated power single pump 400 Va c kW 3 0 5 5 7 5 Maximum motor rated power single pump 230 V a c kW 1 7 3 0 4 0 Maximum current single pump A 8 0 14 0 18 0 input Three phase voltage V 400 10 230 10 fr...

Страница 20: ...e single pump flow rate expressed in litres min is quite adequate For example a unit equipped with pumps with a maximum flow rate of 200 l min single pump and standard application requires a tank with...

Страница 21: ...ters are returned to their normal values 4 OUT OF SERVICE to stop the system manually press the START STOP to manually disable the single pump select it and choose the option STOP 5 UPDATE By means of...

Страница 22: ...nsor see parameter 3 13 FLOW SENSOR together with the second work pressure P2 the parameter OFF FREQ SP2 must also be set This sets the stop frequency see parameter 2 19 OFF FREQ SP2 PARAMETER SYMBOL...

Страница 23: ...DESCRIPTION UNIT default min max step 2 1 RESTART DIFF DPr Restarting differential pressure bar 0 4 0 1 1 0 0 1 The DPr value determines the pump restart pressure given a certain set pressure P1 exam...

Страница 24: ...POWERF3 x Pump 3 minimum cosphi 0 1 0 1 0 0 01 2 10 MIN POWERF4 x Pump 4 minimum cosphi 0 1 0 1 0 0 01 The parameter configures the value of the electrical parameter COSPHI power factor corresponding...

Страница 25: ...7 ACCELERATION ACC Speed of variation of frequency Hz s 20 10 40 1 The parameter regulates the speed of variation of the inverter frequency and consequently the speed at which the pump switches to the...

Страница 26: ...FF FREQUENCY setting is too high this will cause the pump to stop while the request is still active and involve frequent restarts if the setting is too low this could cause the continuous operation of...

Страница 27: ...the HARDWARE SETUP parameters the function in the EXTENDED MENU must be used use of the menu protected by password is restricted to after sales centres or the factory 1 2 HARDWARE CONFIGURATION HARDWA...

Страница 28: ...he second operating pressure set in the PRESSURE SET 2 parameter the inactive signal switches back to the main PRESSURE SET 1 pressure 4 FLOW SIGN Auxiliary flow signal input this input configuration...

Страница 29: ...2 No 2 pressure sensors connected to the analog inputs 1 and 2 the pressure value is the difference between the value of pressure sensor 1 and the sensor value 2 difference the operating logic become...

Страница 30: ...IPTION UNIT default min max step 3 17 P SENS 1 CALIB x Calibration of pressure sensor 1 3 18 P SENS 2 CALIB x Calibration of pressure sensor 2 This parameters allow calibration or recalibration of the...

Страница 31: ...xample of the analysis of the parameters during an alarm is shown below EXTENDED MENU 4 1 SERIAL NUMBER ALARM HISTORY WORKING TIME SET DATA TIME MAINTENANCE 410 V 2 8 A 35 2 HZ 1 1 P 3 0 set 3 5 Bar 0...

Страница 32: ...FREQUENCY to which its performance will be consequently reduced The only operation which can be carried out is to manually INCREASE and subsequently DECREASE the work frequency see fig below to gradu...

Страница 33: ...ption for returning it to WORK mode 410 V 5 5 A 36 8 HZ 15 02 04 11 2011 set 4 0 Bar P 4 0 1 2 1 2 2 1 2 1 P 4 0 set 4 0 Bar 04 11 2011 15 02 00 0 HZ 0 0 A 410 V 2 1 584 Vb 0 05 37 49 C 1 2 STOP ENTER...

Страница 34: ...em off and back on The OUT OF SERVICE mode is that suggested to access the CONFIGURATION mode and is necessary to access the TEST mode Placing the single pump out of service this can be done by select...

Страница 35: ...ture below 3 close the front cover again and switch on DGBOX 4 after initialisation the BOOT LOADER display page appears see fig below HISTORY DOWNLOAD PARAMETER UP DOWN BOOT LOADER FIRMWARE UPDATE 5...

Страница 36: ...ile Size 266110 Byte WRITE SELECTED FIRMWARE PFLMUL 1 S19 FIRMWARE UPDATE 1 1 HISTORY DOWNLOAD PARAMETER UP DOWN BOOT LOADER FIRMWARE UPDATE Example 2 download the error message record history onto th...

Страница 37: ...TARTING phase the system switches to WORK mode and starts the pumps if a pressure is detected below that set see fig below FW 1 1 4 SN D B1 1 1 2 0 0 0 DGFLOW DGBOX DGFLOW DGBOX ST A RT IN G 5 5 sec 2...

Страница 38: ...is not braked check the correct direction of rotation Re arm is only manual by pressing ESC CURRENT LIMIT excessive overcurrent absorption short circuit Make sure the motor pump is not blocked reduce...

Страница 39: ...pump pressure is greater than the SET pressure Check that the pump is not worn or obstructed none The motor is faulty The motori s not connected Check the operation of the motor Check the Check for v...

Страница 40: ...null and void DISPOSAL For the disposal of DGBOX components follow the Standards and Laws in force in the countries where the unit is used Do not disperse pollutant parts in the environment DECLARATIO...

Отзывы: