11
CHECKING THE FREQUENCY OF ELECTRIC MOTOR (MOTOR FREQ – default 50 Hz)
Verify that the parameter MOTOR FREQ match the frequency of the motor plate (default 50 Hz)
PARAMETER
SYMBOL SHORT DESCRIPTION
UNIT
default min
Max step
2.2 MOTOR FREQ
MF
Motor frequency
Hz
50
50
60
10
CHECKING THE MAXIMUM OPERATING FREQUENCY (MAX FREQ - default 50 Hz)
Verify that the parameter MAX FREQ match the frequency of the motor plate (default 50 Hz)
IMPORTANT: the choice of exceeding the maximum frequency is the responsibility of the installer,
who must realise the consequences of raising the maximum frequency on the risks related to the
motor, to the pump and to the electrical system.
PARAMETER
SYMBOL SHORT DESCRIPTION
UNIT
default min
Max step
2.4 MAX FREQ
HiF
maximum operating frequency
Hz
50
40
70
1
SETTING THE OFF FREQUENCY (OFF FREQ. SP1) (operation without flow sensor)
Verify that the parameter OFF FREQ. SP1 (shutdown frequency) matches the frequency of minimum flow (flow
off).
IMPORTANT: If the OFF FREQUENCY setting is too high, this will cause the pump to stop while the
request is still active, and involve frequent restarts; if the setting is too low, this could cause the
continuous operation of the pump even at zero flow, with pump overheating and damage.
For more details on this parameter see part 2 of the manual (PART 2 - USER'S MANUAL)
PARAMETER
SYMBOL SHORT DESCRIPTION
UNIT
default
min
Max step
2.18 OFF FREQ. SP1
OF1
Switch-off frequency with working
pressure 1
Hz
40
Fmin
**
45
0.1
SETTING THE PRESSURE SENSOR FULL-SCALE (P SENSOR 1 F.S.)
In this parameters, the connected
pressure sensors full-scale
value is
entered ( analogue inputs 1), according to the table:
0
10 bar
1
16 bar
2
25 bar
3
40 bar
PARAMETER
SYMBOL SHORT DESCRIPTION
UNIT
default
min
max step
3.11 P SENSOR 1 F.S.
P1S
Pressure sensor n°1 range
-
0
0
3
1
SETTING THE FLOW SENSOR (FLOW SENSOR)
In the presence of a flow sensor (es. TEEVALVE) set the parameter FLOW SENSOR al to value 1
PARAMETER
SYMBOL SHORT DESCRIPTION
UNIT
default
min
max step
3.13 FLOW SENSOR
FwS
Set up of connected flow sensors
-
0
0
4
1