5.5.4.2.5.3 .application.channelTable.channelEntry.channelACInputStatus
OID:
.1.3.6.1.4.1.21035.34.2.5.1.3
.x
Syntax:
INTEGER {ok (1), warning (2), error (3)}
Access:
read-only
Description:
The status of the corresponding AC line, possible values:
"
1
"
ok, i.e. the AC line status is detected as being ok;
"
2
"
warning, i.e. the AC input is less than 102 V AC,
i.e. causing limited output performance;
"
3
"
error, i.e. the AC line status is detected as being not ok.
5.5.4.2.5.4 .application.channelTable.channelEntry.channelTempWarning
OID:
.1.3.6.1.4.1.21035.34.2.5.1.4
.x
Syntax:
INTEGER {ok (1), warning (2), error (3)}
Access:
read-only
Description:
The temperature status of the module, possible values:
"
1
"
ok, i.e. the temperature is detected as being ok;
"
2
"
warning, i.e. the temperature is high causing a warning;
"
3
"
error, i.e. the temperature exceeds 85 °C (185 °F).
5.5.4.2.5.5 .application.channelTable.channelEntry.channelFanStatus
OID:
.1.3.6.1.4.1.21035.34.2.5.1.5
.x
Syntax:
INTEGER {ok (1), error (3)}
Access:
read-only
Description:
The fan speed status of the module, possible values:
"
1
"
ok, i.e. the fan speed is detected as being ok;
"
3
"
error, i.e. the fan speed is detected as being not ok.
5.5.4.2.5.6 .application.channelTable.channelEntry.channelOutVoltageSet
OID:
.1.3.6.1.4.1.21035.34.2.5.1.6
.x
Syntax:
INTEGER (0..60000)
Access:
read-write
Description:
The output voltage set point of the module in [mV].
Note:
The output voltage of each power supply module can be set individually.
However, alterations on the value of a module will affect the setting of
this value for all installed modules; i.e. because the modules are in
parallel, it is pointless to adjust the modules to different values.
Note the default setting and the limits for adjusting this value; please
refer to chapter 4.3.1.
5.5.4.2.5.7 .application.channelTable.channelEntry.channelOutVoltage
OID:
.1.3.6.1.4.1.21035.34.2.5.1.7
.x
Syntax:
INTEGER (0..60000)
Access:
read-only
Description:
The measured output voltage of the module in [mV]