INSTALLATION

AIR FOR COMBUSTION AND VENTILATION

Continued

Figure 2 - Ventilation Air from Inside 

Building

Figure 3 - Ventilation Air from Outdoors

Outlet
Air

Ventilated
Attic 

Outlet
Air

Inlet
Air

Inlet Air

Ventilated 

Crawl Space

To 

Crawl

Space

To Attic

Or

Remove

Door into
Adjoining

Room,
Option

3

Ventilation Grills 

Into Adjoining Room,

Option 2

Ventilation

Grills Into

Adjoining 

Room,

Option 1

12"

12"

 WARNING: If the area in which 

the heater may be operated does 

not meet the required volume for 

indoor combustion air, combus

-

tion and ventilation air shall be 

provided by one of the methods 

described  in  the 

National  Fuel 

Gas Code, ANSI Z223.1/NFPA 54, 

the

 International Fuel Gas Code,

 

or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining 
unconfined  space.  When  ventilating  to  an 

adjoining unconfined space, you must provide 

two permanent openings: one within 12" of the 

ceiling and one within 12" of the floor on the 

wall connecting the two spaces (see options 1 

and 2, Figure 2). You can also remove door into 
adjoining room (see option 3, Figure 2). Fol

-

low the 

National Fuel Gas Code ANSI Z223.1/

NFPA 54, Air for Combustion and Ventilation

 for 

required size of ventilation grills or ducts.

Ventilation Air From Outdoors

Provide  extra  fresh  air  by  using  ventilation 
grills or ducts. You must provide two perma-
nent openings: one within 12" of the ceiling 

and one within 12" of the floor. Connect these 

items directly to the outdoors or spaces open 
to the outdoors. These spaces include attics 
and crawl spaces. Follow the 

National Fuel 

Gas  Code  ANSI  Z223.1/NFPA  54,  Air  for 
Combustion and Ventilation

 for required size 

of ventilation grills or ducts.

IMPORTANT:

  Do  not  provide  openings  for 

inlet or outlet air into attic if attic has a thermo-
stat-controlled power vent. Heated air entering 
the attic will activate the power vent.

NOTICE:  This  heater  is  intended 

for use as supplemental heat. Use 

this heater along with your primary 

heating system. Do not install this 

heater as your primary heat source. 

If you have a central heating system, 

you may run system’s circulating 

blower while using heater. This will 

help circulate the heat throughout 

the house. In the event of a power 

outage, you can use this heater as 

your primary heat source.

  WARNING:  Installation  and 

repair should be done by a quali

-

fied service person. The appliance 

should be inspected before use and 

at least annually by a professional 

service  person.  More  frequent 

cleaning may be required due to 

excessive lint from carpeting, bed

-

ding material, etc. It is imperative 

that control compartments, burners 

and circulating air passageways of 

the appliance be kept clean.

Содержание CSG3924NRA

Страница 1: ...not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical...

Страница 2: ...tallations in accordance with ANSI Z21 11 2 Exception Do not install this appliance in a factory built fireplace that includes instructions stating it has not been test ed or should not be used with u...

Страница 3: ...warnings Keep this manual for reference It is your guide to safe and proper operation of this fireplace WARNING Any change to this heater or its controls can be dangerous WARNING Do not use a blower i...

Страница 4: ...rmance problems with propane LP models do not use propane LP fuel tank of less than 100 lb capacity 20 Provide adequate clearances around air openings Keep the appliance area clear and free from combu...

Страница 5: ...ted decorative listing is required Local Codes Install and use heater with care Follow all local codes In the absence of local codes use the latest edition of The National Fuel Gas Code ANSI Z223 NFPA...

Страница 6: ...ing It requires no out side venting There is no heat loss out a vent or upachimney Heatisgeneratedbybothrealistic flames and glowing coals This heater is de signed for vent free operation with flue da...

Страница 7: ...s between the rooms 1 Determine the volume of the space length x width x height Length x Width x Height __________cu ft volume of space Example Space size 20 ft length x 16 ft width x 8 ft ceiling hei...

Страница 8: ...ventilation grills or ducts Ventilation Air From Outdoors Provide extra fresh air by using ventilation grills or ducts You must provide two perma nent openings one within 12 of the ceiling and one wit...

Страница 9: ...4 page 10 in high traffic areas in windy or drafty areas INSTALLATION Continued CAUTION This heater cre ates warm air currents These currents move heat to wall sur faces next to heater Installing heat...

Страница 10: ...if noncombus tible material is more than 12 you may need the hood accessory to deflect heat away from your mantel shelf See Figures 5 and 6 page 11 and Figure 7 page 12 for minimum clearances IMPORTA...

Страница 11: ...Fireplace Figure 6 Minimum Mantel Clearances Without Using Hood Minimum Noncombustible Material Minimum Noncombustible Material Height Distances to Underside of Mantel Top of Fireplace Opening Undersi...

Страница 12: ...rly these temperatures meet the requirement of the national product standard Follow all minimum clearances shown in this manual NOTICE Ifyourinstallationdoes not meet the minimum clear ances shown you...

Страница 13: ...t free operation 2 State or local codes do not permit vent free operation 3 You prefer vented operation If reasons number 1 or 2 above apply to you you must permanently open chimney flue damper You mu...

Страница 14: ...unting bracket see Figure 12 If installing in a brick bottom fireplace mark screw locations in mortar joint of bricks 8 Remove heater base from fireplace If installing optional control accessories do...

Страница 15: ...inting Down Installation must include a equipment shutoff valve union and plugged 1 8 NPT tap Locate NPT tap within reach for test gauge hook up NPT tap must be upstream from heater see Figure 14 IMPO...

Страница 16: ...shutoff valve to gas supply Check reconnected fittings for leaks Test Pressures Equal To or Less Than 1 2 PSIG 3 5 kPa 1 Close equipment shutoff valve see Fig ure 15 2 Pressurize supply piping system...

Страница 17: ...ording to the log installation instructions in this manual Flames contact ing logs will create soot It is very important to install the logs exactly as instructed Do not modify logs Only use logs supp...

Страница 18: ...hing Grate to Base Assembly Logs and Base Will Vary According to Model Grate Slots in Base Adding lava Rock Place lava rock around base of heater if de sired Be sure not to cover the control knobs or...

Страница 19: ...ct the appliance and to replace any part of the control system and any gas control which has been under water LIGHTING INSTRUCTIONS WARNING If fireplace has glass doors never operate this heater with...

Страница 20: ...burner If needed keep pressing ignitor button until pilot lights Note If pilot does not stay lit contact a qualified service person or gas supplier for repairs Until repairs are made light pilot with...

Страница 21: ...nob clockwise to the OFF position 2 Turn rear burner control knob clockwise to the OFF position 3a Set selector switch in the OFF position 3b If Using Optional Hand Held Remote Set selector switch in...

Страница 22: ...hand held remote to control the room temperature If the hand held remote is misplaced obstructed or for any reason cannot transmit to the receiver the receiver will shut off the fireplace This will oc...

Страница 23: ...t cool before cleaning CAUTION Youmustkeepcon trol areas burner and circulating air passageways of heater clean Inspect these areas of heater before each use Have heater inspected yearly by a qualifie...

Страница 24: ...ssembly see Figure 35 With the unit off lightly blow air through the air inlet hole The access hole for propane LP pilot is on the front of the burner carriage as shown in Figure 35 The access hole fo...

Страница 25: ...en in stalled 5 Depleted gas supply pro pane LP only 6 ODS pilot is clogged 7 Gas regulator setting is not correct OBSERVED PROBLEM Whenignitorbuttonispressed there is no spark at ODS pilot Whenignito...

Страница 26: ...er 1 Contact local natural or propane LP gas company 2 Clean burner s see Clean ing and Maintenance page 23 or replace burner orifice s 3 Contact qualified service person 1 Clean burner see Cleaning a...

Страница 27: ...local natural or propane LP gas company 3 Observeminimuminstallation clearances see page 8 4 Clean burners see Clean ing and Maintenance page 23 1 Turn heater off when us ing furniture polish wax car...

Страница 28: ...see Checking Gas Con nections page 16 1 Open window and or door for ventilation 2 Contact local natural or propane LP gas company 3 Clean ODS pilot see Cleaning and Maintenance page 23 1 Locate and co...

Страница 29: ...e control valve must be connected exactly as shown Specifications CSG3924PRA 10 000 40 000 Btu hr Type Gas Propane LP Ignition Piezo Manifold Pressure 8 W C Inlet Gas Pressure in of water Maximum 14 W...

Страница 30: ...com 123639 01D 30 Parts Remote Ready Models CSG3924NRA and CSG3924PRA 1 16 2 18 11 22 Items 12 22 Natural Gas Models Only 12 20 28 24 32 32 32 32 32 32 7 27 21 30 19 31 29 5 6 4 14 23 25 3 10 26 21 15...

Страница 31: ...r 1 15 098271 10 Ignitor Cable 1 16 099056 18 Burner Orifice Injector Back 1 099056 21 Burner Orifice Injector Back 1 17 101004 02 Burner Orifice Injector Front 1 101004 18 Burner Orifice Injector Fro...

Страница 32: ...erial numbers of your heater how heater was malfunctioning purchase date Service Hints When Gas Pressure Is Too Low pilot will not stay lit burners will have delayed ignition fireplace will not produc...

Страница 33: ...mostati cally controlled mode You can turn the gas log heater on and off without ever leaving the comfort of your easy chair A wall mount docking station is included RECEIVER AND HAND HELD REMOTE CONT...

Страница 34: ...__ ______________________________________________________ ______________________________________________________ ______________________________________________________ ________________________________...

Страница 35: ...__ ______________________________________________________ ______________________________________________________ ______________________________________________________ ________________________________...

Страница 36: ...proved by DESA Heating LLC Warranty parts must be obtained through authorized dealers of this prod uct and or DESA Heating LLC who will provide original factory replacement parts Failure to use origin...

Отзывы: