- 39 -
action
warning
turn OFF
the circuit
breaker
Stop the
engine
indicate by
warning
lamp
function
oil pressure failure
(OIL PRESS.)
–
–
※
set point: 300kPa
–
stop
set point: 200kPa
high jacket water
temperature
(WATER TEMP.)
–
–
※
set point: 103°C
–
stop
set point: 108°C
Battery charging
failure
–
–
※
set point: 26.0V
overcurrent of
generator
–
–
When overcurrent flows, the
device acts.
fuel level failure
(FUEL LEVEL)
(Optional apparatus)
–
–
When fuel supply is necessary
because of fuel shortage, the
device acts.
air filter blinding
(AIR FILTER)
–
–
–
When replace or cleaning of
air filter is necessary because
of blinding of filter, the device
acts.
over speed of engine
(OVER SPEED)
–
stop
–
set point: 2140 min
-1
coolant level failure
– stop
When coolant supply is
necessary because of coolant
shortage, the device acts.
Table of protection device
※
Abnormal value and unit will be indicated lighting on and off.