28
I/O Port Registers
Refer to the following four tables to configure the PowerScout’s two I/O ports.
Modbus
Register
Offset
Register Name
Detailed Description
44400
4399
I/O port 1 status
0 = input LOW (switch is closed)
1 = input HIGH (switch is open)
45100
5099
Configures the pulse input for
I/O port 1
0 = off, pulse input disabled
1 = rising edge, pulse counter increments, falling
edges are ignored. If pulse output is enabled, it
is disabled when this configuration is set.
2 = falling edge, pulse counter increments, rising
edges are ignored. If pulse output is enabled, it
is disabled when this configuration is set.
3 = both edges pulse counter increments. If pulse
output is enabled, it is disabled when this
configuration is set. (Note when pulse is off,
I/O control is enabled)
Setting this register to a value other than 0, forces
register 45110 to 0.
45101
5100
I/O port 1 pulse input
accumulator LSW
Scaled pulse LSW
45102
5101
I/O port 1 pulse input
accumulator MSW
Scaled pulse MSW
45103
5102
I/O port 1 pulse input scaling
(integer)
Integer scale factor
(Scale = 45103 + 45104/1000)
45104
5103
I/O port 1 pulse input scaling
(decimal)
x1000 decimal fraction of scale factor
Table VI-3: I/O Port 1 Pulse Input
Modbus
Register
Offset
Register Name
Detailed Description
44401
4400
I/O port 2 status
0 = input LOW (switch is closed)
1 = input HIGH (switch is open)
45200
5199
Configures the pulse input for
I/O port 2
0 = off, pulse input disabled
1 = rising edge, pulse counter increments, falling
edges are ignored. If pulse output is enabled, it
is disabled when this configuration is set.
2 = falling edge, pulse counter increments, rising
edges are irnored. If pulse output is enabled, it
is disabled when this configuration is set.
3 = both edges pulse counter increments. If pulse
output is enabled, it is disabled when this
configuration is set. (Note when pulse is off,
I/O control is enabled)
Setting this register to a value other than 0, forces
register 45210 to 0.
45201
5200
I/O port 2 pulse input
accumulator LSW
Scaled pulse LSW
Содержание PowerScout 3
Страница 19: ...15 Figure IV 1 Single Phase Two Wire N white L1 black L2 red L3 blue ...
Страница 20: ...16 Figure IV 2 Single Phase Three Wire N white L1 black L2 red L3 blue ...
Страница 21: ...17 Figure IV 3 Three Phase Three Wire Delta N white L1 black L2 red L3 blue ...
Страница 22: ...18 Figure IV 4 Three Phase Four Wire Wye N white L1 black L2 red L3 blue ...
Страница 23: ...19 Figure IV 5 Three Phase Four Wire Delta N white L1 black L2 red L3 blue ...