21
Realtime Values
The
Realtime
Values
screen displays the
current readings for verifying the system is
configured properly.
Element
– The PowerScout 3 is a single meter
and cannot be changed from Element A.
The table in the middle section of the screen
displays the
Phase A
,
Phase B
and
Phase C
for
the real-time values of Volts, Amps, KW and
others for Phase A, Phase B and Phase C.
You may view, in real time, values such as
Volts
,
Amps
and
KW
. This screen also displays
the current Data Scalar Value, the CT Type
connected to the PowerScout and CT Value.
Data Scalar
– A scalar is used to multiply the
raw data value to convert information read
from the modbus registers. Refer to Table III-1
for a list of values. Example: If the scalar value
in register 44602 is set to 3 and the total true
power for the system (kW) is read from
modbus register 44003 (Offset 4002) and a
value of 3465 is returned, the true system kW
is:
3465 X 0.1 = 346.5 kW
CT Type
– Displays the CT selected on the
CT Values
screen. This needs to match the CT connected to
the PowerScout.
CT Amperage Rating
– Displays the amperage rating entered on the
CT Values
screen.
Auto Update
– Select the checkbox to automatically update approximately every 15 seconds.
Update
button retrieves the values from the PowerScout.
The
Status
window displays communication messages.
Содержание PowerScout 3
Страница 19: ...15 Figure IV 1 Single Phase Two Wire N white L1 black L2 red L3 blue ...
Страница 20: ...16 Figure IV 2 Single Phase Three Wire N white L1 black L2 red L3 blue ...
Страница 21: ...17 Figure IV 3 Three Phase Three Wire Delta N white L1 black L2 red L3 blue ...
Страница 22: ...18 Figure IV 4 Three Phase Four Wire Wye N white L1 black L2 red L3 blue ...
Страница 23: ...19 Figure IV 5 Three Phase Four Wire Delta N white L1 black L2 red L3 blue ...