Chapter 4 Parameters
|
VFD-L-I Series
Revision July 2009, SW V1.1
4-37
06-02
Over-Torque Detection Mode (OL2)
Factory Setting: 0
Settings
0
Over-Torque detection disabled.
1
Enabled during constant speed operation. After the over-torque is
detected, keep running until OL1 or OL occurs.
2
Enabled during constant speed operation. After the over-torque is
detected, stop running.
3
Over-Torque detection enabled during running, and continues to run
till OL1 or OL.
4
Enabled during running. After the over-torque is detected, stop
running.
output curr ent
over- curr ent
detec ti on level
output
frequency
over- curr ent stall pr evention during acceleration
Time
output curr ent
out put curr ent
over- curr ent
detec ti on level
over- curr ent stall pr evention during oper ation
Time
Time
06-03
Over-Torque Detection Level
Unit: 1
Settings
30 to 200%
Factory Setting: 150
This setting is proportional to the Rated Output Current of the drive.
06-04
Over-Torque Detection Time
Unit: 0.1
Settings
0.1 to 10.0 sec
Factory Setting: 0.1
If a Multi-function Output Terminal is set as Over-Torque Detection Indication and the output
current exceeds the Over-Torque Detection Level (Pr.06-03, Factory Setting: 150%), the
Over-Torque Detection Time (Pr.06-04, Factory setting: 0.1) and the setting of multi-function
terminal is Over-Torque Detection Indication, the contact will be “close”. Refer to Pr.03-03 for
details.
06-05
Electronic Thermal Overload Relay Selection
Factory Setting: 0
Settings
0
Disabled
1
Standard
Motor
2
Special
Motor
Содержание VFD-L-I Series
Страница 1: ...PLC1 ir...
Страница 2: ......
Страница 3: ......
Страница 5: ...This page intentionally left blank...
Страница 91: ...Chapter 6 Troubleshooting VFD L I Series 6 6 Revision July 2009 SW V1 1 This page intentionally left blank...
Страница 99: ...Appendix A Specifications VFD L I Series A 2 Revision July 2009 SW V1 1 This page intentionally left blank...